Issue: 09/02/95 Technical Description "Network Controller CLX 200"

2. Error message: Failure of station in network

The CLX 200 now also issues an error message when a network station in network operation fails. Only the station number of the station which failed first is given whereas all station failures are recorded on the terminal interface.

#06 Network failure Failure of a network station (with identification)

The CLX 200 continues to poll faulty stations but the intervals between polling are longer.

3. CLX 200 operating and parametrization menu

Values printed in bold are set as the basic setting by factory.

Parametrization Net interface Baud rate *19200 Bd

| | *38400 Bd

| SW handshake ____ *No

| *Yes

|

Host interface Data format. Baud rate *300,.., 9600,.., 38400 Bd Data bits *7 | *8 Parity *no | *even | *odd | *space | *mark Stop bits *1

*2

*Block telegram___Separator *20 Output interval __ *0 .. 999 ms Max. Tele. length _ *10 ... 4000 Byte

| | | | | | | | | Output format ____ *Single telegram | | | | SC version’)__ *INo/ Yes |

Terminator *03 00 00 00...

|

| Prot. check digit __*No/ Yes

| SW handshake _*No

| | * ACK/ NAK framed | | *ACK/ NAK unfram. | Prot. time-out __*100 ,.., 2000...

| | 6000 ms | | | | *

Interface control__ *No *RTS/ CTS *XON/ XOFF 3964 3694R (BCC)___ *Yes/ No Priority high ____ *Yes/ No RK512__ ss Sele excerpt 7

| | | | | | | | | | | | | | | | | Protocol *Standard (Sick) Header. *02 00 00 00.. | | | | | | | | | | | | | |

Fig. 1. Summary of menu (software version V 2.10)

Erwin Sick GmbH, Optik-Elektronik, Material Handling Automation, Nimburger StraBe 11, D-79276 Reute Page 61

Page 62 read from a scan by OCR; it may hold reading errors

Technical Description "Network Controller CLX 200" Issue: 09/02/95 menu continued:

*Output configuration : | Standard configuration *No

*Yes

|

|

|

|

|

|

Language shift *deutsch © Start of menu *english *italiano *francais

|

|

|

|

Quit menu *temporary *no change *permanent

1) SC Version: Block length of data block in double byte, number of separator characters completes data block length to an even number of bytes. After the last data block 2 ASCII characters "F" are transmitted.

Fig. 2. Summary of menu (continued)

Excerpt 1 RK 512 *No *Yes Header Position 4 *DA XM | Position 5/ 6 *00 00 | Position 9 *00 | Position 10 *00 Reaction telegram ____*Yes/ No Fill character *00

Fill character pos. *beginning/ end

Fig. 3. Excerpt of menu

Page 62 Erwin Sick GmbH, Optik-Elektronik, Material Handling Automation, Nimburger StraBe 11, D-79276 Reute

Page 63 read from a scan by OCR; it may hold reading errors

Issue: 04/05/95 Technical Description "Network Controller CLX 200"

15.3 Software version V 2.20

Bases on the software version V 2.11 the CLX 200 contains the following new features:

e Priority list for network stations (max. 6 stations) e Advanced data output of the high-priority stations

1. General

In system components, in which the flow of goods is routed via a central point of distribution to the various processing locations, there are more elaborate requirements on the real time capabilities of the identification system in these points of distribution. The goods pass the central point of identification to be further routed at the point of distribution to the various processing stations. During the "travel time’ from identification to distribution the object must have been identified and the total signal path from identification to activation of the distributor” been completed.

In systems with bar code readers CLV 2xx and a network controller CLX 200 with "network priority list’, in such cases the data transmission from the scanner to the processing computer can be optimised.

2. Network operation 2.1. Priority list for network stations

For priority control in the CLX 200 a list of scanner stations, to which certain priorities are to be allocated, are parametrized in the CLX 200 menu. This group of stations is only called in parametrizable intervals. An input of 3 or 40 during “polling” results in the stations parametrized in the priority list to be always called after 3 or 40 interrogations of other stations (see example). The stations parametrized in the priority list are interrogated (polling) independent from their existence in the network. The value "00" signals the end of the priority list.

Example:

There are 8 CLV in the network. Station numbers 1 to 8 are allocated stations 1 and 2 being the ones with priority. This group is to be always polled after 3 other stations. The processing sequence of the network stations is then the following:

12 34512 678 12 x34 12 567 12..

