Page 51

Chapter 3. Operation

LEDs Network Status LEDs The network status LEDs display the operational condition of the network interface located on the controller board in the unit. LED Display

Color

Indicates that...

OK

Green

The operation is in the normal mode and no errors have been detected.

Test

Yellow

The network interface is operating in a test mode. This includes a self-test or a test loopback. When lighted, this LED also indicates that normal data flow is not occurring on the network interface.

Error

Red

An error has occurred, such as a BPV, OOF, or CRC.

Alarm

Red

An alarm condition has been detected. Any alarm condition will activate the alarm relay for the external alarm device. When the alarm condition is no longer valid, the OK LED activates (turns on). To view an alarm condition, select the active alarm menu item.

If the alarm conditions have been corrected, the alarm which caused the activation of the Alarm LED can be viewed under the UNIT HISTORY menu.

61202156L2

TDU 120e User Manual

3-9

Page 52

Chapter 3. Operation

Port Status LEDs

LED Display

Color

Indicates that...

OK

Green

The operation is in the normal mode and no errors have been detected.

Test

Yellow

One of the interfaces is operating in a test mode. This includes a self-test or a test loopback. When lighted, also indicates that normal data flow is not occurring in at least one of the module ports.

Alarm

Red

An alarm condition has been detected. Any alarm condition will activate the alarm relay for the external alarm device. When the alarm condition is no longer valid, the OK LED activates (turns on). To view an alarm condition, select the active alarm menu item.

If the alarm conditions have been corrected, the alarm which caused the activation of the Alarm LED can be viewed under the UNIT HISTORY menu.

Port 1.1 Option Card Monitor Jacks These are used to connect option cards to the computer.

3-10

TDU 120e User Manual

61202156L2

Page 53

Chapter 3. Operation

ALTERNATE METHODS OF CONTROL T-Watch PRO (ADTRAN PC Program) T-Watch PRO is the ADTRAN PC control program. It provides complete control over the configuration of the TDU 120e using a graphical interface. The T-Watch PRO program displays the same status and performance data as the terminal screen. This data is displayed in tables and graphs. The T-Watch PRO program has the following capabilities: •

Interfaces with a modem which permits dialing into a remote TDU 120e location to configure the unit or read the status or performance of the unit.

•

Receives traps from any TSU product.

•

Records and creates display performance data over a 30-day period.

•

Accesses units via the local area network (LAN).

Setting up the TDU 120e to Work over a LAN To set up the TDU 120e to work with T-Watch PRO over the LAN, follow these steps:

61202156L2

Step

Action

1

Set the Unit ID using the Front Panel. See Unit ID on page 6-3 for details.

2

Set control port interface to Normal (10BaseT) or SLIP (chain-in port).

3

Configure the IP address, default gateway, and subnet mask.

4

Follow the installation instructions for T-Watch PRO to start the program and connect to the unit.

TDU 120e User Manual

3-11

Page 54

Chapter 3. Operation

Setting up the TDU 120e to Work over an EIA-232 Connection To set up the TDU 120e to work with T-Watch PRO over a direct EIA-232 connection, follow these steps: Step

Action

1

Set the Unit ID and set a passcode. See page 6-3.

2

Set the control port rate to the same setting as the PC Com port.

3

Connect the PC Com port to the Chain-In port on the TDU 120e using the DB-25 adapter and modular cable provided.

4

Follow the installation instructions for T-Watch PRO to start the program and connect to the unit.

SNMP The ADTRAN TDU 120e supports the Simple Network Management Protocol (SNMP) through the 10BaseT or chain in (SLIP) interface. See Appendix A, Understanding SNMP, for more information. To use SNMP with the TDU 120e, follow these steps: Step

Action

1

Set the control port to either Normal (10BaseT) or SLIP (Chain-in port).

2

Set the IP address, default gateway, and subnet mask through the front panel.

3

Load the appropriate MIB browser into the Network Management Station. The MIB browser issues SNMP and sets the TDU 120e. See the ADTRAN webpage at: http://www.adtran.com.

3-12

TDU 120e User Manual

61202156L2

Page 55

Chapter 4

Status Menu

STATUS The STATUS menu branch allows you to view the status of the TDU 120e operation. See Figure 4-1.

