Page 11
Attach Cabling
Under ideal conditions, maximum cable lengths can match the distances shown in table 1-1. However, since cable lengths and sizes are dictated by local conditions such as wire size, wire shape (flat or round), shielding, grounding, extraneous signal noise, etc., maximum cable distances will vary.
1–Setup and Inst.
2 Attach Cabling
Table 1-1 Cable Distances
Maximum Distance
Cabling
RS-232 Decoder to Host 50 ft. (15.2 m) RS-422 Decoder to Host 4000 ft. (1219 m) Decoder to Scan Head
15 ft. (4.57 m)
RS-485 Multidrop Trunk
4000 ft. (1219 m)
RS-485 Multidrop Drop
10 ft. (3 m)
Front Panel Connectors The MS-3000 decoder has six I/O connectors. On the front panel (figure 1-2) there are the following two connectors: a. Trigger (Microscan or other object detector) (6-pin DIN socket) b. Scan head (modular RJ-45)
PW R TRIG
SC AN
IND2
IND1
Figure 1-2 Front Panel
MS-3000 Single Head Decoder User’s Manual
1-3
Page 12
Chapter 1 Setup and Installation
Trigger Connector
The trigger connector (TRIG) is a 6-pin DIN socket (figure 1-3) that mates with a 240 degree 6-pin DIN plug. Pin assignments are shown in table 1-2.
Table 1-2 Trigger Connector Pin Assignments os) a = xo) c © Q. S Sond ® a =
Pin Function
Trigger Input +3 VDC to + 24 VDC
TTL Relay driver output signal 5 VDC
+5 VDC +12 VDC
Ground
Figure 1-3 Trigger Connector Socket oO }o |; |wo
Not used
Pin 1 is the input from the object detector. When operating the decoder in external trigger mode, a toggle at this pin causes the decoder to begin a read cycle.
Pin 2 of the trigger connector is a programmable relay driver. The MS-3000 software can be programmed to set this pin high or low upon a good read, a no read, a good match, or a mismatch. This pin can source or sink 4 mA (maximum) and can be used to drive a small relay to operate an alarm, diverter, etc.
Microscan offers an optical object detector (P/N 99-440001-03) that plugs directly into this connector and a user-customized trigger port connector (P/ N 20-600090-02). '
Figure 1-4 shows examples of positive and negative external trigger inputs that could be applied to the trigger connector. (Shown in untriggered state.)
1. Trigger sources other than the Microscan object detector can be used. Mechanical switches, relays, etc. - which tend to be slow and bouncy and produce multiple trigger signals - are not recommended unless equipped with optical sensors or filtered transitions (optical, Hall effect, or DC solid state relays).
1-4 MS-3000 Single Head Decoder User’s Manual
Page 13
Attach Cabling
+0 VDC to +24 VDC
1–Setup and Inst.
Positive Trigger
Negative Trigger
J2 1
Trigger input
2
Aux. relay driver
+0 VDC to +24 VDC
J2 1
Trigger input
2
Aux. relay driver
N.C.
N.O.
Solid state switching device
3
+5 VDC
3
+5 VDC
4
+12 VDC
4
+12 VDC
5
Ground
5
Ground
6
Not used
6
Not used
Solid state switching device
Decoder
Decoder
Figure 1-4 Trigger Connector Wiring Diagram (untriggered)
Scan Head Connector To prevent voltage loss, cables between decoder and scan head should not exceed 15 feet (4.57 m) unless wire sizes exceed the minimum 26 AWG. Figure 1-5 shows a MS-3000 decoder connected to a Microscan MS-500 scan head. M S -520 S can Head
MS-3000 Decoder
PW R TRIG
SC AN
IND2
IND1
Figure 1-5 Decoder to Scan Head
MS-3000 Single Head Decoder User’s Manual
1-5
Page 14
1–Setup and Inst.
