This two-page Sola/Hevi-Duty catalog section describes the MCR Hardwired Series of single-phase power line conditioners with ferroresonant voltage regulation. It gives the features, selection tables for 60 Hz and 50 Hz models with catalog numbers, voltages, sizes and ship weights, and the specifications.

Device
Hardwired single-phase power line conditioner with ferroresonant voltage regulation, noise filtering, surge suppression and galvanic isolation p. 1
Output regulation
± 3% for 60 Hz units, ± 5% for 50 Hz units, with input from 80% to 110% of nominal p. 2
Noise attenuation
120 dB common mode, 60 dB transverse mode p. 1
Surge suppression
Tested to ANSI/IEEE C62.41 Class A & B waveform, under 10 V let-through typical p. 1
Input range
+10% to -20% of nominal continuous at full load; +20% to -35% for temporary surges or sags p. 2
Ratings
120 VA to 15000 VA, 60 Hz or 50 Hz depending on model p. 1, 2
60 Hz Group 2
120 VA (63-23-112-4) to 15000 VA (63-28-315-8); input 120, 208, 240, 480 V (208, 240, 480 V from 7500 VA); output 120 V up to 250 VA, else 120, 208, 240 V p. 1
60 Hz Group 3
600 V input: 500 VA (63-31-150-8) to 3000 VA; 5000 VA to 15000 VA (63-29-315-8) take 208, 240, 480 or 600 V p. 2
50 Hz Group 4
120 VA (63-23-612-8) to 15000 VA (63-28-815-8); input up to 415 V; output 110, 120, 220, 240 V p. 2
Overload protection
Current limited at 1.65 times rated current p. 2
Efficiency
Up to 92% at full load p. 2
Temperature
Operating -20° to 50°C; storage -20° to +85°C; humidity under 95% non-condensing p. 2
Size and weight
From 9 x 4 x 5 in, 15 lbs ship weight (120 VA, Group 2) to 30 x 38 x 10 in, 776 lbs (15000 VA, Group 4), height x width x depth p. 1, 2
Audible noise
35 dBA to 65 dBA p. 2

What this sheet walks you through

  • Choosing a model by VA rating, input and output voltage p. 1, 2
  • Finding the electrical connection diagram letter for each model p. 1, 2
  • Estimating input current at full load p. 2

Good to know

  • Group 2 units from 7500 VA are UL listed only; Group 3 is the cULus choice. p. 1
  • Fuse sizing is in the user manual, not this sheet. p. 2
  • A lower input voltage is possible only at lighter load. p. 2

Questions this sheet answers

What is the catalog number of a 1000 VA Sola MCR for 480 V input?

In Group 2 (60 Hz) it is 63-23-210-8, taking 120, 208, 240 or 480 V input and giving 120, 208 or 240 V out. p. 1

How do I order a cULus certified MCR for Canada?

For the starred Group 2 models, change the "-8" at the end of the catalog number to "-C8". p. 1

How closely does the MCR regulate output voltage?

Within ± 3% on 60 Hz units and ± 5% on 50 Hz units, for input between 80% and 110% of nominal. p. 2

How much input current does an MCR draw?

The sheet gives Iin ≅ (VA/.89)/(Vin x 80%) at full load and 80% of nominal input voltage. p. 2

The file

Size and text

Pages2
PDF130 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Sola MCR Power Conditioner Spec Sheet

The text of page 1, from the PDF itself

1

Power Protection and Conditioning MCR Hardwired Series – Power Line Conditioning with Voltage Regulation The MCR Hardwired Series provides excellent noise filtering and surge suppression to protect connected equipment from damage, degradation or misoperation. Combined with the excellent voltage regulation inherent to Sola/Hevi-Duty’s patented ferroresonant design, the MCR can increase the actual Mean Time Before Failure (MTBF) of protected equipment. The MCR is a perfect choice where dirty power, caused by impulses, swell, sags, brownouts and waveform distortion can lead to costly downtime because of damaged equipment.

Features

  • ±3% output voltage regulation
  • Noise attenuation
  • 120 dB common mode
  • 60 dB transverse mode
  • Surge suppression tested to ANSI/IEEE C62.41 Class A & B Waveform:
  • <10 V let through typical
  • Acts as a step-up or step-down transformer
  • Harmonic filtering
  • Hardwired
  • Galvanic isolation provides exceptional circuit protection.
  • 25 year typical MTBF
  • No maintenance required

Applications

  • Industrial automation and control equipment PLCs
  • Machine tools
  • Computer loads and electronic equipment
  • Robotics
  • Semiconductor fabrication equipment

Related Products

  • On-line UPS (S4K Industrial)
  • Surge Suppression
  • Three Phase Power Conditioners

