B7A Technical Reference Data
Manual10 pagesPDF 244 KB
Technical reference for Omron B7A series link terminals, including the B7AS-T6B1 input terminal, and their use with Omron PLC I/O modules.
Covers · 1 model
The models it covers
Summary
What is in it
Technical reference data that applies to all Omron B7A series link modules, including the B7AS-T6B1 input terminal. It shows which B7A input and output link terminals work with which C500 and C200H PLC I/O modules, gives connection examples, peripheral and noise protection circuits for the printed circuit board models, transmission errors and output signals, I/O status and ON/OFF conditions, and precautions for wiring, cables, link master adapters, screw terminal models, soldering and DIN track mounting.
Its parts
- Operation
- Precautions
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
This is Omron's B7A Technical Reference Data, which applies to all B7A Series Link Modules, including the B7AS-T6B1 input model the site files it under. It shows how to connect B7A link terminals to Omron C500 and C200H PLC I/O modules, with input and output circuits, noise protection and transmission error behavior. It also gives wiring, cable, mounting and soldering precautions.
- Device
- B7A Series Link Module (link terminal) for single-signal transmission without a transmission host p. 1
- B7AS-T6B1 inputs
- B7AS-T6B1: input model for NPN photoelectric and proximity sensors (ON residual voltage 4 V max.) p. 6
- Supply voltage
- 12 to 24 V ±10% p. 6
- PLC connection
- Through a PLC I/O module: B7A input module with PLC output module, B7A output module with PLC input module p. 1, 9
- Error behavior
- On a transmission error, HOLD keeps the last outputs or LOAD OFF turns all outputs OFF; automatic reset p. 6
- Power-on error
- An error is reset within 300 ms after power on p. 6
- VCTF cable
- Normal-speed B7A/S: VCTF 0.75 x 3 C with one shared power supply; VCTF 0.75 x 2 C with independent supplies p. 9
- Twisted-pair wire
- 0.75 mm2 or greater with a single power supply; 100 m max. p. 10
- High-speed cable
- High-speed B7A: shielded wire, 0.75 mm2 min. p. 10
- Longer distance
- Path resistance 2.5 Ω or less (1.25 mm2 wire or more) gives 160 m p. 9
- Mounting
- DIN track; 3 mm min. between terminals side by side (PFP-S Spacers recommended) p. 10
- Terminal torque
- Screw terminal models: 8 to 12 kgf·cm (0.78 to 1.18 N·m) p. 9
- Panel screw torque
- 6 to 10 kgf·cm (0.59 to 0.98 N·m) p. 9
What this manual walks you through
- Connecting B7A link terminals to Omron C500 and C200H PLC I/O modules p. 1, 2, 3, 4
- Sensor input circuits and resistor values for printed circuit board models p. 5
- Adding noise protection circuits on power, input and output lines p. 5
- Causes of transmission errors and how outputs respond p. 6
- Matching input and output models to switches, sensors and loads p. 6, 7, 8
- Wiring precautions for transmission lines and terminals p. 9
- Choosing cables for the needed transmission distance p. 9, 10
- Mounting on and removing from a DIN track p. 10
Good to know
- B7A terminals cannot be connected to Omron's SYSMAC BUS Remote I/O System. p. 9
- 10-point and 16-point models cannot be connected to each other; their data formats differ. p. 9
- The input and output circuits are not isolated; use photocouplers if external noise affects them. p. 9
- A wrong pairing of B7A and PLC modules may damage the B7A. p. 9
- The terminals malfunction if the SIG terminal is shorted to a power terminal or the BPP terminal. p. 9
Questions this manual answers
Can the B7AS-T6B1 connect to a SYSMAC BUS Remote I/O system?
No. The reference states B7A-series terminals cannot be connected to SYSMAC BUS Remote I/O; they connect to an I/O module on the PLC. p. 1, 9
What supply voltage do B7A link terminals need?
12 to 24 V, within ±10%. A supply outside that range is listed as a cause of transmission errors. p. 6
What happens to B7A outputs when a transmission error occurs?
In HOLD, outputs keep the state they had just before the error; in LOAD OFF, all outputs turn OFF. The terminals reset themselves once the error is corrected. p. 6
What cable should be used with B7A link terminals?
For normal-speed B7A/S, VCTF 0.75 x 3 C when two terminals share one power supply, or VCTF 0.75 x 2 C with independent supplies. Twisted-pair wire reaches 100 m max. p. 9, 10
How is a B7A terminal mounted on a DIN rail?
Hook the upper part on the DIN track, then press the terminal in. Leave at least 3 mm between terminals mounted side by side. p. 10
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 1 part
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.