For the Synel SY-780A
Page 1
SY-760 SY-780/A Installation Manual
Synel Industries Ltd.
Page 2
Refer to: ftp://synel.com/docs/ for enhanced documentation!
Manual February 9, 2004. Document no. (76/80INSTL-222-03), Catalogue no. 650506 All rights reserved. to Synel Industries Ltd. Reproduction or use, without express permission of editorial or pictorial content, in any manner is prohibited. No patent liability is assumed with respect to the use of the information contained herein. While every precaution has been taken in the preparation of this manual, Synel Industries Ltd. assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained herein. Pictures in this manual are for illustration purposes only. SY-760+780/A is a trademark of Synel Industries Ltd. All trade names referenced herein are either trademarks or registered trademarks of their respective companies.
Synel Industries Ltd.
Page 3
SY-760 & SY-780/A Installation Manual
Technical Specifications
1.
Technical Specifications
1.1
Technical and interface specifications
• • • • • • • • •
32 character LCD with back light display Eight (780)/six (760) programmable function keys Ten numeric keys Four special function keys: Escape, Return, dot and clear Two arrow keys Badge Reader: magnetic/wiegand/bar code/proximity 512K of protected RAM Protected Real Time date/time clock Rechargeable backup battery (one month capacity) for the memory and Real Time clock Rechargeable backup battery for operation with auto shut-off for use during power outages RS-232 and RS-485 communication Two relays for bell, door, etc Two sensors (door monitoring) Variable baud rate - 1200 to 19200 bps
• • • • •
1.1.1 •
• • • • •
Options Fingerprint reader verification or identification (780):
Verification Identification Template size 400Bytes 2Kb Response time 3 seconds 3 seconds Security level 5 NONE Template storage 4000 200 False accept/reject 0.001 0.001 Bar-code slot reader model (Codes: 128, 2/5, 3/9, UPC-EAN) Magnetic (Track II, Track I) Proximity reader (125 KHz) Mifare reader (13.56 MHz) Wiegand 26/27/34/36/37/44/48bit (as of version 6.201)
Synel Industries Ltd.
1
Page 4
Technical Specifications • •
1.2 • • • •
1.3 • •
SY-760 & SY-780/A Installation Manual
2400/14400 bps internal modem Ethernet (10BASE-T/100BASE-T or AUI)
Physical characteristics Dimensions: Height - 17.0 cm. Width - 25.0 cm. Depth – 9.5 cm.
Power Requirements Voltage: 115/230 VAC Back-up battery - rechargeable, included
Bottom connector panel The connector panel is located at the lower part of the casing, withholding the socket openings for all external connections as follows: 1. Power supply 2. External secondary Reader 3. I2C – I/O extension (N/A) 4. Network 5. Serial I – Serial port connection for printer 6. Host – RS-232/RS-485
Internal components 1.
Battery back-up modules: The terminal has two back-up battery modules, one for the real time clock memory and the other for operation during a power failure. The standard memory back-up module is a 30 day span lithium battery, keeping the internal clock running and the memory intact. The battery (in addition to the standard memory back-up) is self-contained, this allows operation during a power failure for 11/2 hours. A shut down timeout feature enables longer operation time. During a power failure, the user presses the battery key to activate the terminal. Data can then be entered and stored in the terminal memory. Timeout will cause the terminal to shut down automatically after the last use of the terminal, until the battery key is pressed again. Note: You must plug the terminal into a main power source, for at least 18 hours continuously before using it for the first time.
2
Synel Industries Ltd.
Page 5
SY-760 & SY-780/A Installation Manual 2.
3.
Unpacking
Memory: The terminal contains a 512 Kbyte user memory, providing storage for data from more than 10,000 simple operations depending on programming tables length, and the complexity of collected data. Serial RS-232/485 internal Card
2.
Unpacking
Note: Do not throw away the box or packing materials. Check the box and contents for signs of damage that may have occurred during shipment. Carefully unpack and check contents:
2.1
Contents
The terminal package contains: • Terminal • Mounting panel • 1 connecting/splitter box (included only when network communication is not available) • Short RS-232/485 communication cable (included only when network communication is not available) • Short TCP/IP communication bridge cable (included only when network communication is available) • Four Phillips flat head 3.5x30mm anchors, for terminal mounting • Mounting template • Connector cover
3.
Installation
3.1
Mounting the terminal on a wall
Make sure the unit is unplugged. If you have already connected the terminal to a PC, disconnect it. You can reconnect after mounting has been completed. Caution: The terminal contains computer components. It should not be mounted where it will be exposed to extreme heat or cold, water, steam, violent vibrations, high electromagnetic radiation including high voltage power lines and electrical equipment. Step 1:
Place the terminal near an easily accessible power outlet. Select an
Synel Industries Ltd.
3
Page 6
Installation
SY-760 & SY-780/A Installation Manual appropriate location for the terminal and mount it at employee shoulder-height. Do not place the communication cable near a source of electromagnetic radiation or radio interference such as power lines, large machinery, etc. If the communication cable is to be threaded into the wall, make sure that it is safe to drill a hole at the desired location. The recommended height from top edge is 140cm (4’7’’). Remove the back panel by sliding it to the side and pulling it out.
Step 2: Warning:
Live wires in the vicinity may be 115V or 220V. Make sure not to drill into any live electric wires. Overlooking this warning may result in harmful contact with an electrical current.
