For the Allen-Bradley 2755-DS
Page 1
Application Note Bulletin 2755 Bar Code Decoder to PLC-5/30/40/60
A–B
ALLEN-BRADLEY
Bulletin 2755 Bar Code Decoder to PLC-5/30/40/60 ASCII User Port Application Note Overview
The New Generation processors from Allen–Bradley have a user port that can be used to interface a single point Series 2755 Bar Code Decoder using either RS-232 or RS-422 communication. This document includes cable diagrams for a variety of Bulletin 2755 bar code decoders, configuration information for the 2755-DS/DD decoder, as well as an example program necessary to establish communication through User Port 0 on the PLC-5 platform.
Hardware Requirements
Implementation of the procedure described in this application note requires the following Allen-Bradley hardware:
• • • • •
2755-DS/DD Enhanced Bar Code Decoder and related manuals. Bulletin 1785 PLC-5 processor. Bulletin 1771 rack. Bulletin 1771 power supply. Appropriate cables to program the PLC-5 and configure the Bulletin 2755 bar code decoder. Refer to hardware manuals for cable requirements. • Catalog Number 1478-KT card installed in your personal computer to enable you to program the PLC-5.
Software Requirements
Implementation of the procedure described in this application note requires the following Allen-Bradley software:
• Bulletin 6200 development software for the PLC-5. • Terminal Emulation Package (such as or Terminal) to configure the 2755 DS/DD with a personal computer.
1
Page 2
Application Note Bulletin 2755 Bar Code Decoder to PLC-5/30/40/60
Related Publications
This document refers to the following publications, which should be available for reference while working through this application note: Publication Number 1785-XXX 6200-XXX
Title User Manual for your PLC-5 Programming Manual for your PLC-5 Bulletin 2755-DS/DD Series B Enhanced Decoder User Manual
2755-833
Configuration
For this application the PLC-5 occupies the PLC slot in a 1771 rack. Power is supplied externally or from an internal power supply installed in any acceptable slot in the 1771 rack. Figure 1 Configuring PLC-5 to Bulletin 2755 DS/DD Bar Code Decoder Bulletin 1771 Chassis
User Port 0
Power Supply
PLC-5
RS-232 or RS-422 Host Port
Scan Head Bulletin 2755 DS/DD Bar Code Decoder
Cabling Cabling connecting the Host port of the Bulletin 2755–DS/DD Enhanced Bar Code Decoder to User Port 0 on the PLC-5 must be constructed. For RS-422 installations, a special pinout cable must be constructed. Refer to the figures below for cabling diagrams.
2
Page 3
Application Note Bulletin 2755 Bar Code Decoder to PLC-5/30/40/60
Figure 2 RS-232 Cable Diagrams (PLC-5 to 2755 Bar Code Decoder) PLC-5/30, /40, /60 User Port 0
2755-DM6/9 DD/DS NEMA1
2 3 7
3 2 7
PLC-5/30, /40, /60 User Port 0
2755-DD/DS NEMA4
2 3 7
B C D
Figure 3 RS-422 Cable Diagrams (PLC-5 to 2755 Bar Code Decoder) PLC-5/30, /40, /60 PIN
2755-DS/DD Bar Code Decoder NEMA 1 NEMA 4 PIN PIN
2 TXD+
RXA– –16
S
14 TXD–
RXB+ –17
T
3 RXD+
TXA– –16
R
16 RXD–
TXB+ –16
P
18 19
Terminators
U Note: Maximum run length 200 feet
V
PLC-5 Configuration Set the PLC-5 “Channel 0” to USER as shown in the Channel Overview screen illustrated in Figure 4. Configure Channel 0 as shown in the User Mode Channel 0 Configuration illustrated in Figure 5. Note that Termination 1 is set for \0xd or Carriage Return [CR], and ’Termination 2” is set for \0xa or Line Feed [LF]. These terminators, along with the ARL instruction in the PLC-5, allow the User port to read in one message at a time with [CR] [LF] terminators.
3
Page 4
Application Note Bulletin 2755 Bar Code Decoder to PLC-5/30/40/60
Figure 4 Channel Overview Screen Channel Overview
Channel 0
USER
Channel 1A: Channel 1B:
DH+ SCANNER MODE
Channel 3A:
UNUSED
Press a function key or enter a value.
Rem RUN Forces: None Channel Config F5
Accept Edits F1
5/30 Addr 1 BAR_CODE Channel Status F7
Select Option F10
Figure 5 Channel O Configuration Screen User Mode Channel 0 Configuration Diag. file: Remote mode change: Mode attention char.: Baud rate: Stop bits: Control line:
0 DISABLED \0x1b
XON/XOFF: System mode char.: User mode char.:
DISABLED S U
9600 1 NO HANDSHAKING
Parity: Bits per Character:
NONE 8
Echo/Delete mode: Termination 1: Termination 2:
DISABLED \0xd \0xa
RTS send delay (20 ms): RTS off delay (20 ms): Append 1: Append 2:
0 0 \0xd \0xa
Press a function key or enter a value.
