The text of a manual · part 4 of 7
MA 21 connector unit as Leuze multiNet plus slave and as protocol converter: Technical Description, pages 20 to 28
Pages 20 to 28 of 44: 4 Mounting; 5 Connection
The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Leuze MA21
Page 20
Mounting
4
Mounting Notice! To mount the respective ident devices, please observe the notices in the corresponding operating instructions.
4.1
Mounting the MA 21 There are different types of mounting arrangements for the MA 21. • •
Using 4 threaded holes (M6) or using the provided M8 screws in the lateral fastening grooves in the mounting plate.
Figure 4.1: Fastening options for the MA 21
18
MA 21
Leuze electronic
Page 21
Mounting 4.2
Arrangement of devices Ideally, the MA 21 should be mounted so that it is easily accessible near the ident device in order to ensure good operability, e.g. for configuring the device connected. Slave 1 BCL 31
MA 2
Slave 2 RFM
MA 21 100.2
Host (PLC, process etc.)
RS 232 RS 422 RS 485 or TTY
Slave 3 BCL or VR
-Backup -Parameter
Network master
MA 31
Voltage supply multiNet plus
Leuze electronic
MA 21
TNT 35/7-24V
Figure 4.2: Example of arrangement of devices: Networking via multiNet plus
19
Page 22
Connection
5
Connection
5.1
Connecting the host interface Connection terminals: 1-6 Pin assignments of interface modules Attention! The pin assignments of the connection terminals are dependent on the interface module connected. The respective terminal designations are printed on the modules or affixed to the cover of the MA 21. The type designation of the MA 21 indicates which interface module is installed:
MA 21Interface types
20
Type designation/ Order code
Interface module of the host interface
MA 21 100
RS 485
MA 21 100.2
RS 485 multiNet plus with system connectors
For multiNet see chapter 5.2
MA 21 110
RS 232
MA 21 120
TTY
MA 21 130
RS 422
These versions use the MA 21 as an interface and protocol converter from RS 232 to the corresponding host interface (cf. following pages)
MA 21
Leuze electronic
Page 23
Connection 5.1.1
RS 232 interface (MA 21 110) The MA 21 110 functions as a protocol converter with two electrically isolated RS 232 interfaces (1 host, 1 client).
RS 232 Host interface module Shield
Host
RS232 1 2 3 4 5 6
RXD TXD CT S RT S GND
R XD TX D C TS R TS GN D
1
2 3 4 5 6 up to 10 m
Figure 5.1: Connection of the MA 21110 to an RS 232 host computer
Notice! The wiring for RTS and CTS must only be connected if RTS/CTS hardware handshake is used.
TTY interface (MA 21 120) TNT 35/7-24V
5.1.2
The MA 21 120 functions as an interface converter from RS 232 (client) to TTY (host).
TTY active a) MA 21 active/host passive: Host interface module Host
Shield
TX + TX RX + RX G ND
1 2 3 4 5 6 p as . TX a k t.
+20mA T x+ T xGND
TTY pa s. RX ak t.
1 2 3 4 5 6
+20mA R x+ R xGND
Ground (shield)
up to 1000 m
Jumper position active
Figure 5.2: Active connection of the MA 21120 to a TTY host computer Leuze electronic
MA 21
21
Page 24
Connection TTY passive b) MA 21 passive/host active: Host interface module Host
Jumper pa s . TX ak t.
Jumper
TTY TX+ 1 TX- 2 RX+ 3 RX- 4 5 GND 6 pas. RX ak t.
+20mA T x+ T xG ND
Shield 1 2 3 4 5 6
+20mA R x+ R xGND
Ground (shield)
up to 1000 m
Jumper position passive
Figure 5.3: Passive connection of the MA 21120 to a TTY host computer
Hints for connecting the TTY interface: • The active subscriber is the one which supplies the current (20 mA). • Switching between active/passive on the host interface card is carried out using two jumper pairs, independent for transmit (Tx) and for receive (Rx). • The jumpers for active/passive switching must always be changed in pairs (upper and lower jumpers in the same position). Thus the current source and GND are switched internally at the MA 21 host interface module. • Mixed operation is possible (transmit active/receive passive or vice versa). • When switching between active and passive operation or vice versa, the pin order of the connection cable is changed (pin assignment).
