Page 1

9

Technical Reference Data

B7A

The following information applies to all B7A Series Link Modules 1 Connecting B7A to a programmable

1 Signal configuration examples for inputs controller and outputs

1 Peripheral circuits of printed circuit

1 I/O ON/OFF conditions 1 Precautions 1 Recommended cables 1 Mounting guidelines board B7A models

1 Noise protection circuits recommended 1 Transmission errors and output signals

Operation 3 CONNECTING B7A TO A PROGRAMMABLE CONTROLLER Each terminal of the B7A should be used for only single signal transmission without a transmission host. Therefore the B7A cannot be connected to OMRON’s SYSMAC BUS Remote I/O System. To transmit signals from the B7A to a programmable controller, connect the B7A’s terminals to an I/O module mounted on the PLC.

3 RECOMMENDED COMBINATIONS OF OMRON PLC I/O MODULES AND B7A LINKS Outputs B7A Link Module

Conditions of PLC

C500 I/O Modules

C200H I/O Modules

ID213

ID218

ID219

ID212

ID215

ID501

ID216

ID217

12 to 24 VDC

12 to 24 VDC

24 VDC

24 VDC

24 VDC

5 VDC

24 VDC

24 VDC

+ common

+/-common

+ common

+/-common

+/-common

+/-common

+/-common

+/-common

16 points

32 points

64 points

16 points

32 points

32 points

32 points

64 points

B7A-R6B11 B7A-R6B31 B7A-R6B16 B7A-R6B36 B7A-R6A52 B7A-R6A57 B7AS-R6B11 B7AS-R6B31 B7AS-R6B16 B7AS-R6B36 B7AM-6BS B7AM-8B11 B7AM-8B31 B7AM-8B16 B7AM-8B36 B7A-R10SC01 B7A-R10MC

DC or AC/DC input and + common or +/-- common (-- common if the PLC with non--voltage input is used.)

Yes

Yes

Yes

Yes

Yes

Yes (See Note)

Yes

Yes

B7A-R6F11 B7A-R6F31 B7A-R6F16 B7A-R6F36

DC or AC/DC input and -- common or +/-- common (+ common if the PLC with non--voltage input is used.)

No

Yes

No

Yes

Yes

No

Yes

Yes

Note: An independent power supply for the PLC is required due to the difference in operating voltage between the PLC and B7A.

Page 2

B7A Technical Reference

B7A Technical Reference Input B7A Link Module

Conditions of PLC

C500 I/O Module

C200H I/O Module

OC221

OD212

OD412

OC225

OD215

OD212

OD218

OD219

Relay output

PNP output

NPN output

Relay

NPN output

NPN output

NPN output

NPN output

24 VDC

12 to 24 VDC

12 to 48 VDC

24 VDC

5 to 24 VDC

24 VDC

5 to 24 VDC

24 VDC

16 points

32 points

32 points

16 points

32 points

16 points

32 points

64 points

B7A-T6A1 B7A-T6A6 B7A-T6B1 B7A-T6B6 B7AS-T6B1 B7AS-T6B6 B7AM-6BS B7AM-8B11 B7AM-8B31 B7AM-8B16 B7AM-8B36 B7A-T10S1 B7A-T10S3

NPN transistor output (residual voltage must be 1.6 V max. if the B7A has 10 output points.) Relay output

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

B7A-T6C1 B7A-T6C6

PNP transistor output, relay output

Yes

Yes

No

Yes

No

No

No

No

B7A-T6D2 B7A-T6D7

TTL output (See Note 1), PNP transistor output

See note 2

Yes

See note 2

See note 2

See note 2

See note 2

See note 2

See note 2

B7A-T10M2

TTL output (See Note 1)

See note 2

See note 2

See note 2

See note 2

See note 2

See note 2

See note 2

See note 2

Note: 1. An independent power supply for the PLC is required due to the difference in operating voltage between the PLC and B7A. 2. An external interface unit is required.

2

Page 3

B7A Technical Reference

B7A Technical Reference 3 EXAMPLES OF CONNECTIONS WITH PLC I/O MODULES PLC output

B7A input

3G2A5-OD212

B7A-T6CP Transmission path

12 to 24 VDC

B7A output B7A-R6BPP

PLC input 3G2A5-ID213

12 to 24 VDC

Transmission path

Any one of B0 through B15 can be used.