Rem RUN Accept Edits F1
4
Forces: None
5/30 Addr 1 BAR_CODE Chan 0 Select Status Option F9 F10
Page 5
Application Note Bulletin 2755 Bar Code Decoder to PLC-5/30/40/60
2755-DS/DD Enhanced Bar Code Decoder Configuration An example configuration for the 2755-DS/DD Bar Code Decoder appears in Figure 6 and Figure 7. Notice that the END MESSAGE is set to [CR] [LF]. Note that the settings illustrated below represent only part of the configuration required for the 2755-DS/DD Enhanced Bar Code Decoder to work in a given application. Refer to the decoder documentation for complete details on decoder configuration. Figure 6 2755-DS/DD Host Communications Configuration Screen.
Figure 7 2755-DS/DD Host Message Format Configuration Screen.
5
Page 6
Application Note Bulletin 2755 Bar Code Decoder to PLC-5/30/40/60
PLC-5 Program The sample ladder logic listing appearing in Figure 8 below instructs the PLC-5 to:
• Rung 2:0 – Read one string of ASCII data terminated with a [CR] [LF]. • Rung 2:1 – Based on the done bit from the ASCII Read Line instruction in run 0, move the string data into an integer file in the PLC-5 data table. Note: The Length variable in the Copy File instruction is set to 12. This value includes a leading word indicating string length, ten words of bar code data, and one word for the [CR] [LF] terminator. Figure 8 Sample PLC Ladder Listing. 3 August 1994 Page 1 Program Listing Report PLC–5/30 File 2_51F6_8 Rung 2:0 Rung 2:0 | R6:23 +ARL––––––––––––––––––––+ | +––]/[––––––––––––––––––––––––––––––––––––––––––+ASCII READ LINE +–(EN)–+ | DN |Channel 0| | | |Dest ST52:72+–(DN) | | |Control R6:23| | | |String Length 0+–(ER) | | |Characters Read 0| | | +–––––––––––––––––––––––+ | Rung 2:1 | R6:23 +COP–––––––––––––––+ | +––] [––––––––––––––––––––––––––––––––––––––––––––––––––––+COPY FILE +–+ | DN |Source #ST52:72| | | |Dest #N7:10| | | |Length 12| | | +––––––––––––––––––+ | Rung 2:2 | | +––––––––––––––––––––––––––––––––[END OF FILE]–––––––––––––––––––––––––––––––––+ | |
Refer to your PLC-5 Instruction Reference Manual for detailed information on using the PLC-5 programming software.
6
Page 7
Application Note Bulletin 2755 Bar Code Decoder to PLC-5/30/40/60
Running the Application
Refer to Figure 9 for an example of a bar code data string in the ASCII file, and to Figure 10 for an example of the resulting data table. Figure 9 PLC-5 ASCII File. STRING TEXT ADDRESS ST52:69
LEN 0
ST52:70
0
ST52:71
0
ST52:72
22
NO READ THIS LIGHTER^M^J
Press a function key or enter a value.
ST52:72 = Rem RUN
Forces: None
Data:Decimal
Change Radix F1
Edit String F3
Specify Address F5
Addr:Decimal 5/30 Addr 1 BAR_CODE Next File F7
Prev File F8
Figure 10 PLC-5 Data Table After Copy (“COP”) Instruction. ADDRESS N7:0 N7:10 N7:20 N7:30 N7:40 N7:50 N7:60 N7:70 N7:80 N7:90
0 1 2 3 4 5 6 7 8 9 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\16 N O R E A D T H I S L I G H T E R \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\00 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16 \00\16
Press a function key or enter a value.
N7:10 = RUN
Change Radix F1
Forces: None
Data:ASCII Specify Address F5
Addr:Decimal 5/30 Addr 1 BAR_CODE Next File F7
Prev File F8
7
Page 8
PLC and PLC-5 are registered trademarks of Allen-Bradley Co., Inc., a Rockwell International Company Windows is a trademark of Microsoft Procomm is a registered trademark of Datastorm Technologies, Inc.
Allen-Bradley has been helping its customers improve productivity and quality for 90 years. A-B designs, manufactures and supports a broad range of control and automation products worldwide. They include logic processors, power and motion control devices, man-machine interfaces and sensors. Allen-Bradley is a subsidiary of Rockwell International, one of the world’s leading technology companies.
With major offices worldwide. Algeria • Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • New Zealand • Norway • Oman • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Switzerland • Taiwan • Thailand • The Netherlands • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia World Headquarters, Allen-Bradley, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 2755-2.51 – September 1994 Copyright 1994 Allen-Bradley Company, Inc. Printed in USA