22
MA 21
Leuze electronic
Page 25
Connection 5.1.3
RS 422 interface (MA 21 130) With the MA 21 130 the client interface (RS 232) is converted to a 422 (host) interface. A protocol conversion is also possible.
RS 422 Host interface module Host
Shield R S 422
1 2 3 4 5 6
R x+ R xTx+ TxG ND
TX + 1 TX - 2 RX+ 3 RX- 4 5 GND 6 up to 1200 m
Figure 5.4: Connection of the MA 21130 to an RS 422 host computer
5.2
Connecting the multiNet plus interface Connection terminals: 1-6 RS 485
RS 485 interface (MA 21 100 and MA 21 100.2) TNT 35/7-24V
5.2.1
RS 485 Host interface module Host
Shield 485A
485B
485B
GND
GND
R S48 5 1 2 3 4 5 6
485A
485A 485A 485B 485B GND GND
1 2 3 4 5
6 up to 1200 m
Figure 5.5: Connection of the MA 21100 to an RS 485 host computer
Leuze electronic
MA 21
23
Page 26
Connection multiNet plus interface The multiNet plus interface establishes the connection between the subscriber. Note that the RS 485 interface module must be plugged in. The two-wire RS 485 with galvanic decoupling is passed through from slave to slave. Recommended network cable:
twisted pair cross section: min. 0.2 mm2 shielded copper resistance <100 Ω/km e.g. LiYCY 2 x 0.2 mm2 multiNet plus wiring Master MA 30/31
Connection with MA 30 only BCL 40 or BCL 80
485 A
GND
485 B multiNet plus interface
Terminal resistance 220 Ω
GND 485 B 485 A
GND GND 485 B 485 B 485 A 485 A
GND GND 485 B 485 B 485 A 485 A
GND GND 485 B 485 B 485 A 485 A
GND 485 B 485 A
GND GND 485 B 485 B 485 A 485 A
GND 485 B 485 A
RS 485
RS 485
RS 485
RS 485
MA 10
MA 2
MA 90
MA 21
BCL 40 or BCL 80
BCL 21 or BCL 31
BCL 90
HS or RS 232 device
Figure 5.6: multiNet plus wiring
24
MA 21
Leuze electronic
Page 27
Connection Hints for connecting the multiNet plus interface: • The RS 485 A, 485 B and GND lines are passed through in the network; for the MA 30, MA 21, MA 10 and MA 90 the corresponding terminals are doubly provided for this purpose. • Connect the shielding to the slaves with GND. • The maximum wire length in the network is 1200 m. • The (physically) last slave in the network should be fitted with a 220 Ω terminating resistor between 485 A and 485 B. This prevents reflections and improves resistance to interference. • 485 A and 485 B wires must in no case be exchanged within the network. The multiNet will otherwise not function.
5.3
Connecting the voltage supply Connection terminals: 17-21 (for all MA 21) Voltage supply
Input voltage:
18 … 36 V DC
Power consumption:
4 VA max., MA 21 without BCL
Terminal 17, 18:
V_IN
Terminal 19, 20:
GND_IN
(Reference potential, Ground)
Terminal 21:
PE
(protective conductor; earth)
TNT 35/7-24V
Connection terminals for the voltage supply of MA 21
(pos. operating voltage)
Notice! The terminals for V_IN and GND_IN are doubly supplied for ease of wiring. Thus the supply voltage can be passed through from one read station to the next.
Leuze electronic
MA 21
25
Page 28
Connection 5.4
Connecting an external device
5.4.1
Connecting the RS 232 client interface Connection terminals: 26-28 (not for MA 21 100.2) RS 232 Connection terminals for the RS 232 interface of an external device such as a hand-held scanner
5.4.2
Terminal 26:
RXD
Terminal 27:
TXD
Terminal 28:
GND
Connecting the voltage supply Connection terminals: 15, 16, 30, 31 (not for MA 21 100.2) Voltage supply Various voltages are available: 5.2 V and 24 V fixed. Terminals 15:
24 V
Terminals 16:
GND
Terminals 30:
5.2 V ± 5 %
Terminals 31:
GND
The 24 V client voltage supply is potential-free relative to the MA 21 voltage supply as well as the client interface.
26
MA 21
Leuze electronic