Step 3:
Step 8: Step 9:
Place the panel on the wall as a template and mark the place for drilling the holes. Drill holes using a 6 mm. (1/4") drill bit. If the communication cable is to be wired through the wall, wire one end. Screw the panel to the wall. Slide the terminal over the panel hinges. Connect the communication cable: Plug one end of the communication cable into the communication socket of the terminal. Plug the terminal into the power socket. Re-place the connector cover at the bottom.
3.2
Communication connections
Step 1:
Select a location for the connection box. The box must be positioned where both the communication line and the terminal can be connected to it. Plug the terminal communication cable into the connection box. Wire an additional connection for Ethernet. If an internal modem has been added and the modem is used, plug the RJ-45 connector of a standard telephone cable into the telephone line. Do not use the terminal communication cable.
Step 4: Step 5: Step 6: Step 7:
Step 2: Step 3: Step 4:
4
Synel Industries Ltd.
Page 7
SY-760 & SY-780/A Installation Manual
4.
Technician Mode (Setup)
Technician Mode (Setup)
Enter into Technician Mode by swiping an authorized badge or by clicking both the line up/down keys six times simultaneously (if the terminal is not programmed key-in 6 times 0 + Enter). Use the Enter key to scroll between screens, and the line up/down keys for moving between options within the selected screen. To return to the previous screen use the C key. To exit technician mode double-click the Enter key. Technician mode enables setting up: • Real Time Clock (RTC) Calibration • Baud rate • Fingerprint unit Baud rate • Printer Baud rate • Station ID settings • Modem rings • Network connection • User Field - A field in which the user can fill-in 4 digits that will characterize that terminal. Enter into Technician Mode: The display screen flashes for a five seconds interval and displays the version then flips to display the TECHNICIAN MODE and time and date alternately, (time&date are adjusted from the PC). For further information you can refer to the extended user manual.
5.
Terminal-Host Interfacing
The terminal data collection terminal can be connected to the host computer using either an RS-232 or an RS-485 connection with an asynchronous serial port. RS-232 is used for a single device with a point to point connection, for distances of up to 50 meters (160 ft). RS-232 is the communication standard used by nearly all PCs and modems. Cabling distance is limited to 50 meters (160 ft) and only one terminal may be connected to the same COM port. The RS-485 standard extends the potential cabling distance to 1,000 meters (3,280 feet). Using 9600 baud enables multi-COM port connections. It uses only two communication wires. The SY-65 communication adapter converts RS-232 to RS-485. Note: Most PCs use DTE type connectors on their RS-232 ports. The terminal is equipped with an RJ45 (telephone jack) connector. Thus, you will need a connection box intermediating the terminal and the host.
Synel Industries Ltd.
5
Page 8
Terminal-Host Interfacing
5.1
SY-760 & SY-780/A Installation Manual
Installing communication cables
1.
The cable should not be installed near EMI sources, such as: • Motors, generators, alternators, and transformers • Air conditioners, elevators • Radio/television transmitters, signal generators and internal communication networks Cables should not be within: • 30 cm. (1 foot) range from less than 5 KVA power lines. • 60 cm. (2 feet) range from 5-10 KVA power lines. • 1.5 meters (5 feet) range of power lines of exceeding 10 KVA. Cables should not run parallel to power lines for more than 15 meters (49 feet). Use a single continuous cable for the communication line. If this is not possible, the cable should have only one indoor connection as follows: a. Using two connectors with appropriate shielding and cover. b. Using a connection box. For aerial installation, use NYY shielded cables.
2.
3. 4.
5.
5.2
Connecting your PC to the SY-65
SY-65 must be set to one of the RS-485 modes: 4,5,6 and 7 dip-switches. For more information, refer to the manual for the SY-65 communication adapter. The diagrams below describe the pin outs for the cable connecting PC - SY65 communication adapter. For 9-pin connector PC refer to first diagram, for a 25-pin connector refer to the second diagram. SY65 9Pin D-Type 2 3 5
5.2.1 1. 2.
6
Computer 9Pin 3 2 5
25Pin 2 3 7
If communication problems occur Lower the baud rate. Use cables with a heavier gauge conducting wire.
Synel Industries Ltd.
Page 9
SY-760 & SY-780/A Installation Manual 3.
4.
5.3
Terminal-Host Interfacing
Connect 120 ohm resistors between the MRxD and PRxD, and also between MTxD and PTxD that are at the ends of the wire of the following two connectors: a. The connector on the computer. b. The connector on the last terminal of the multi-drop line. EMI protection is integrated into the terminal, but it is best to use an external protector for lightning problems.
Making a multi-drop connection
Note: Terminal IDs are set using the technician mode. There is no procedure for hardwiring the terminal ID as in the SY-1XX and SY-4X terminals. All terminals and their connection boxes are connected in exactly the same way, regardless of their terminal IDs. The multi-drop line may be created in one of two ways: creating a chain of connection boxes, using a junction box. Method 1
Method 2
The SY-65 is connected to a connec- The SY-65 is connected to a junction box. tion box which cascading another con- A separate cable is connected from each nection box. connection box to the junction box.
5.3.1
Cable from the terminal to the connection box
This is a standard 6 wire telephone cable with an RJ45 connector cable which is supplied with the terminal. The pin locations are illustrated below. Cable length should not exceed 30 meters (98feet). The RJ45 connector on the terminal’s side must be a short (12.35mm) RJ45 connector to enable the terminal connector case to close.
Synel Industries Ltd.
7