Chapter 1
Setup and Installation
Back Panel Connectors On the rear panel (figure 1-6) there are the following four connectors: a. Power (5-pin DIN socket) b. LAN (modular RJ-11) c. Host (25-pin D-subminiature socket) d. Monitor (9-pin D-subminiature socket)
HOST
POWER
MONITOR
LAN
Figure 1-6 Rear Panel of MS-3000 Decoder
Power Connector The power connector (figure 1-7) has a 5-pin DIN socket with pin assignments shown in table 1-3. You may also supply the required DC voltages yourself. A mating connector (Switchcraft #05BL5M plug) is required. Caution: Switching power supplies for Microscan equipment with a switching noise of 20 mV or greater with ±12 VDC are not recommended due to excessive ripple characteristics. Table 1-3 Power Connector Pin Assignments
1
Pin
3 5
POWER
2
4
Figure 1-7 Power Connector Socket
1-6
Function
1
DC Ground
2
Chassis Ground
3
+5 VDC
4
–12 VDC
5
+12 VDC
MS-3000 Single Head Decoder User’s Manual
Page 15
Attach Cabling The Local Area Network (LAN) connector allows the MS-3000 decoder to communicate with a multidrop concentrator via a 4-wire cable (preferably shielded) with a 6-pin, 6-wire, RJ-11 type connector. Pin assignments are as shown in table 1-4. The LAN connector is used when a MS-3000 decoder is configured for RS-485 multidrop communications. 1
Table 1-4 LAN Connector Pin Assignments
6
Pin
Figure 1-8 LAN Connector
Function
1
Ground
2
Receive Data (+)
3
Receive Data (–)
4
Transmit Data (+)
5
Transmit Data (–)
For proper operation of RS-485 multidrop communications, the main cable should not exceed 4000 feet, with each drop no more than 10 feet. The Microscan MS-5000 multidrop concentrator can support up to 50 decoders or other multidrop devices on one RS-485 line. Note that the last device must be terminated correctly. RS-485 pinouts are also available at the host connector.
Host Connector The host connector (figure 1-9 on page 1-9), a 25-pin D-subminiature socket, allows the decoder to be connected to a host, a concentrator, or other communications device such as a PLC (programmable logic controller), a monitor, a PC, a relay, a diverter, an alarm, etc. Note: All Microscan products are configured as DTE at the host connector when in RS-232 operation. Caution: Do not use a host cable with more wires connected than are required for the application. The host connector of the decoder has many outputs that could cause damage or interfere with normal operation if connected and improperly used.
MS-3000 Single Head Decoder User’s Manual
1-7
1–Setup and Inst.
LAN Connector
Page 16
1–Setup and Inst.
Chapter 1
Setup and Installation Table 1-5 Host Connector Pin Assignmentsa
Pin
Function
1 2
Chassis ground Transmit data
3
Receive data
4
Request-to-send
5
Clear-to-send
6 7 8 9 10
TTL 5V signal Signal Ground TTL 5V signal +5 VDC Trigger input
11
Default (reset)
12 13 14 16 19
Aux Input RXD + TXD – RXD – TXD +
20
+12 VDC
21 22 23 24 25
Profile Card Input Signal Ground –12 VDC +12 VDC Match Code
Comment connected to dc ground +12v data output from the decoder ±12v signal indicating data from the host to the decoder ±12v signal asserted high by the decoder when it has data to send to the host ±12v signal asserted low by the host to stop the decoder from sending data to it (data transmission will resume when the signal is asserted high.) indicates a good read connected to chassis ground indicates a noread auxiliary supply +0 VDC to +24 VDC resets decoder to default configuration (future use) RS-422/485 RS-422/485 RS-422/485 RS-422/485 data terminal ready (asserted high on power-up to indicate decoder is on)
next label read as master label, if enabled a. The default communications mode does not support pin 4 (RTS). If RTS is not required by the host port, pin 4 should not be wired as the results will be unpredictable.
A good read will cause a 5V signal (high or low) to be output to pin 6. A noread will cause a 5V signal (high or low) to be output to pin 8. Caution: There must be ±12V present before the decoder will transmit data to the host. However, the decoder can receive commands without the presence of either voltage.
1-8
MS-3000 Single Head Decoder User’s Manual
Page 17
Attach Cabling 1–Setup and Inst.
