Page 21
Operating Instructions
Installation
Chapter 4
OTS400
4
Installation
4.1 Installation sequence •
Mount the frame above the reading location (if not already installed)
•
Mount the bar code scanners
•
Align and adjust the bar code scanners with the objects and range in which bar codes can appear
•
Mount the sensor for generating the reading pulse (if a reading interval signal is not already provided)
•
Install OTS400/ OTC400
4.2 Preparations for installation 4.2.1 • •
Hinged bracket (no. 2018435) or basic mounting bracket (no. 2013824) with the enclosed screws 2 screws for fixing each bar code scanner to the frame (if already provided)
4.2.2 • • • • • • • •
Required components to be mounted
OTS400/ OTC400 CLV bar code scanners Reflection photoelectric switch for external reading interval control Connector covers with EEPROM Connecting cables Terminating resistor Hinged bracket or mounting bracket Frame (if not already provided)
4.2.3 • • •
Required accessories
Required tools
Tool Measuring tape (max. required length 3,000 mm) Protractor
4.2.4
Procedure for mounting the bar code scanners
The procedure for mounting bar code scanners is described in detail in Chapter 4 Installation in the Operating Instructions of the bar code scanner in question.
8008869/RA61/2007-07-30
© SICK AG · Auto Ident · Germany · All rights reserved
4-1
Page 22
Chapter 4
Installation
Operating Instructions OTS400 Omni Tracking System
4.3 Mounting the OPS 4.3.1
Mounting the OTS400/ OTC400
1
Install the frame and the bar code scanners.
2
Install the OTS400/ OTC400. The OTS400/OTC400 is attached near the CLVs. See Section 3.4 Maximum cable lengths. The OTS400/ OTC400 must be mounted in such a way that the open device can be accessed at any time.
Mounting holes are provided on the OTS400/OTC400 or OTC400 (stand-alone) for securing the devices. See 11.2 Dimensional drawings OTS400/ OTC400. 4.3.2
Mounting the external reading pulse sensor
See Chapter 4 Installation in the Operating Instructions of the bar code scanner in question. 4.3.3
Mounting sensors for detecting the object distance
The CLV490 bar code scanner, which is mainly used in the OPS, is equipped with an autofocus function for detecting the object distance automatically. For this reason, sensors for detecting the object distance are usually unnecessary. If you want to use sensors for detecting the object, nevertheless, proceed as described in Chapter 4 Installation for the bar code scanner in question.
4.4 Disassembling the OPS 1. 2. 3. 4.
Switch off the operating voltage. Disconnect all cables Remove the bar code scanners and OTS400/ OTC400 from the mounting device Remove the frame if necessary
For information on environmentally-friendly disposal, please refer to Section 9.3 Disposal.
4-2
© SICK AG · Auto Ident · Germany · All rights reserved
8008869/RA61/2007-07-30
Page 23
Electrical installation
Operating Instructions
Chapter 5
OTS400
5
Electrical installation
5.1 Installation sequence •
Connect the bar code scanners to the OTS400/ OTC400
•
Connect the data and function interfaces of the OTS400/ OTC400
•
Connect the PC to the OTS400/ OTC400
•
Connect the OTS400 or OTC400 to the operating voltage
5.2 Electrical connections and cables The power supply for the OTS400 is connected via the screw terminals (top left in the OTS400, see Fig. 3-2 on page 3-4). Terminal specifications: Connection cable
Cross section
Rigid
0.2 ... 4 mm2
Flexible
0.2 ... 4 mm2
Table 5-1: Power supply connection cable for OTS400
