Page 53
AXIOM™ / AXIOM-X™ Product Line Manual
Electrical Installation
Polarity Check After completing the power connection, and before connecting other devices to the wiring base, be sure to perform a polarity check. When power is applied to the wiring base, other devices wired to it (i.e., tachometer and photoeye) could be damaged if the power polarity is reversed. ATTENTION: While performing the polarity check, be sure to follow all safety procedures regarding high-voltage as outlined in Chapter 2, Safety. Before correcting a polarity problem, be sure to disconnect the power source. IMPORTANT: After completing power connections, check Polarity LED inside the wiring base. A GREEN LED indicates polarity is correct. When more than one AXIOM-X are daisy-chained together, check polarity in the correct sequence.
Location of Polarity LED in Wiring Base 1. Apply power. 2. Check that all Polarity LEDs are GREEN. If multiple AXIOM-X are daisychained together, check the polarity of the first unit in the chain (i.e., unit wired directly to power source), then the second, then the third. If all Polarity LEDs are GREEN, polarity is correct. 3. If any Polarity LEDs are RED, polarity is reversed and must be corrected. 4. Disconnect from power source. 5. Correct wiring. For single units, simply swap the wiring at the INPUT POWER terminal block of any unit that had a RED polarity indication. In a daisy-chain, correct the wiring on the first unit in the daisy-chain that had a RED polarity indication. 6. Reconnect to power source. 7. Apply power. 8. Check polarity to assure wiring has been corrected. 9. If all Polarity LEDs are GREEN, polarity check is complete. NOTE: In daisy-chained power applications, if the first or second unit’s Polarity LED is RED and the last unit‘s LED is GREEN, you need to swap the INPUT POWER wiring of the first unit with RED LED and the OUTPUT POWER wiring of the last unit with RED LED.
04-AXIOM-AXIOM-X_Electrical_Installation_R10.doc
Accu-Sort Systems, Inc.
53
Page 54
54
AXIOM™ / AXIOM-X™ Product Line Manual
Electrical Installation
Trigger Connections AXIOM readers support three trigger modes: hardware, software, and continuous. When using hardware trigger, one or more input signals “trigger” the reader. Software trigger is accomplished by sending a specific ASCII message via serial or network communications. Continuous trigger requires no external trigger. When a hardware trigger (i.e., package detector) is required, Accu-Sort’s retro-reflective photoeye (PN 100020569) is recommended.
Wiring Trigger to Wiring Base Connect trigger wiring to the wiring base terminal blocks. Wire the Accu-Sort photoeye as indicated in shaded area of the table below. (Wire colors indicated for standard NPN Output, shown in shaded areas.) WIRE COLOR RED (Jumper to V+) WHITE BLACK
TERM V+ TRIG + TRIG GND
NPN OUTPUT Supply Voltage Jumper to V+ Photoeye output Common
PNP OUTPUT 24V Supply Voltage Photoeye Output + Output Jumper to GND - Output Common
If your application uses a photoeye other than the one available from AccuSort, follow the TRIGGER wiring table to assure proper wiring. The trigger must be able to operate using the +24VDC source (24V) and not draw more than 100mA. The trigger input must be able to sink (or source) 10mA at +24VDC. NOTE: To confirm the Trigger photoeye is functioning properly, watch the Trigger LED while the photoeye’s beam is blocked. (See Chapter 5 for details.) The Accu-Sort photoeye also includes a status LED. Multiple Readers When an application incorporates multiple readers wire the trigger photoeye to the AXIOM-X Controller. (See drawings 107480 and 107481 in Appendix E.)
Accu-Sort Systems, Inc.
04-AXIOM-AXIOM-X_Electrical_Installation_R10.doc
Page 55
AXIOM™ / AXIOM-X™ Product Line Manual
Electrical Installation
Tachometer Connections In applications where product tracking is required, a tachometer is typically used. Connect the tachometer wiring to the wiring base terminal blocks.
Wiring Tachometer Input to Wiring Base When a tachometer is required, the Accu-Sort tachometer is recommended. Wire this tachometer as indicated in shaded area of the table below. (Wire colors indicated for standard NPN Output, shown in shaded areas.) Tachometer Wiring TACH WIRE COLOR WHT/ORG (Jumper to V+) WHT/BLU BLU/WHT+ORG/WHT
TERM V+ TACH + TACH GND
NPN OUTPUT Supply Voltage Jumper to V+ Tach Output Common
PNP OUTPUT 24V Supply Voltage Tach Output + Output Jumper to GND - Output Common
WARNING: The maximum tachometer current should not be more than 0.3 amps @ 24 volts.
The shielding for the tachometer wiring MUST be terminated to earth ground. Otherwise, belt static could result in a system failure.
Tachometer Shielding Terminated to Earth Ground
If your application uses a tachometer other than the one available from AccuSort, follow the TACH wiring table to assure proper wiring.
04-AXIOM-AXIOM-X_Electrical_Installation_R10.doc
Accu-Sort Systems, Inc.
55
Page 56
56
AXIOM™ / AXIOM-X™ Product Line Manual
Electrical Installation
Multiple Readers When an application incorporates multiple readers wire the tachometer to the AXIOM / AXIOM-X Controller. (See drawings 107480 and 107481 in Appendix E.)
Using Ferrite Clamps when Wiring Tachometer In order to absorb transient currents generated by motors and belts, two ferrite clamps should be added to the TACH cable as shown below. Doing this prevents external noises from damaging the wiring base and scan head.
Close-up of Ferrite Clamp in the open position (included with the wiring base)
Proper positioning of ferrite clamps on tachometer cable
Accu-Sort Systems, Inc.
