These are two pages of wiring tables from a Sola power protection catalog for MCR power conditioners (60 Hz and 50 Hz) and CVS units. For each model range the tables show which primary and secondary terminals to link and which to connect the lines to for each voltage.

Content
Tables of primary (H) and secondary (X) terminal links and line connections for each voltage p. 1
MCR 60 Hz ratings
120–250 VA, 500–3000 VA, 500–5000 VA, 5000–15000 VA, and 7500, 10000 and 15000 VA p. 1, 2
MCR 50 Hz ratings
120–5000 VA, 7500 VA and 10000–15000 VA p. 1
CVS ratings
CVS 60 Hz 30–120 VA and 7500 VA, 250 VA, and 500–5000 VA p. 2
Primary voltages
Tables include 120, 208, 240, 480 and 600 V, and 110-120, 220-240 and 380-415 V p. 1
Secondary voltages
Tables include 110, 120, 208, 220 and 240 V outputs p. 1

What this sheet walks you through

  • Linking primary terminals for the supply voltage p. 1, 2
  • Connecting the secondary for the output voltage p. 1, 2

Good to know

  • A note on the second page states that the secondaries are not grounded and X2 is to be grounded per code. p. 2

Questions this sheet answers

How do I wire a Sola MCR for a different input voltage?

Find the table for the model's frequency and VA range; it lists which H terminals to link and which to connect the supply lines to for each primary voltage. p. 1

Which Sola MCR sizes do these wiring tables cover?

MCR 60 Hz units from 120 VA to 15000 VA and MCR 50 Hz units from 120 VA to 15000 VA, plus CVS 60 Hz units. p. 1, 2

Is the secondary of a Sola MCR or CVS grounded?

A note on the second page says the secondaries are not grounded and X2 should be grounded per code. p. 2

The file

Size and text

Pages2
PDF237 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Sola MCR Power Conditioner Electrical Connections

The text of page 1, from the PDF itself

1

Power Protection and Conditioning Electrical Connections

APrimary VoltageInterconnect208H1 to H4 H2 to H5H1 & H5240H1 to H4 H3 to H6H1 & H6480H3 to H4H1 & H6600H3 to H4H1 & H7Secondary VoltageInterconnectBConnect Lines ToPrimary VoltageInterconnect600

Connect Lines To H1 & H2

Connect Lines ToSecondary Voltage120X1 & X2 or X3 & X2120X1 & X2 or X3 & X2208X4 & X5208X4 & X5240X1 & X3Interconnect240X1 & X3

MCR 60 Hz 5000–15000 VA

Primary VoltageInterconnectConnect Lines To110-120H1 to H3 H2 to H4H1 & H4220-240H2 to H3H1 & H4380-415H2 to H3H1 & H5Secondary VoltageInterconnectPrimary VoltageInterconnectConnect Lines To220-240H1 to H3 H2 to H5H1 & H5380-415H2 to H3H1 & H4Secondary VoltageInterconnectConnect Lines To110X1 & X2 or X2 & X3120X4 & X2 or X5 & X2220X1 & X3240X4 & X5Connect Lines To110X1 & X2 or X3 & X2120X4 & X2 or X5 & X2220X1 & X3240X4 & X5MCR 60 Hz 500–3000 VAC1MCR 50 Hz 7500 VAConnect Lines ToCMCR 50 Hz 120–5000 VAC2Primary VoltageInterconnectConnect Lines To220-240H2 to H3H1 & H4380-415H2 to H3H1 & H5Secondary VoltageInterconnectConnect Lines To110X1 & X2 or X3 & X2120X4 & X2 or X5 & X2DPrimary VoltageInterconnectConnect Lines To120H1 & H2208H1 & H3240H1 & H4480H1 & H5220X1 & X3Secondary Voltage240X4 & X5120

MCR 50 Hz 10000–15000 VA

Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com.

Interconnect

Connect Lines To X1 & X2

MCR 60 Hz 120–250 VA

17

Page 2 of Sola MCR Power Conditioner Electrical Connections

The text of page 2, from the PDF itself

1

Power Protection and Conditioning

Electrical ConnectionsEPrimary VoltageInterconnectConnect Lines To120H1 & H2Primary Voltage208H1 & H3208H2 & H3InterconnectConnect Lines To240H1 & H4240H2 & H4480H1 & H5480H1 & H4Connect Lines ToSecondary VoltageSecondary VoltageInterconnectGF120X1 & X2 or X3 & X2208X4 & X5240X1 & X3MCR 60 Hz 500–5000 VAInterconnectConnect Lines ToPrimary VoltageInterconnectConnect Lines To120

H1 to H3 H5 to H7 H2 to H4 H6 to H8

H1 & H2

240

H2 to H3 H6 to H7 H1 to H5 H4 to H8

H1 & H4

480

H2 to H3 H4 to H5 H6 to H7

H1 & H8InterconnectConnect Lines To120X1 & X2 or X3 & X2208X4 & X5Secondary Voltage240X1 & X3120

MCR 60 Hz 7500, 10000 and 15000 VA

H

Series-Multiple Primary with Tap for two input voltages

X1 & X2CVS 60 Hz 250 VA onlyJ

Open MCR/CVS terminal 30 & 60 VA Primary Voltage

120 VA Primary Voltage

7500 VA Primary Voltage

InterconnectConnect Lines To120N/AN/A

Note: H3 & H4 are not used

H1 & H2240H1 to H3 H2 to H4H1 & H4H2 to H3H1 & H4InterconnectConnect Lines ToPrimary VoltageInterconnectConnect Lines To120

H1 to H3 to H6 to H8 H2 to H5 to H7 to H10

H1 & H2208H2 to H3 H1 to H6H7 to H8 H4 to H9H1 & H4240

H2 to H3 H7 to H8 H1 to H6 H5 to H10

H1 & H5

480

H2 to H3 H5 to H6 H7 to H8

H1 & H10Secondary VoltageInterconnectConnect Lines ToN/AN/A120X1 & X2 or X3 & X2N/AN/A240X1 & X3N/A120N/A240480

30 & 60 VA Secondary Voltage

120 VA Secondary Voltage

7500 VA Secondary Voltage

120120N/AX1 & X2120X1 & X2 or H3 & X2240X1 & X3

CVS 60 Hz 30–120 VA & 7500 VA

CVS 60 Hz 500–5000 VA

18

Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com.

Note: Secondaries are not grounded. Ground X2 per Code.