PVC cables are suitable for all connections. Neither heat protection nor halogen-free cables are required. The load carrying capacity of each terminal is 30 A. The OTC400 can also be used separately (without an OTS400). In this case, a functional extra-low voltage of 24 V DC +20%/–10% % pursuant to IEC 364-4-41 is required. The functional extra-low voltage can be generated by using a safety transfomer pursuant IEC 742. The is voltage wired directly on the terminal strip on the front panel. Specification of the connection terminal: Connection cable
Cross section
Rigid
0.2 ... 2.5 mm2
Flexible
0.2 ... 2.5 mm2
Table 5-2: Power supply connection cable for OTC400
Furthermore, the following connections can be made using the terminals on the front panel: •
RS 232 or RS 422/485 host interface (connection to the host)
•
CAN Bus/CANOpen connection for communication with the bar code scanners
•
Power supply for the bar code scanners
•
Four switching outputs
•
A relay switching output
•
Three trigger inputs for external reading pulse triggers
•
Two travel increment inputs for external incremental encoders
•
Seven sensor inputs (“Sensor 1-1 ... 1-7”) that can be freely defined (e.g. for height photoelectric switches)
•
Four sensor inputs (“Sensor 2-1 ... 2-4”) that can be freely defined (e.g. for height photoelectric switches)
•
An "AUX" connection (9-pin D Sub HD connector) for test/diagnosis and parameter purposes
•
A "CAN" connection (9-pin D Sub HD socket) for test and diagnosis purposes
8008869/RA61/2007-07-30
© SICK AG · Auto Ident · Germany · All rights reserved
5-1
Page 24
Chapter 5
Electrical installation
Operating Instructions OTS400 Omni Tracking System
¾
All connections, with the exception of the relay switching output must be wired with copper leads with a minimum wire cross-section of 0.125 mm2!
¾
Connections for the relay switching output at least 1 mm2.
5.3 Connector pin assignment 5.3.1
"CAN" connection
Pin
Signal
Function
2
CAN L
CAN Bus (IN/OUT)
3
GND
Ground
CAN H
CAN Bus (IN/OUT)
1
4 5 6 7 8 9 Table 5-3: Pin assignment of the 9-pole D Sub socket "CAN"
5.3.2
"AUX" connection
Pin
Signal
Function
1
T+ (RS 422/485)
Host interface (RS 422/485)
2
RxD_T
Aux interface (RS 232)
3
TxT_T
Aux interface (RS 232)
4
R+ (RS 422/485)
Host interface (RS 422/485)
5
GND
Ground
6
T- (RS 422/485), TxD (RS 232)
Host interface (RS 422/485)
7
RTS_T
Aux interface (RS 232)
8
CTS_T
Aux interface (RS 232)
9
R- (RS 422/485), RxD (RS 232)
Host interface (RS 422/485)
Tab. 5-4: Pin assignment of the 9-pole D Sub "AUX" plug
5-2
© SICK AG · Auto Ident · Germany · All rights reserved
8008869/RA61/2007-07-30
Page 25
Electrical installation
Operating Instructions
Chapter 5
OTS400
CAN interface
Aux interface
Fig. 5-1: OTC400 - front view
In addition to the 9-pin connectors of the auxiliary interface, the individual connections for the host and auxiliary interface (AUX) are available in two connector strips. See Fig. 5-1.
5.4 Preparations for electrical installation 5.4.1
Requirements of the host interface
The host interface of the OTS400/OTC400 can be operated as an RS 422/485 or RS 232 interface. Table 5-3 shows the recommended maximum cable length, in accordance with the data transmission rate. Interface type
Transmission rate
Distance to host
RS 232
Up to 19,200 bd max. 10m
38,400 bd max. 3m max. 38,400 bd max. 1200 m
1)
RS 422/485
1) with appropriate line termination
Table 5-5: Maximum cable length between the OTS400 and host
Alternatively, bus connection modules can be used, see Chapter 3 Product description. 5.4.2
Supply voltage
The OTS400 with OTC400 requires an operating voltage of 230 V AC (115 V AC) –15%/+10% with protective grounding. In stand-alone operation (without the OTS400), the OTC400 requires an operating voltage of 24 V DC –10%/+20% (functional extra-low voltage pursuant to IEC 364-4-41). For connecting the power supply to the OTS400, see Fig. 3-2. For connecting the power supply to the OTC400 in stand-alone operation at the 24 V IN connector strip, see Fig. 5-1.
