Page 35

Diagnostics and troubleshooting

7

Diagnostics and troubleshooting If problems occur during commissioning of the MA 21, you can refer to the following table. Typical errors and their possible causes are described here as well as tips for their elimination.

No.

Error description

Possible error causes

Measures

Error when switching on

No LED illuminates

• Incorrect polarity or improper connection of operating voltage

❏ Check connection, correct if

1

RDY LED flashes for longer than 30 s after start-up

• "Power-ON" function test could not be carried out successfully

❏ Check the network wiring;

2 necessary switch the operating voltage off and back on again

No communication between host and master:

4

5

With network operation, network master (Addr. "00") does not respond to the host

Master responds with "00S", the connected slaves do not respond

Master responds with "00S", all connected slaves respond with time-out (e.g. "01T, 02T, 03T etc.)

❏ Replace interface module

• Interface incorrectly connected

❏ Correct according to the con-

• Incompatible data format between host and MA 21

❏ Check the data format and nection diagram change in the master setup

• DIP switch 3 set to "Service"

❏ Set DIP switch 3 to "Host"

• Last slave address on the master MA 21 not set

❏ Use the rotary switch or master setup to set the last slave address

• DIP switch 4 set to "BCL"

❏ Set DIP switch 4 to "MA 21"

• Interruption or polarity reversal of the multiNet plus interface (RS 485)

❏ Test and correct the connec-

• The slaves have not recognised the "multiNet" protocol type and are using a different data format

❏ Test and correct settings for tion; wires A and B must not be interchanged the host protocol of the slaves at the service interface data format: multiNet mode baud rate: 57600 protocol: multiNet plus slave other errors on start-up

6

Leuze electronic

Master and slaves respond with "Addr.+S", but MA 21 with timeout (e.g. 03T)

• MA 21 is not connected correctly or is using an incorrect data format

❏ Test the connection of the

• MA 21 is set to "Service"

❏ Switch MA 21 to "Operation"

MA 21

MA 21, check host protocol (see above)

33

TNT 35/7-24V

3

• Incorrect interface type plugged in

Page 36

Diagnostics and troubleshooting

No.

Error description

Possible error causes

Measures

Errors during operation

7

DTR LED flashes but no data arrive at the host computer

• Incorrect protocol set at the host interface of the MA 21

❏ Set the protocol on the

• DIP switch 3 set to "Service"

❏ Set DIP switch 3 to "Host"

MA 21 to the values of the host computer

RDY and ERR LEDs flash synchronously

• The MA 21 is in setup mode; no reading tasks can be performed while in this mode

❏ End setup and save if neces-

8

RDY LED does not illuminate

• Operating software of the MA 21 does not function properly

❏ Perform a software RESET

9 sary; the MA 21 returns to operating mode

Notice! Please use page 34 and page 33 as a master copy should servicing be required. Mark the items in the "Measures" column which you have already examined, fill out the following address field and fax both pages together with your service contract to the fax number listed below.

Customer data (please complete) Leuze service fax number: +49 7021 573-199 Device type: Company: Contact person/ Department: Phone (direct): Fax: Street / No: ZIP code/City: Country:

34

MA 21

Leuze electronic

Page 37

Type overview and accessories

8

Type overview and accessories

8.1

Type overview of the MA 21 Type designation MA 21 100

500 03125

MA 21 100.2

500 30482

MA 21 110

500 30483 500 30484

MA 21 120 MA 21 130

Remark Protocol/interface converter - from RS 232 to RS 485/RS 485 multiNet Protocol/interface converter - from RS 232 to RS 485 multiNet with system connection Protocol/interface converter - from RS 232 to RS 232, electrically isolated Protocol/interface converter - from RS 232 to TTY Protocol/interface converter - from RS 232 to RS 422

TNT 35/7-24V

Part No. 500 30481

Leuze electronic

MA 21

35