Selection Tables: Single Phase Group 2 – MCR Series, 60 Hz Only VA

Height (inch)Width (inch)Depth (inch)Ship Weight (lbs)Design StyleElec ConnCatalog NumberVoltage InputVoltage Output12063-23-112-4120, 208, 240, 480120945151D25063-23-125-4120, 208, 240, 4801201068271D50063-23-150-8120, 208, 240, 480120, 208, 2401397371E75063-23-175-8120, 208, 240, 480120, 208, 2401497521E1000*63-23-210-8120, 208, 240, 480120, 208, 2401797621E1500*63-23-215-8120, 208, 240, 480120, 208, 24017139951E2000*63-23-220-8120, 208, 240, 480120, 208, 240181391091E3000*63-23-230-8120, 208, 240, 480120, 208, 240191391421E5000*63-23-250-8120, 208, 240, 480120, 208, 240281392221E7500**63-28-275-8208, 240, 480120, 208, 240272693622F10000**63-28-310-8208, 240, 480120, 208, 240282694462F15000**63-28-315-8208, 240, 480120, 208, 2402838107103F

  • Canadian option: cULus certified units must be ordered by changing “-8” (UL only) to “-C8”. ** UL Listed Only. Use Group 3 for cULus.

Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com.

15

Page 2 of Sola MCR Power Conditioner Spec Sheet

The text of page 2, from the PDF itself

1

Power Protection and Conditioning

Selection Tables: Single Phase Group 3 – MCR Series, 60 Hz Only VA

Catalog NumberVoltage InputHeight (inch)Voltage OutputWidth (inch)Depth (inch)Ship weight (lbs)Design StyleElec Conn50063-31-150-8600120, 208, 2401397381B100063-32-210-8600120, 208, 2401797621B200063-32-220-8600120, 208, 2401813101091B300063-32-230-8600120, 208, 2401913101421B500063-29-250-8208, 240, 480, 600120, 208, 2402813102211A750063-29-275-8208, 240, 480, 600120, 208, 2402725103602A1000063-29-310-8208, 240, 480, 600120, 208, 2402825104412A1500063-29-315-8208, 240, 480, 600120, 208, 2402838107063A

Group 4 – MCR Series, 50 Hz Only (±5% output voltage regulation) VA

Catalog NumberVoltage InputVoltage OutputHeight (inch)Width (inch)Depth (inch)Ship weight (lbs)Design StyleElec Conn12063-23-612-8

110, 120, 220, 240, 380, 415

110, 120, 220, 240968241C25063-23-625-8

110, 120, 220, 240, 380, 415

110, 120, 220, 2401168271C50063-23-650-8

110, 120, 220, 240, 380, 415

110, 120, 220, 2401397401C100063-23-710-8

110, 120, 220, 240, 380, 415

110, 120, 220, 2401897641C200063-23-720-8

110, 120, 220, 240, 380, 415

110, 120, 220, 2401813101131C300063-23-730-8

110, 120, 220, 240, 380, 415

110, 120, 220, 2402713101621C500063-23-750-8

110, 120, 220, 240, 380, 415

110, 120, 220, 2403013102661C750063-28-775-8220, 240, 380, 415110, 120, 220, 2402826103932C11000063-28-810-8220, 240, 380, 415110, 120, 220, 2403026104902C21500063-28-815-8220, 240, 380, 415110, 120, 220, 2403038107763C2

Specifications Parameter

ConditionValueInput Voltage Current

Continuous at full load (lower input voltage possible at lighter load)

+10% to -20% of nominal

For temporary surge or sags

+20% to -35% of nominal Iin ≅ (VA/.89)/(Vin x 80%)

at Full Load & 80% of nominal input voltage

1

Frequency

See Operating Characteristics section for details.

50 Hz or 60 Hz depending on model

Output Line Regulation

Vin >80% and <110% of nominal

± 5% for 50 Hz units, ± 3% for 60 Hz units

Overload Protection

At Nominal Input Voltage

Current limited at 1.65 times rated current

Output Harmonic Distortion

At full load within input range

Noise Attenuation

-Common Mode -Transverse Mode

EfficiencyAt Full LoadUp to 92%Storage Temperature

Humidity <95% non-condensing

-20° to +85°C

Operating Temperature

Humidity <95% non-condensing

-20° to 50°CAudible NoiseFull Resistive Noise

3% total RMS content 120 dB 60 dB General

Approvals Warranty

UL1012, CSA evaluated by UL

50 Hz Models

CE (EMC & LVD)

See General Information section for details

Notes
1 - Consult user manual for fuse sizing.

1635 dBA to 65 dBA60 Hz Models

Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com.