8008869/RA61/2007-07-30
© SICK AG · Auto Ident · Germany · All rights reserved
5-3
Page 26
Electrical installation
Chapter 5
Operating Instructions OTS400 Omni Tracking System
5.5 Electrical installation 5.5.1
Connecting the bar code scanners
Photoelectric switch No. 6021166
CAN Bus / CAN Open Protocol
OTS Host connection
OTC CLV490
CLV490
CLV490
Incremental encoder Fig. 5-2: Wiring diagram
Cable no. 6021166 is available for connecting the first bar code scanner to the OTS400/ OTC400. A socket is provided for connection to the bar code scanner; open cable heads are available for the connection to the OTC400.
Recommendation: the supply cable should be shortened as much as possible, in order to prevent unnecessary transmission losses. Pin
Signal
Color
Connection OTC400
1
Shield
2
+24 V
Red
+24 V
3
GND
Black
0V
4
CAN_H
White
H
5
CAN_L
Blue
L
Shield*)
*) with the OTS400, apply the shield directly over the conduit thread (housing entry).
Table 5-6: Pin assignment of the connection cables
For connecting the cables, see Fig. 5-3.
5-4
© SICK AG · Auto Ident · Germany · All rights reserved
8008869/RA61/2007-07-30
Page 27
Electrical installation
Operating Instructions
Chapter 5
OTS400
Danger of irreparable damage to the OTC400 When operating the OTC400 as a stand-alone device: ¾ The power supply for the bar code readers may only be supplied at the 24V and 0V terminals in the CAN field. The correct currents are only available at these terminals.
Abb. 5-3: Ansicht OTC400
4: CAN H 5: CAN L 3: GND 2: +24V 1: Shield
Plug-in jumpers
Fig. 5-3: OTC400 - front view
The cables for connecting the individual bar code scanners are available in 3 different lengths: Order No.
Length
Article
6021166
5m
Supply cable (1x open end/ 1x socket)
6021175
10 m
Supply cable (1x open end/ 1x socket)
6021164
0.7 m
Cable (1x connector/ 1x socket)
6021165
3m
Cable (1x connector/ 1x socket)
6021168
5m
Cable (1x connector/ 1x socket)
6021293
10 m
Return cable (1x connector/ 1x open end)
Table 5-7: Length of cables
8008869/RA61/2007-07-30
© SICK AG · Auto Ident · Germany · All rights reserved
5-5
Page 28
Chapter 5
Electrical installation
Operating Instructions OTS400 Omni Tracking System
The connector cover with EEPROM parameter memory (no. 2021264) should be attached between the connection cables and the bar code scanner. The operating principle of the connector cover is described in detail in the CLV490 Operating Instructions. The basic design is shown in Fig. 5-4. The last bar code scanner is provided with a terminating resistor (no. 6021167). This is also pluggable. A maximum of 2 branch lines per OTS400/ OTC400 are possible.
Fig. 5-4: CLV490 bar code scanner with connector cover and connection cables
5.5.1
Connecting the incremental encoder
An incremental encoder is to assign the bar codes to the various objects and must be connected directly to the OTC400. The terminal INC 1 is provided for this purpose. The plug-in jumper "0V – OV 3" is used to connect the frame potential of the incremental encoders with the frame potential of the OTC400 (top position of the plug-in jumper), if the latter is to be powered via the OTC400. The terminal strip below the INC 1 terminal is used to connect the power supply. Otherwise, the external potential should be assigned to the incremental encoder (bottom position of the plug-in jumper). A dual-channel incremental encoder can also be connected if necessary. The OTC400 then evaluates the two phase-shifted signals. Switching behavior:
Provision of an incremental signal at a distance of 10 to 15 mm per increment. Between 4 and 5 increments should be always available for the smallest object gap. See Fig. 5-5.
