Technical Description: Proximity Laser Scanner PLS, pages 71 to 78

Pages 71 to 78 of 78

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Sick PLS101

Page 71

Properties min. Short-circuit-protected

Type details

Comments max.

By monitoring outputs

In event of error: leakage current

2.1 mA

Pure load capacity

100 nF

Operating sequence

3 Hz

Pure load inductance

2H

At low operating sequence, the max. permitted load inductance is higher

500 Hz see test pulse data

Arc-suppression element (RC combination)

Event of error: interruption of GND line. The post-switched control element must recognise this condition as Low.

without

Load low-pass behaviour (limit frequency) Test pulse data

The outputs are cyclically tested in activated status (in short: LOW switching). When selecting the post-switched control elements, ensure that the test pulse cannot cause a shutdown when using the parameters given above.

OSSD 1 Test pulse width

55 µs

Test pulse frequency every 40 ms

OSSD 2 Test pulse width

55 µs or 460 µs

Test pulse frequency

Alternating every 40 ms

OSSD 1 und OSSD 2 Test pulse width

55 µs

Test pulse frequency

3s

Cable specification Cable length

30 m

Cable cross-section

0.5 mm2

Permitted cable impedance

2.5 Ohm

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

71

08.07.2004, 15:55

71

Page 72

Properties min.

Type details

Comments max.

Optical details Scan angle

180°

Angular resolution

0.5°

Protective field Range (radius)

4m

Object remission

1.8 % (diffuse)

Resolution

70 mm

Reflector

Safety categories DIN V 19250

Requirement category 4

EN 954-1

Category 3

Category 3

Category 3

IEC/EN 61496-1

Type 3

Type 3

Type 3

The EU type test was carried in line with BiA test recommendations which, in the essential parts, comply with the current standards proposal for IEC 61496-3: 1999.

Warning field Range (radius)

50 m

Remission at 15 m and 80 mm object diameter

20 %

Safety category none

Measuring area Range (radius)

50 m

Remission

Diagram (see p. 67)

Resolution of distance measurement

± 50 mm

Measuring error ≤ 2 m distance

94 mm

Measuring error ≤ 4 m distance

131 mm

General data

72

Electrical connection

Plug-in connection box, for 0.5 mm2 screws; crimp connection, PG 9

Interface universal (RS 232 / RS 422)

When assembling the cables yourself, make sure that the cable shielding is attached. Contacting the shielding at both ends is recommended if a RS 232 connection is being used. When deploying an RS 422 connection, the shielding should only be connected to one end. The shielding should be applied to the computer (or LSI).

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

72

08.07.2004, 15:55

Page 73

Properties min.

Type details

Comments max.

Transfer rate RS 232

9600 Baud

56 kBaud

RS 422

9600 Baud

500 kBaud

Permanent computer link-up only permitted with RS 422.

Cable length RS 232

15 m

RS 422

100 m

No. of multiple evaluations

2

16

Restart after n seconds

2

60

Laser protection class

1

Enclosure rating

IP 65, to EN 60529

Protection class totally insulated, protection class 2

Temperature range Ambient operating temperature

0° C

50 ° C

Storage temperature

-25° C

70 ° C

Humidity

DIN 40040, Table 10, code letter E, moderately dry

Sender

Infrared laserdiode

Wavelength

885 nm

905 nm

935 nm

Receiver Acceptance angle

± 0,5°

± 1°

Housing Material

Die-cast aluminium

Front screen Material

Polycarbonate

Surface

Scratch-proof coating on front

Vibration

IEC 68, Parts 2 - 6, Table c2

Frequency range

10 ... 150 Hz

Amplitude

0.35 mm or 5 g

Single shock

IEC 68, Parts 2 - 27, Table 2, 15 g / 11 ms

Continuous shock (1000)

IEC 68, Parts 2 - 29, 10 g / 16 ms

Interference immunity (EMC)

IEC 61496-1, EN 61000-6-4:2001-10 DIN 40839-1 and -3

Weight (net)

approx. 4.5 kg

Dimensions (W x H x D)