3G2A5-OD412 Transmission path

B7A-T6AP

B7A-R6BPP

12 to 24 VDC

24 VDC

3G2A5-ID219

Transmission path

Any one of B0 through B15 can be used.

Note: The B7A-T6BP can be connected in the same method. C200H-OC225

B7A-T6AP Transmission path

24 VDC

B7A-R6FPP

C200H-ID212

24 VDC

Transmission path

Any one of B0 through B15 can be used.

Note: The B7A-T6BP can be connected in the same method.

3

Page 4

B7A Technical Reference

B7A Technical Reference PLC output

B7A input

C200H-OD212

B7A-T6AP Transmission path

B7A output B7A-R6A5P

PLC input 3G2A5-ID218

24 VDC

24 VDC

12 to 24 VDC

Note: The B7A-T6BP can be connected in the same method. Transmission path

3G2A5-OC221

B7A-T6DP

B7A-R6A5P 24 VDC

Transmission path R=18 kΩ (1/10W min.)

24 VDC

C200H-OD215

Transmission path

B7A-T6DP Transmission path 12 to 24 VDC R=4.7 kΩ (1/2W min.)

4

C200H-ID215

Page 5

B7A Technical Reference

B7A Technical Reference

3 PERIPHERAL CIRCUITS OF PRINTED CIRCUIT BOARD MODELS The printed circuit board model has a minimum ON discrimination voltage of 2.2 V and a maximum OFF discrimination voltage of 0.8 V, which are suitable for TTL circuits. If sensors are used for input, the following input circuits are required.

Input with B7A and Common Power Supply 12 to 24 VDC, 10-point PCB Model only The 10-point printed circuit board model has an input voltage range of 0 to 5 VDC. If a common power supply is connected, current limit resistor R3 is required as shown in the diagram below. Use the following formula to calculate the value of R3.

Two--wire DC Sensor Input R3 =

If a two-wire DC sensor is used for input, current limit resistor R1 and leakage current diverter R2 are required as shown in the diagram below. The following table lists R1 and R2 values for the E2E-XD-N Two-wire DC Proximity Sensor (with a current leakage of 0.8 mA maximum, a residual voltage of 3 V maximum, and a minimum control output current of 3 mA).

Supply voltage VS (V) -- 1.4 (V) Input current (2 x 10 --3 (A)) Vs(12 to 24 VDC) +

Interior of B7A

IN

2.2 kΩ

Input Interface (E2E--XD--N) Supply voltage

12 V

24 V

R1

1,800 Ω

5,600 Ω

R2

820 Ω

820 Ω

+

R1

R3

--

Interior of B7A

Note: The 16-point module’s input voltage range is 0 V to the power supply voltage. Therefore no current limit resistor is required.

Intemal circuit

Two-wire DC proximity sensor

-- 2,200 (Ω)

Intemal circuit

Input Interface Circuit

IN

R2 --

3 NOISE PROTECTION CIRCUIT If there is a possibility of noise interference from the power supply, input, and/or output lines, add the following noise protection circuits. Power supply noise protection circuit

Input noise protection circuit

Output noise protection circuit

V1N + 12 to 24 VDC

R

Photocoupler

Input device R + V

ZD IN

C

B7A

R: 10 to 20 Ω (1/8 W min.) C: 33 µF min. with a dielectric strength of 50 V min.

Load

C

+ --

R +

Photocoupler C: 0.1 µF min. R: Photocoupler input current limit resistor

-B7A

IN Input device

V

OUT -B7A

R: Photocoupler input current limit resistor ZD: VZD = 36 V (with a power consumption of 1 W min.)

+ Load

ZD OUT

ZD

-ZD: VZD = 36 V (with a power consumption of 1 W min.)

-B7A B7A

ZD: VZD = 36 V (with a power consumption of 1 W min.)