Characteristics:
Opto-decoupled, non-interchangeable
Electrical values:
Low: –10V ≤ Vi ≤ +10V; –3mA ≤ Ii ≤ +3mA High: –30V ≤ Vi ≤ –15V; –10mA ≤ Ii ≤ –5mA High: +30V ≤ Vi ≤ +15V; +10mA ≤ Ii ≤ +5mA
Table 5-8: Characteristic data of the "incremental encoder" input
5-6
© SICK AG · Auto Ident · Germany · All rights reserved
8008869/RA61/2007-07-30
Page 29
Operating Instructions
Electrical installation
Chapter 5
OTS400
5.5.2
Connecting the reading pulse sensor
The TRIGGER 1 terminal is provided for connecting the reading pulse sensor. The plug-in jumper "0V – OV 1" is used to connect the ground potential of the reading pulse sensor with the ground potential of the OTC400 (top position of the plug-in jumper), if the latter is to be powered via the OTC400. The terminal strip below the TRIGGER terminal is used to connect the power supply. Otherwise, the external potential should be assigned to the reading pulse sensor (bottom position of the plug-in jumper). A 2nd and 3rd reading pulse sensor (TRIGGER 2 or 3) can also be connected, with power supply and assigned ground potential (plug-in jumper "0V – 0V2"). Switching behavior:
Start reading interval when input is live (default: active high, de-bouncing: standard). For connection diagram, see Fig. 5-5.
Characteristics:
Opto-decoupled, non-interchangeable
Electrical values:
Low: –10V ≤ Vi ≤ +10V; –3mA ≤ Ii ≤ +3mA High: –30V ≤ Vi ≤ –15V; –10mA ≤ Ii ≤ –5mA High: +30V ≤ Vi ≤ +15V; +10mA ≤ Ii ≤ +5mA
Table 5-9: Characteristic data of the "TRIGGER 1, 2, and 3" inputs
5.5.3
Connecting sensors
Additional sensors can be connected if necessary. The SENSOR 1 (1-1 ...1-7) and SENSOR 2 (2-1 ... 2-4) terminal strips are provided for this purpose. A plug-in jumper (0V – 0V4) is also available for SENSOR 1. At present, the switching function is not defined and can be configured by the customer. Switching function:
Undefined. See Fig. 5-5.
Characteristics:
Opto-decoupled, non-interchangeable
Electrical values:
Low: –10V ≤ Vi ≤ +10V; –3mA ≤ Ii ≤ +3mA High: –30V ≤ Vi ≤ –15V; –10mA ≤ Ii ≤ –5mA High: +30V ≤ Vi ≤ +15V; +10mA ≤ Ii ≤ +5mA
Table 5-10: Characteristic data of the "SENSOR" inputs
Fig. 5-5: Input circuits
The GND shown in Fig. 5-5 is the external GND. To connect this to the internal GND, change the jumper setting.
8008869/RA61/2007-07-30
© SICK AG · Auto Ident · Germany · All rights reserved
5-7
Page 30
Electrical installation
Chapter 5
Operating Instructions OTS400 Omni Tracking System
5.5.4
Connecting the outputs
The 4 switching outputs and the relay output can be assigned various result functions, independent of one another. If the associated event occurs during the read operation, the corresponding output becomes live at the end of the reading pulse for the selected pulse duration. Switching outputs: The 4 outputs have the same characteristic data. Switching behavior:
Switches with respect to the supply voltage VS and ground
Characteristics:
Short-circuit-proof, temperature-protected, not electrically isolated from Vs
Function assignment (defaults)
Output 1: "Device ready" (static), output 2: "Good read", output 3: "No read", Output 4: "Data pulse", pulse duration 100ms
Electrical values:
0V ≤ Vo ≤ Vs Io ≤ 100mA
Guaranteed: Vo ≥ Vs –2.5V for Io ≤ 100mA
Table 5-11: Characteristic data of the 4 switching outputs
1)
Vs Short circuit monitor
Temperature monitor
Fig. 5-6: Circuit diagram of the 4 switching outputs (Here: output 1 in detail)
Relay output:
Characteristics:
Not short-circuit-proof, not temperature-protected, electrically isolated, floating
Function setting (defaults) Relay output: "Device ready" (static) Electrical values:
Alternating voltage/direct voltage 0V ≤ VSWITCH ≤ 250V according to VDE 0110 group C Max. current 1.5 A for 24 V DC Max. current 0.2 A for 250 V DC Max. current 1.5 A for 250 V AC
Table 5-12: Characteristic data of the relay output
5-8
© SICK AG · Auto Ident · Germany · All rights reserved
8008869/RA61/2007-07-30