155 mm x 185 mm x 156 mm

Colour

RAL 1021

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

73

08.07.2004, 15:55

73

Page 74

12.4 Standards and regulations The following lists the key standards and regulations applicable to the use of optoelectronic safety devices in Europe and in the Federal Republic of Germany. Depending on the field of application, additional regulations may be of importance for you. You can get information on other device-specific standards from local regulatory authorities, or from professional bodies. If the machine or vehicle is operated in a country not belonging to the European Union, we recommend contacting the plant operators and the local authorities. Regarding the use and installation of safety devices: Machine Directive 89 / 392 EEC Safety of machines – Basic terms, general design guidelines (EN 292) Safety of integrated manufacturing systems (DIN EN 1921) Safety of machines – Electrical equipment on machines – Part 1: General requirements (EN 60204) Safety of machines – Safety distances to prevent reaching hazardous areas with upper limbs (EN 294) Safety requirements for robots (EN 775) Safety rules for non-contact safety devices on power-driven machinery (ZH 1 / 597) Safety of machines – Arrangement of safety devices with regard to approach speed of body parts (EN 999) Safety of machines – Risk assessment (EN 1050)

Regarding construction and equipping of safety devices: Safety of machines – Non-contact safety devices – Part 1: General requirements (EN 50100-1 and -2 / DIN VDE 0113, Part 201) Basic safety observations for instrumentation and control safety devices (DIN V 19250) Safety of machines – Electrical equipment on machines – Part L: General requirements (EN 60204) Safety of machines – Safety-related components of controls – Part 1: General design guidelines (EN 954) On these subjects please also order our brochure “Safe machines with optoelectronic safety devices”.

74

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

74

08.07.2004, 15:55

Page 75

12.5 Notes on non-certified PLS types The PLS type 201-313 is not certified as a safety device. Therefore, subject to risk assessment, it may not be suitable for personal protection.

The main part of this description deals only with the certified PLS type PLS 101-312. In the following you can find all the relevant information relating to the non-certified PLS type PLS 201-313. The information given here replaces the corresponding sections in the main part of the description. 1 Approvals and Certificates:

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

75

08.07.2004, 15:55

75

Page 76

2 Notices / Regulation Use: The PLS type 201-313 is not certified as a safety device. Therefore, subject to risk assessment, it may not be suitable for personal protection. The recommendations regarding mounting apply. 3 How the PLS works: This chapter applies. 4 Fields of Application - What the PLS Can Do: Not relevant. 5 Location Planning: 5.1 Not relevant. 5.2 Only relevant for collision protection if danger to persons resulting from a collision can be excluded. 6 Supply Package: This chapter applies 7 Mounting the PLS: This chapter applies 8 Connecting Up the PLS Not relevant. 9 Programming the PLS with the PLS / LSI User Software This chapter applies 10 Care and Maintenance This chapter applies 11 Appendix Technical data: the protective field radius is programmable up to 50 metres. Since the resolution dependent on the distance from the scanner is more than 70 mm, the PLS type 201-313 may not be used for personal protection subject to risk assessment. Therefore a test in accordance with IEC 61496 is also irrelevant. The resolution of this scanner is shown in the adjacent diagram.

76

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

76

08.07.2004, 15:55

Page 77

13 Glossary Start-up testing

Sensor status

When the power has been connected the sensor releases the plant only after the protective field has been infringed intentionally once.

The sensor status characterises the overall state of the system in detail. The data it contains is required to analyse the system.

Verification of the protective field Fault memory A code describing the occurring fault is written to the fault memory. This error code can be read-out by the SICK diagnosis system to provide initial fault analysis.

DTS Driverless Transport System (industrial conveyors). Measurement zone The field of vision of the PLS is its measurement zone. It is heavily dependent on the remission of the object struck, but without special measures also extends to around 15 metres. When using heavily reflective materials the maximum range of the 50 metres is also achievable. With the PLS the distance to objects can also be measured in order to display them on the PC (via the computer interface) or to carry out any other evaluations on the computer. OSSD The OSSD outut is the switching output of the PLS. This is semiconductor based, and its fault-free functioning is tested periodically. The PLS has two parallel-working OSSD outputs, which for safety reasons must be evaluated on two channels.