5

Page 6

B7A Technical Reference

B7A Technical Reference 3 TRANSMISSION ERRORS AND OUTPUT SIGNALS Transmission errors occur in the following cases:

Output Signals

• When the signal or 0 V wire is disconnected. • When the signal is influenced by high-level external noise or the

HOLD: When an error occurs, the output signals just before the occurrence of the error will be maintained.

signal is excessively deformed because the length of the transmission path is more than the permissible distance.

LOAD OFF: When an error occurs, all output signals will be turned OFF.

• When the supply voltage to the Link Terminals are not within the

Automatic Reset

• Immediately after the Link Terminals are turned on.

When the error is corrected, the Link Terminals will automatically reset themselves.

operating voltage range (12 to 24 V ±10%).

(An error is reset within 300 ms after the power is turned on.)

3 I/O STATUS Signal Configuration Input Models Type

Applicable model

ON/OFF

Screw terminals

B7A-T6A1 B7A-T6A6 B7AM-6BS B7AM-8B11 B7AM-8B31 B7AM-8B16 B7AM-8B36 B7A-T10S1

For switches ON: Switch is closed. OFF: Switch is open.

B7A-T10S3

For photoelectric sensors and proximity sensors (NPN) ON: Sensor signal is ON (residual voltage is 1.6 V max.). OFF: Sensor signal is OFF.

Circuit

Suitable input example IN

SW _

+V

OUT Sensor

B7A-T6B1 B7AS-T6B1 B7A-T6B6 B7AS-T6B6 B7AM-6BS B7AM-8B11 B7AM-8B31 B7AM-8B16 B7AM-8B36

For photoelectric sensors and proximity sensors (NPN) ON: Sensor signal is ON (residual voltage is 4 V max.). OFF: Sensor signal is OFF.

B7A-T6A1 B7A-T6A6 B7A/S-T6B1 B7A/S-T6B6 B7AM-6BS B7AM-8B11 B7AM-8B31 B7AM-8B16 B7AM-8B36

For proximity sensors (two-wire sensor with DC output) ON: Sensor signal is ON (residual voltage is 4 V max.). OFF: Sensor signal is OFF (leakage current is 1.5 mA max.).

B7A-T6C1 B7A-T6C6 B7AM-8F31

For switches ON: Switch is closed. OFF: Switch is open.

IN

0V

_

+V

+

OUT Sensor

Sensor

+

_

+V

IN

+ SW

+V Sensor

For photoelectric sensors and proximity sensors (PNP) ON: Sensor signal is ON (residual voltage is 4 V max.). OFF: Sensor signal is OFF.

0V +V

OUT Sensor 0V

6

E2E-XPE 3-wire DC Inductive Proximity Sensor E3S Photoelectric sensor

E2E-XD-N 2-wire DC Inductive Proximity Sensor

--

IN

For proximity sensors (two-wire sensor with DC output) ON: Sensor signal is ON (residual voltage is 4 V max.). OFF: Sensor signal is OFF (leakage current is 1.5 mA max.).

WL01P Limit Switch

IN

0V

0V

A3G Push-button Switch (microload)

+

A3G Push-button Switch (microload) WL01P Limit Switch E2E-XD-N 2-wire DC Inductive Proximity Sensor

IN +

IN _

E2E-XPF 3-wire DC Inductive Proximity Sensor E3S Photoelectric sensor (PNP output type)

Page 7

B7A Technical Reference

B7A Technical Reference Input Models Type

Applicable model

Printed circuit board models (see note)

B7A-T6D2 B7A-T6D7 B7A-T10M2

ON/OFF For switches ON: Switch is closed. OFF: Switch is open.

Circuit

Suitable input example A3G Push-button Switch (microload)

+V IN SW

For NPN open-collector inputs ON: Transistor is OFF. OFF: Transistor is ON. (residual voltage is 0.8 V max.)

+V

IN 0 UT

+V + 0 UT

For IC (TTL, CMOS) inputs ON: Output is 2.2 V min. OFF: Output is 0.8 V max.

3G2A5-OD213 C200H-OD215 PLC Transistor Output Module

_

_

For PNP open-collector inputs ON: Transistor is ON. OFF: Transistor is OFF.