04-AXIOM-AXIOM-X_Electrical_Installation_R10.doc
Page 57
AXIOM™ / AXIOM-X™ Product Line Manual
Electrical Installation
RS232/422 Communications Connections The wiring base provides an RS232/RS422 terminal block for serial point-topoint communications. Typically, network communications will use Ethernet.
RS232 Connections Use RS232 for a direct connection to a controller, personal computer, or other device. RS232 provides point-to-point communications at distances up to 50 feet (15.2 meters). If longer cable lengths are needed, use RS422. RS232 connections are made to the SERIAL COM terminal block. Follow the SERIAL COM / RS232 wiring table to assure proper wiring. IMPORTANT: Before attempting to use RS232 communications with RTS/CTS, contact Accu-Sort Customer Service for additional information.
RS422 Connections Use RS422 for a direct connection to a controller, personal computer, or other device. RS422 provides point-to-point communications at distances up to 1000 feet (300 meters). RS422 connections are made to the SERIAL COM terminal block. Follow the SERIAL COM / RS422 wiring table to assure proper wiring. Line Termination The end devices on an RS422 point-to-point connection must be terminated. A termination resistor is pre-installed in the wiring base. The HOST end of the connection must also be terminated using a 120-ohm resistor between the RECEIVE+ and RECEIVE- terminals.
04-AXIOM-AXIOM-X_Electrical_Installation_R10.doc
Accu-Sort Systems, Inc.
57
Page 58
58
AXIOM™ / AXIOM-X™ Product Line Manual
Electrical Installation
Ethernet Communications Connections Use Ethernet for network/host communications or multiple-reader networks. Ethernet communications cabling can be run up to 330 feet (100 meters). Ethernet connections are made to the ETHERNET terminal block. Follow the ETHERNET wiring table to assure proper wiring.
IMPORTANT: Do not strip wires before inserting them into the Ethernet terminal block. For additional details on Ethernet and EtherNet/IP communications, go to Appendix C: AXIOM Networking Guide. Another useful source of information is the ODVA official web site (www.odva.org).
NOTE: To simplify your network installation, Accu-Sort offers the following options: RJ45 Adapter Kit RJ45 adapter cables (10 and 20 ft. lengths) a 5-port Ethernet switch (Linksys) and an 8-port dual speed Ethernet switch (10/100).
Multiple Readers Most multi-reader applications will use Ethernet or EtherNet/IP communications. See the following drawings on the documentation CD for wiring details: 107480 – Controller/Client with tachometer 107481 – Controller/Client/Client with tachometer
Accu-Sort Systems, Inc.
04-AXIOM-AXIOM-X_Electrical_Installation_R10.doc
Page 59
AXIOM™ / AXIOM-X™ Product Line Manual
Electrical Installation
I/O Module Connections The wiring base supports up to four (4) optional input or output (I/O) modules. (See table below.) These modules function like switches; they do not supply a voltage. (See Appendix A.) Connect I/O wiring to the correct terminal blocks. When using DC modules, observe the polarity of the connections illustrated on insulating cover label.
Part Number
Description
Color
Rating
Current Range
1000056135
DC Input Module white
3.3 to 32 VDC
32 mA
1000056136
DC Output Module red
3 to 60 VDC
3 A max. *
1000056137
AC Output Module black
12 to 42 VAC
3 A max. *
NOTE: Relay modules are only for connection to SELV, LPS power source. * Derate 33mA/deg above 25C.
Proper I/O module wiring is shown for the following applications on drawings found in Appendix E: 107482 – End Trigger Photoeye 109364 – Height Tracking Photoeyes (for AXIOM-X) 107483 – Stack Light
04-AXIOM-AXIOM-X_Electrical_Installation_R10.doc
Accu-Sort Systems, Inc.
59
Page 60
60
AXIOM™ / AXIOM-X™ Product Line Manual
Electrical Installation
Output Module Application Shown below is a typical output module application. When connecting high impedance loads, you may need to add a resistor in parallel with the load. This resistor (typically 300 to 6,000 ohms) provides a continuous minimum current flow (10 mA DC or 50 mA AC) through the output module in the closed state.
Output Module TB +
Fuse Recommended
Load
Optional Resistor
+ AC or DC Source
Optional Resistor for High Impedance Loads Back Electromotive Force (EMF) is sometimes generated when an inductive load is switched off. Back EMF may damage the output module. A diode in parallel with the inductive device dissipates the back EMF.
Output Module TB +
Inductive Load
Fuse Recommended
Optional Diode
+ DC Source
Optional Diode to Dissipate Back EMF An example output module application is the use of a Stack Light with three output modules. Each module will send a signal to the stack light to visually indicate specific conditions (e.g., green = read, yellow = multiple codes, red = no read). (See drawing 107483 in Appendix E.) Input Module Application Input module 1000056135 is most often used for an End Trigger Photoeye application. (See drawing 107482 in Appendix E.) It can also be used for Height Tracking Photoeyes. (See drawing 109364 in Appendix E.) NOTE: Any other input module application requires custom software. Contact Accu-Sort Customer Service for more information.
Accu-Sort Systems, Inc.
04-AXIOM-AXIOM-X_Electrical_Installation_R10.doc
Page 61
AXIOM™ / AXIOM-X™ Product Line Manual
Electrical Installation
Installing a Scan Head Once all wiring is completed and checked for accuracy, install the AXIOM or AXIOM-X scan head to the wiring base. (See Chapter 3.) You can install the scan head with or without the power disconnected from the wiring base.
Check Installation After completing the installation of your AXIOM / AXIOM-X: Confirm that the reader has been properly installed mechanically and electrically. Use the Installation Sequence at the beginning of this chapter and your application specifications to check your installation. Configure the reader’s parameters to meet the needs of your application. (See Chapter 5 and online help for details.) See Chapter 5 and 6 for details regarding first-time startup and an operations checklist.