DB-25 DTE to DB-25 DTE Connection
1
Decoder
HOST
Host
Transmit 2
2 Transmit
Receive
3 Receive
3
Signal Grnd 7
7 Signal Grnd
DB-25 DTE to DE-9 DCE Connection
25
Figure 1-9 Host Connector
Decoder
Host
Transmit 2
2 Receive
Receive 3
3 Transmit
Signal Grnd 7
5 Signal Grnd
Figure 1-10 DTE and DCE Host Connections
Monitor Connector The monitor connector (auxiliary terminal) connects the decoder to an auxiliary monitor via a 9-pin D-subminiature socket and cable. Table 1-6 shows auxiliary terminal pin assignments. Communication at this connector is RS-232 only. 1 MONITOR
9
Table 1-6 Monitor Connector Pin Assignments
Pin
Function
2
Receive Data (in)
3
Transmit Data (out)
5
Signal Ground
Figure 1-11 Monitor Connector
MS-3000 Single Head Decoder User’s Manual
1-9
Page 18
Chapter 1
Setup and Installation
1–Setup and Inst.
3 Configure Decoder
Settings for Communications, Operations, Code Types, and User Outputs and Raster Setup are stored in non-volatile memory and can be configured by menu, serial command, or profile card commands. For explanations of configuration settings, see Chapter 2, “ Menu Configuration.” To establish communications you will need to match the host’s or auxiliary terminal’s communication settings with your decoder’s settings (see Communications Menu” on page 2-5). Also make certain that the code type enabled in the decoder matches that of the label being used (see Code Types Menu” on page 2-22). Hint: Sending the <P> command will allow your scan head to read all of the listed code types.
Communicating with and ASCII Terminal The MS-3000 decoder communicates in full duplex, terminal mode with no handshake. It also recognizes carriage returns and line feeds. The host or ASCII terminal must match the following default settings before any communication can take place: 9600 Baud Rate, Seven Data Bits, Even Parity, and One Stop Bit. A PC or Macintosh computer can be used as a dumb terminal if connected as shown in table 1-5 on page 1-8 and running a communications program set to the above defaults. See your computer user’s manual for communication’s port pinouts.
4 Position Scan Head and Label
Before testing, you will need to position the scan head and label in a manner that matches as nearly as possible the actual conditions of your application. Consult your scan head user’s manual for important setup specifications.
1-10
MS-3000 Single Head Decoder User’s Manual
Page 19
Do Read Rate Test
This test calculates the percentage of scans decoded. It is useful during setup procedures to help optimize scan head-to-label orientation. a. Place the label used in your application in front of the scan head and within the desired read range. Note: Ensure that the label being scanned is of a code type enabled in the decoder’s software. Hint: Read rates are easier to read on the screen if Postamble is enabled. b. Select from the ESP Utilities menu or send a <C> command to the decoder to start testing (see the “Enter Read Rate Test” command on page 5-5). A percentage number from 0 to 100 will be displayed on the monitor in the read rate test indicating the ratio of good reads per total number of scans. c. Find the correct read rate area by moving the label in and out and right and left while observing read rate on the monitor.
Read Rate Percentage Label Data
Avoid the specular reflection area (see scan head user’s manual). d. Record the range area measurements and file the test results for future reference. If the results are not satisfactory, reposition or re-configure the decoder or choose a different narrow-bar-width label size. e. Select from the ESP Utilities menu or send a <J> command to the decoder when testing is complete (see the “Exit Read Rate Test” command on page 5-5).
MS-3000 Single Head Decoder User’s Manual
1-11
1–Setup and Inst.
5 Do Read Rate Test
Page 20
Chapter 1
Setup and Installation
1–Setup and Inst.
6 Install Decoder
The MS-3000 decoder can be mounted temporarily using the four rubber pads, or permanently, as follows: a. Position the decoder in a dry place. b. Before mounting, ensure that there is at least a 3 inch (76.2 mm) clearance at the rear and front of the decoder for the connectors and cables being used. c. Use the measurements provided in figure 1-12 to locate centers of mounting holes and drill four 5/32 inch or four 4 mm holes. d. Secure decoder with four 6-32 screws of the appropriate length. Caution: Make certain that mounting screws do not penetrate into the decoder case more than .175 in. (4.4 mm) or damage to the decoder could result. Measurements in inches (millimeters)
1.85" (46.99)
6.2" (157.48)
Fr ont
Optional foot pads (4 places)
2.5" (63.5)
6/32 threads (4 places)
0.5" (12.7)
5.6" (142.24)
Figure 1-12 Bottom Mounting Diagram (not full size)
1-12
MS-3000 Single Head Decoder User’s Manual