WL01P Limit Switch

IN

C200H-OD216 C200H-OD217 PLC PNP Output Module 3G2A5-OD501CN C200H-OD501 PLC TTL Output Module

TTL +5 V

IN _

CMOS

+5 V IN _

PLC Link Terminal Adapter

B7A-T6E3 B7A-T6E8 B7A-T3E3 B7A-T3E8

For PLC output unit, NPN open collector ON: Transistor ON OFF: Transistor OFF

OUT

B7A

------

IN

COM

--

Note: The positive input voltage range of the B7A-T6DP printed circuit board model is 0 to 24 VDC and the positive input voltage of the B7A-T10M2 printed circuit board model is 5 VDC.

7

Page 8

B7A Technical Reference

B7A Technical Reference Output Models Type Screw terminals

Output configuration

Applicable model B7A/S-R6B11 B7A/S-R6B31 B7A/S-R6B16 B7A/S-R6B36 B7AM-6BS B7AM-8B11 B7AM-8B31 B7AM-8B16 B7AM-8B36 B7A-R10SC01

NPN open collector

ON/OFF

Circuit

For PLC input ON: PLC is ON. OFF: PLC is OFF.

COM

+

IN

OUT

For relays and solenoids ON: Operates. OFF: Reset.

PLC

+ Load OUT

PNP open collector

B7A-R6F11 B7A-R6F31 B7A-R6F16 B7A-R6F36 B7AM-8F31

For PLC input ON: PLC is ON. OFF: PLC is OFF.

IN

OUT

COM

--

For relays and solenoids ON: Operates. OFF: Reset.

PLC

OUT Load

-Printed circuit board model

NPN open collector

B7A-R6A52 B7A-R6A57 B7A-R10MC

For PLC input ON: PLC is ON. OFF: PLC is OFF.

COM

+

IN

OUT

For relays and display terminal ON: Operates. OFF: Reset.

PLC

5 to 24 VDC Load OUT

For IC (TTL, CMOS) ON: Input is Low. OFF: Input is High.

+5V

OUT

GND

--

Link master adapter

NPN open collector

B7A-R6A13 B7A-R6A18 B7A-R6A33 B7A-R6A38 B7A-R3A13 B7A-R3A18 B7A-R3A33 B7A-R3A38

For PLC input module, + common photocoupler input ON: PLC is ON. OFF: PLC is OFF.

B7A

+

OUT

COM

IN

3 I/O ON/OFF CONDITIONS Input

Output Screw terminal

Screw terminal

Printed circuit board Active high (N/P open)

Active low (N/P 0 V)

Link master adapter

ON

ON

OFF

ON

ON

OFF

OFF

ON

OFF

OFF

Printed circuit board

ON

ON

OFF

ON

ON

OFF

OFF

ON

OFF

OFF

Link master adapter

ON

ON

OFF

ON

ON

OFF

OFF

ON

OFF

OFF

8

Page 9

B7A Technical Reference

B7A Technical Reference

Precautions 3 GENERAL Each terminal of the B7A-series should be used for only single signal transmission without a transmission host. The B7A-series cannot be connected to OMRON’s SYSMAC BUS Remote I/O System. Avoid places subject to corrosive gasses or continual shock and/or vibration.

Do not apply a strong acidic or alkaline solvent to the printed circuit board to remove the flux. The 10-point PCB version of B7A does not have sealed construction, so the cleaning solvent must not remain on the bottom of the module after it is cleaned. The 16-point PCB version of B7A does have sealed construction. The input and output circuits are not isolated. If Link Terminals are influenced by external noise, use photocouplers to isolate the I/O circuits.

If high-level electrostatic discharge is generated at the installation site (e.g., for transfer of a molding material, powder, or liquid through a pipe), separate the Link Terminals as far as possible from the source of the electrostatic discharge.

3 LINK MASTER ADAPTERS

If the Input and Output Terminals are connected via a threeconductor cable to transmit signals with a single power supply (i.e., the power supply is connected directly to one of the Link Terminals and indirectly to the other), the transmission distance greatly varies with the diameter of the cable. This is due to the potential difference between the current on the 0 V transmission wire and on the 0 V I/O transmission line caused by the resistance of the cable. By increasing the diameter of the cable (decreasing its resistance), the transmission distance can be increased. By reducing the resistance of the transmission path to 2.5 Ω or less for example (i.e., increasing the thickness of the wire to 1.25 mm2 or more), a transmission distance of 160 m will be achieved.