To ensure the registered contour really matches the area being protected, especially when teaching-in a protective field, it is necessary to “show” the sensor the desired field a second time as confirmation. This is done in the so-called verification process by slowly running a target board over the contour along the inside of the protective field (toward the sensor), but no more than 70 cm from the edge of the protective field. The process can be tracked on-screen by following the change in beam colour from red to green.

Warning field The warning field is a sensor field with a radius of up to 50 metres. It can be used to monitor larger areas and to trip simple switching functions (e.g. warning functions) or to switch a driverless transport system to slow running.

Restart inhibit A device for preventing a plant from being automatically restarted after activation of the sensor function during a hazardous part of the machine cycle, after altering the operating or activation mode, or after changing the start control device on the machinery.

Remission The remission describes the diffuse reflectance of surfaces.

Protective field In the “close-up zone” (radius 4 metres) the PLS offers a sensor field with fail-safe accident prevention functions in accordance with category 4 of DIN 19250 – for area protection but also as a (non-tactile) bumper replacement.

Segmented field Protective fields are handled in segmented form; that is to say, a protective field consists of triangular areas touching each other at the edges of the field. You can freely select the number of segments on which a field is based between 90, 180 and 360. You should note, however, that the earlier PLS/LSI user software version 3.0X was only capable of processing 180 segments. If you programme a field with 360 segments using the new user software version 3.2X and view it subsequently using the old software, the display may be distorted.

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

77

08.07.2004, 15:55

77

Page 78

02_A4_2c_int17.fm Seite 1 Dienstag, 29. Juni 2004 8:16 08

8 008 316/07-07-04 • GO/SM • Printed in Germany (07-04) • Subject to change without prior notice • The specified product features and technical data do not represent any guarantee • 02 A4 2c iint17

Contact: Au s tr a lia Phone +61 3 9497 4100 1800 33 48 02 – tollfree E-Mail sales@sick.com.au B e l gi u m / L u x e m b o u rg Phone +32 (0)2 466 55 66 E-Mail info@sick.be B r a s i l Phone +55 11 5091-4900 E-Mail sac@sick.com.br C e sk á R e p u bl ik a Phone +420 2 57 91 18 50 E-Mail sick@sick.cz C hi na Phone +852-2763 6966 E-Mail ghk@sick.com.hk Da n m ar k Phone +45 45 82 64 00 E-Mail sick@sick.dk De ut s ch la n d Phone +49 (0)2 11 53 01-260 E-Mail vzdinfo@sick.de E s p a ñ a Phone +34 93 480 31 00 E-Mail info@sick.es F ra n c e Phone +33 1 64 62 35 00 E-Mail info@sick.fr G r e at B r i t a i n Phone +44 (0)1727 831121 E-Mail info@sick.co.uk I t a l i a Phone +39 02 27 40 93 19 E-Mail ced@sick.it Ja p a n Phone +81 (0)3 3358 1341 E-Mail info@sick.jp K o r e a Phone +82-2 786 6321/4 E-Mail kang@sickkorea.net

N e d e rl a nd s Phone +31 (0)30 229 25 44 E-Mail info@sick.nl N o r ge Phone +47 67 81 50 00 E-Mail austefjord@sick.no Ö s t e r r e i c h Phone +43 (0)22 36 62 28 8-0 E-Mail office@sick.at P o l s ka Phone +48 22 837 40 50 E-Mail info@sick.pl S c hw e i z Phone +41 41 619 29 39 E-Mail contact@sick.ch S i n g a p or e Phone +65 6744 3732 E-Mail admin@sicksgp.com.sg S u o m i Phone +358-9-25 15 800 E-Mail sick@sick.fi S v e r i g e Phone +46 8 680 64 50 E-Mail info@sick.se T ü r ki y e Phone +90 216 388 95 90 pbx E-Mail info@sick.com.tr T a i w a n Phone +886 2 2365-6292 E-Mail sickgrc@ms6.hinet.net U S A/ C a n ad a /M é x ic o Phone +1(952) 941-6780 1 800-325-7425 – tollfree E-Mail info@sickusa.com

More representatives and agencies in all major industrial nations at www.sick.com

SICK AG • Industrial Safety Systems • Waldkirch • Germany • www.sick.com