The station number "x" represents a "search station", which can be re-entered in the poll list after each polling run.

2.2. Polling cycle time

The use of the priority list results in two different poll cycle times. These are determined by the parameters in the parametrization menu of the CLX 200.

Erwin Sick GmbH, Optik-Elektronik, Material Handling Automation, Nimburger StraBe 11, D-79276 Reute Page 63

Page 64 read from a scan by OCR; it may hold reading errors

Technical Description "Network Controller CLX 200" Issue: 04/05/95

2.2.1. Standard stations

The poll run time for the stations not parametrized in the priority list (standard stations) depends on the number of the stations existing in the network and on the parameters for the stations in the priority list.

TPoll cycle time = (P+ 1 + (2-2 )) x TPoll

TPoll cycle time: time between successive interrogations of a certain station p: number of stations identified by the network controller excluding those entered in the priority list

1: additional poll for a station to be added n: number of interrogated stations not contained in the priority list (menu parameter "poll scheme - n + prio. list")

m: number of stations contained in the priority list

TPoll: duration of a poll (11 ms at 19 200 Bd/ 6 ms at 38 400 Bd)

2.2.2. Priority stations

The poll run time for the stations contained in the priority list depends on the number of stations existing in the network.

TPoll cycle time = (n +m) x TPoll

TPoll cycle time: time between successive interrogations of a certain station n: number of interrogated stations not contained in the prority list (menu parameter "poll scheme - n+ pro. list")

m: number of stations contained in the priority list

TPoll: duration of a poll (11 ms at 19 200 Bd/ 6 ms at 38 400 Bd)

3. Data output at the Host interface

The data available to the CLX 200 by polling are transmitted to the host computer. The data of the parametrized stations can in the output format "single telegram" then be dealt with priority during host output (not with output format "block telegram’’). Should at the beginning of a new data output several data strings be contained the data buffer of the CLX 200, the data of the parametrized stations in the priority list will be output first. This allows maximum data cycle times to be calculated for the stations identified in the priority list. These data cycle times result from the constant poll cycle time for a given parametrization and the data processing times on the network and the host interface. The data output of the remaining stations is on wait until these data have been output.

3.1. Display mode "Data buffer"

Starting from software version V2.20 a further indication mode (D 5) is implemented. By pressing the [ENTER] key on the equipment keyboard, after indication of the stations existing in the network (D 4) the data strings currently in output are displayed. If the amount of data read by the network per unit of time exceeds the amount of data that can be output on the host interface, the output buffers of the CLX 200 are used for the intermediate data buffering. For each of the 32 data buffers a position on the display is reserved (point presentation). The current load state of the buffer is displayed as bar diagram. The maxi-

Page 64 Erwin Sick GmbH, Optik-Elektronik, Material Handling Automation, Nimburger StraBe 11, D-79276 Reute

Page 65 read from a scan by OCR; it may hold reading errors

Issue: 04/05/95 Technical Description "Network Controller CLX 200" mum value is recorded and indicated on the display as a bar. The maximum value identification is also active with another display mode selected. The maximum value on the display is cleared by pressing the [=] key.

In this display mode the influence of the host protocol in use or the host baud rate may then be observed. This setting provides assistance in the selection of the suitable interface parameters.

4. CLX 200 operating and parametrization menu

Values printed in bold are set as the basic setting by factory.

Parametrization Net interface Baud rate *19200 Bd

| | *38400 Bd | SW handshake ___ *No/ Yes | Poll function__ *Standard | *Prio .controlled ___Prio. list *00 00 00 00... | Poll scheme _____s*1,.. 5, .99 + | Prio. list | Data output____- *Standard | *with prority | Host interface Data format Baud rate *300,.., 9600,., 38400 Bd