1) NETWORK (NI) PERFORMANCE REPORTS 2) NETWORK (NI) ERRORS

%AS %EF ES SES UAS

NETWORK (NI) RED ALARM LOSS OF SIGNAL END OF LIST

1)STATUS 3) ACTIVE ALARMS 4)VIEW HISTORY

(HISTORY LIST) END OF HISTORY

5) PORT STATUS

Nx/DBU (0.1)

6) REMOTE PORT

7) CLEAR PORT ALARM

DS-1 (0.2) (OPTION LIST)

1) DTE DATA CLOCK 2) DTE STATUS 3) DTE PORT RATE 4) DBU DATA/CNTRL 5) DBU CONTROL 6) DBU STATUS DS-1 ERRORS

8) ETHERNET STATUS

Figure 4-1. Status Menu Tree Menu flow is depicted from left to right. At every level of the menu, pressing ESCAPE returns the system to the previous menu level. Press ESCAPE repeatedly to return the system to the main menu.

61202156L2-1

TDU 120e User Manual

4-1

Page 56

Chapter 4. Status Menu

Network (NI) Performance Reports The NETWORK INTERFACE PERFORMANCE REPORTS (see Figure 4-2) display the performance data. The TDU 120e maintains this performance data on the network in compliance with ANSI T1.403 and AT&T document TR54016. The data displayed is data accumulated over the last 15 minutes and over the last 24 hours. Where

Means

%AS Percentage of available seconds %EF Percentage of error free seconds ES Number of errored seconds (1 or more errors/second) SES Number of severely errored seconds (more than 320 errors/second) UAS Number of unavailable seconds (10 or more consecutive seconds) Figure 4-2. Network Interface Performance Report

If insufficient time has passed to collect data, NA displays. Continue with standard operating procedures to exit the display.

4-2

TDU 120e User Manual

61202156L2-1

Page 57

Chapter 4. Status Menu

Network Interface (NI) Errors The NI Errors submenu displays the types of errors the Network Interface (NI) detects. A blinking CSU error LED indicates that network errors are detected. The asterisk (*) above an item indicates the type of errors detected. The error types are listed below: CRC CRC-6 bit errors based on the FDL. This is valid only in ESF mode. BPV Bipolar violations XSO Excess zeros FER Framing errors

Active Alarms This menu item displays a list of current alarms reported by either the base controller or any of the ports. If no alarms are current, using this menu item displays END OF LIST. This display (see Table 4-1 on page 4-4) includes two text fields. The left field is the alarm source. The right field is the alarm message. A list of alarm messages is found in Appendix C, System Messages. If one or more of the Alarm LEDs are illuminated, an alarm is present. Press Escape to return to the previous menu item

61202156L2-1

TDU 120e User Manual

4-3

Page 58

Chapter 4. Status Menu

Table 4-1. Alarm Message Display Active Alarms Network (Ni) Red Alarm Loss Of Signal End Of List

View History This menu item both displays and clears the accumulated status changes of the unit. VIEW HISTORY displays a history of the last 20 status changes in the unit, including the date, time, and type of change. The unit also records for viewing the date and time an alarm became active and inactive, as well as the date and time of test activation and deactivation. To clear the VIEW HISTORY display, press C.

Port Status PORT STATUS displays the signals monitored on the data ports. For example, the Nx/DBU interface monitors the RTS, CTS, RD, and RD, along with other signal lines. When a port is selected, the terminal indicates if the signal is present. The base Nx interface shows the status screen listed in this section. When using other option cards, refer to the appropriate separate manual for a definition of any status screens offered. The PORT STATUS of Nx/DBU shows how to use this item.

4-4

TDU 120e User Manual

61202156L2-1

Page 59

Chapter 4. Status Menu

Nx/DBU (0.1) Menu Items DTE Data/Clock An asterisk (*) indicates an active status of the following lines:

TXD Transmit data from the DTE RXD Receive data toward the DTE XSO Excess zeros from the DTE LCK Lock status of the phase locked loop DTE Status An asterisk (*) indicates an active status of the following lines:

RTS Request to send from DTE CTS Clear to send to DTE DCD Data carrier detect to DTE DSR Data set ready to DTE DTE Port Rate The PORT RATE displays the current setting of the Nx port. Continue with standard operating procedures to exit the display.

61202156L2-1

TDU 120e User Manual

4-5

Page 60

Chapter 4. Status Menu

DBU Data/CNTRL An asterisk (*) indicates an active status on the following lines:

TXD Transmit data to the DCE RXD Receive data from the DCE DCD Data carrier detect from the DCE RI Ring indicate from the DCE DBU Control An asterisk (*) indicates an active status on the following lines:

RTS Request to send the DCE CTS Clear to send from the DCE DTR Data terminal ready to the DCE DSR Data set ready from the DCE DBU Status

DBU SECS Total seconds in current DBU session IN DBU YES/NO indication of active DBU status

4-6

TDU 120e User Manual

61202156L2-1