Page 431

Appendices 7. Double-click on the “Controller Tags” item, and verify FIS-6801’s :I and :O tags appear in the Controller Tags window:

8. Open the “Main Routine”:

FIS-6801 Industrial Scanner User’s Manual

A-103

Page 432

Allen-Bradley PLC Setup 9. Right-click on the top rung and select “Import Rung”:

10. Navigate to the “32-000001-xx.L5X” file and click “Import”:

A-104

FIS-6801 Industrial Scanner User’s Manual

Page 433

Appendices 11. At the “Import Configuration” window, link the first two items to the module name assigned earlier:

12. Link “:I” to the input assembly:

FIS-6801 Industrial Scanner User’s Manual

A-105

Page 434

Allen-Bradley PLC Setup 13. Link “:O” to the output assembly:

14. Delete any empty rungs:

A-106

FIS-6801 Industrial Scanner User’s Manual

Page 435

Appendices 15. Select one CPS instruction per rung, the “_small_pt” on the left, or the “_big_pt” on the right. Keep the one that corresponds to the assembly sizes configured for the module, and delete the other:

FIS-6801 Industrial Scanner User’s Manual

A-107

Page 436

Allen-Bradley PLC Setup 16. In this example, the small assembly set has been kept:

In this example, the big assembly set has been kept:

For the remainder of this document, the big assembly set is demonstrated. The system is now configured enough to test communication with FIS-6801. A-108

FIS-6801 Industrial Scanner User’s Manual

Page 437

Appendices 17. Select the control button next to “Offline”, and select “Download”:

18. Once the program has downloaded, make sure the PLC is in Run Mode:

FIS-6801 Industrial Scanner User’s Manual

A-109

Page 438

Allen-Bradley PLC Setup 19. To open the Program Tags, right-click on “Program Tags” and select “Monitor Tags”:

20. Expand the “FIS-6801Hawk_IO_big_pt” so that the .IN and .OUT structures and values are visible:

A-110

FIS-6801 Industrial Scanner User’s Manual

Page 439

Appendices 21. Change the “.OUT.usertag” to non-zero:

FIS-6801 Industrial Scanner User’s Manual

A-111

Page 440

Allen-Bradley PLC Setup The “.IN.usertag_echo” will change to match the same value as the “.OUT.usertag”:

This confirms that two-way communication with FIS-6801 is successful. It is left to the programmer to move or modify the CPS instructions in the Main Program according to the application’s requirements. Operation of the data fields within the assemblies is described in the object model documentation.

A-112

FIS-6801 Industrial Scanner User’s Manual