Data bits *7

| *8

Parity *no

| *even

| *odd

| *space

| *mark

Stop bits *1

*2

| | | | | | | | | | Output format ___ *Single telegram | *Block telegramm _Separator *20 | Output interval __ *0 .. 999 ms | Max. Tele. length _ *10 .. 4000 Byte | SC version)__ - s«*No/ Yes | Protocol *Standard (Sick) Header. *02 00 00 00... | Terminator ____*03 00 00 00... | Prot. check digit _*INo/ Yes | SW handshake _*No | | *ACK/ NAK framed | | *ACK/ NAK unfram. | Prot. time-out __*100 ,.., 2000... | | 6000 ms | Interface control__ *No | *RTS/ CTS | |

| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | *XON/ XOFF |

Fig. 1. Summary of menu (software version V 2.20}

Erwin Sick GmbH, Optik-Elektronik, Material Handling Automation, Nimburger StraBe 11, D-79276 Reute Page 65

Page 66 read from a scan by OCR; it may hold reading errors

Technical Description "Network Controller CLX 200" Issue: 04/05/95 menu continued:

* 3964 3694R (BCC) *Yes/ No RK 512 see excerpt 7

| | | Priority high _____s *Yes/ No | | |

*Output configuration

| Standard configuratio_ *No

*Yes

Language shift *deutsch © Start of menu *english *italiano *francais

|

|

|

Quit menu *temporary *no change *permanent

1) SC Version: Block length of data block in double byte, number of separator characters completes data block length to an even number of bytes. After the last data block 2 ASCII characters "F" are transmitted.

Fig. 2. Summary of menu (continued)

Excerpt 7 RK 512 *No *Yes __ - s Header Position 4 *DAXM | Position 5/ 6 *00 00 | Position 9 *00 | Position 10 *00 Reaction telegram ___*Yes/ No Fill character *00

Fill character pos. *beginning/ end

Fig. 3. Excerpt of menu

Page 66 Erwin Sick GmbH, Optik-Elektronik, Material Handling Automation, Nimburger StraBe 11, D-79276 Reute

Page 67

This page is a scan with no text; see it in the PDF.

Page 68

8007157/06-1993 • 5M/TR <PM6.5/Word97/PDF>/VD . Printed in Germany . Subject to change without notice . The specified product features and technical data do not represent any guarantee . 05 Aft int55

Australia Phone +61 3 9497 4100 1800 33 48 02 – tollfree E-Mail sales@sick.com.au Belgium/Luxembourg Phone +32 (0)2 466 55 66 E-Mail info@sick.be Brasil Phone +55 11 5091-4900 E-Mail sac@sick.com.br Ceská Republika Phone +420 2 57 91 18 50 E-Mail sick@sick.cz China Phone +852-2763 6966 E-Mail ghk@sick.com.hk Danmark Phone +45 45 82 64 00 E-Mail sick@sick.dk Deutschland Phone +49 (0)2 11 53 01-270 E-Mail info@sick.de España Phone +34 93 480 31 00 E-Mail info@sick.es France Phone +33 1 64 62 35 00 E-Mail info@sick.fr Great Britain Phone +44 (0)1727 831121 E-Mail info@sick.co.uk India Phone +91–22–2822 7084 E-Mail info@sick-india.com Italia Phone +39 02 27 40 93 19 E-Mail info@sick.it

Österreich Phone +43 (0)22 36 62 28 8-0 E-Mail office@sick.at Polska Phone +48 22 837 40 50 E-Mail info@sick.pl Republic of Korea Phone +82-2 786 6321/4 E-Mail kang@sickkorea.net Republika Slowenija Phone +386 (0)1-47 69 990 E-Mail office@sick.si Russia Phone +7 95 775 05 30 E-Mail info@sick-automation.ru Schweiz Phone +41 41 619 29 39 E-Mail contact@sick.ch Singapore Phone +65 6744 3732 E-Mail admin@sicksgp.com.sg Suomi Phone +358-9-25 15 800 E-Mail sick@sick.fi Sverige Phone +46 8 680 64 50 E-Mail info@sick.se Taiwan Phone +886 2 2365-6292 E-Mail sickgrc@ms6.hinet.net Türkiye Phone +90 216 388 95 90 pbx E-Mail info@sick.com.tr USA/Canada/México Phone +1(952) 941-6780 1 800-325-7425 – tollfree E-Mail info@sickusa.com

Japan Phone +81 (0)3 3358 1341 E-Mail info@sick.jp Nederlands Phone +31 (0)30 229 25 44 E-Mail info@sick.nl Norge Phone +47 67 81 50 00 E-Mail austefjord@sick.no

SICK AG | Waldkirch/Reute | Germany | www.sick.com

More representatives and agencies in all major industrial nations at www.sick.com