Wire the screw terminals of the adapter while disconnected from the PLC I/O module. This avoids imposing excessive force on the PLC’s I/O connector.

It is recommended that a switch for minute loads be connected to the 16-point screw terminal model because there is a contact input current of only 3 to 6 mA to the model from the connected switch or relay. The Output Terminal has an error of 300 ms maximum after the Output Terminal is turned on. The user should be well aware of this before using error outputs. Note: The 10-point and 16-point models cannot be connected to each other because their transmission signal data formats are not compatible.

3 SCREW TERMINAL MODELS Apply a torque of 8 to 12 kgf : cm (0.78 to 1.18 N : m) to tighten wiring terminals. Lift both edges of the terminal cover to open it.

Apply a torque of 8 to 12 kgf : cm (0.78 to 1.18 N : m) to tighten wiring terminals.

Use the correct combination of B7A modules and PLC modules or the B7A may be damaged. The following are correct combinations. B7A Input Module and PLC Output Module B7A Output Module and PLC Input Module

3 WIRING Separate the transmission lines from high voltage or power lines as far away as possible and do not wire the transmission lines in parallel with high voltage or power lines. If Link Terminals are used near a device that generates noise, make sure that the Link Terminals do not malfunction due to the noise generated from the device. Make sure to turn off the Link Terminals while wiring in order to avoid a short--circuiting accident that may damage the internal element(s) of the Link Terminals. Link Terminals will malfunction if the SIG terminal is short--circuited with one of the power terminals or BPP terminal. Before turning the power on, make sure that the SIG terminal is not short--circuited with these terminals. Before checking the insulation resistance of the transmission path, disconnect the wires from the Link Terminals. If the OUT terminal and positive power terminal of the Output Link Terminal is short--circuited during signal transmission, the Link Terminal will malfunction. Apply an appropriate load between these terminals. When measuring the current, use a multimeter without disconnecting the load.

3 RECOMMENDED CABLES If the Input or Output Terminal is mounted to a panel with screws, apply a torque of 6 to 10 kgf : cm (0.59 to 0.98 N : m) to tighten the screws.

3 PRINTED CIRCUIT BOARD MODELS Soldering (with a soldering iron or in a soldering bath) must be completed within 5 s at a temperature of 260°C or less. The supply voltage must be within the operating voltage range. Do not use a power supply which generates irregular voltages or large ripples.

For B7A with Normal Speed I/O Delay VCTF Cable When a single power supply is used for two Input Terminals or Output Terminals: VCTF 0.75 x 4 C (B7AM) VCTF 0.75 x 3 C (B7A/S/C) When independent power supplies are connected to each Link Terminal: VCTF 0.75 x 3 C (B7AM) VCTF 0.75 x 2 C (B7A/S) The following cable can also be used.

9

Page 10

B7A Technical Reference

B7A Technical Reference Twisted-pair Wire When a single power supply is connected to either the Input Terminal or Output Terminal, the thickness of the wire must be 0.75 mm2 or greater. Transmission distance: 100 m max.

3 MOUNTING To mount the Input or Output Terminal to a DIN track, hook the upper part (A) on the DIN track first. Then press the Input or Output Terminal in the (B) direction.

For B7A with High Speed Shielded Wire Use a shielded wire with a thickness of 0.75 mm2 min.

(A)

3 COLOR Screw Terminal Models Marked “IN” in white ink. The background is red.

(B)

When mounting more than two Input or Output Terminals side by side, leave a space of 3 mm minimum between each Terminal. It is recommended that PFP-S Spacers be used to maintain a space of 3 mm between each Input or Output Terminal. Input Terminal Marked “OUT” in black ink. The background is yellow.

Output Terminal

3 mm min.

Insert a flat--blade screwdriver to part (C) to remove the Input or Output Terminal from a DIN track.

30 mm min. (C) Rail lock

NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.