For the Leuze MA21

Page 20

Mounting

4

Mounting Notice! To mount the respective ident devices, please observe the notices in the corresponding operating instructions.

4.1

Mounting the MA 21 There are different types of mounting arrangements for the MA 21. • •

Using 4 threaded holes (M6) or using the provided M8 screws in the lateral fastening grooves in the mounting plate.

Figure 4.1: Fastening options for the MA 21

18

MA 21

Leuze electronic

Page 21

Mounting 4.2

Arrangement of devices Ideally, the MA 21 should be mounted so that it is easily accessible near the ident device in order to ensure good operability, e.g. for configuring the device connected. Slave 1 BCL 31

MA 2

Slave 2 RFM

MA 21 100.2

Host (PLC, process etc.)

RS 232 RS 422 RS 485 or TTY

Slave 3 BCL or VR

-Backup -Parameter

Network master

MA 31

Voltage supply multiNet plus

Leuze electronic

MA 21

TNT 35/7-24V

Figure 4.2: Example of arrangement of devices: Networking via multiNet plus

19

Page 22

Connection

5

Connection

5.1

Connecting the host interface Connection terminals: 1-6 Pin assignments of interface modules Attention! The pin assignments of the connection terminals are dependent on the interface module connected. The respective terminal designations are printed on the modules or affixed to the cover of the MA 21. The type designation of the MA 21 indicates which interface module is installed:

MA 21Interface types

20

Type designation/ Order code

Interface module of the host interface

MA 21 100

RS 485

MA 21 100.2

RS 485 multiNet plus with system connectors

For multiNet see chapter 5.2

MA 21 110

RS 232

MA 21 120

TTY

MA 21 130

RS 422

These versions use the MA 21 as an interface and protocol converter from RS 232 to the corresponding host interface (cf. following pages)

MA 21

Leuze electronic

Page 23

Connection 5.1.1

RS 232 interface (MA 21 110) The MA 21 110 functions as a protocol converter with two electrically isolated RS 232 interfaces (1 host, 1 client).

RS 232 Host interface module Shield

Host

RS232 1 2 3 4 5 6

RXD TXD CT S RT S GND

R XD TX D C TS R TS GN D

1

2 3 4 5 6 up to 10 m

Figure 5.1: Connection of the MA 21110 to an RS 232 host computer

Notice! The wiring for RTS and CTS must only be connected if RTS/CTS hardware handshake is used.

TTY interface (MA 21 120) TNT 35/7-24V

5.1.2

The MA 21 120 functions as an interface converter from RS 232 (client) to TTY (host).

TTY active a) MA 21 active/host passive: Host interface module Host

Shield

TX + TX RX + RX G ND

1 2 3 4 5 6 p as . TX a k t.

+20mA T x+ T xGND

TTY pa s. RX ak t.

1 2 3 4 5 6

+20mA R x+ R xGND

Ground (shield)

up to 1000 m

Jumper position active

Figure 5.2: Active connection of the MA 21120 to a TTY host computer Leuze electronic

MA 21

21

Page 24

Connection TTY passive b) MA 21 passive/host active: Host interface module Host

Jumper pa s . TX ak t.

Jumper

TTY TX+ 1 TX- 2 RX+ 3 RX- 4 5 GND 6 pas. RX ak t.

+20mA T x+ T xG ND

Shield 1 2 3 4 5 6

+20mA R x+ R xGND

Ground (shield)

up to 1000 m

Jumper position passive

Figure 5.3: Passive connection of the MA 21120 to a TTY host computer

Hints for connecting the TTY interface: • The active subscriber is the one which supplies the current (20 mA). • Switching between active/passive on the host interface card is carried out using two jumper pairs, independent for transmit (Tx) and for receive (Rx). • The jumpers for active/passive switching must always be changed in pairs (upper and lower jumpers in the same position). Thus the current source and GND are switched internally at the MA 21 host interface module. • Mixed operation is possible (transmit active/receive passive or vice versa). • When switching between active and passive operation or vice versa, the pin order of the connection cable is changed (pin assignment).

22

MA 21

Leuze electronic

Page 25

Connection 5.1.3

RS 422 interface (MA 21 130) With the MA 21 130 the client interface (RS 232) is converted to a 422 (host) interface. A protocol conversion is also possible.

RS 422 Host interface module Host

Shield R S 422

1 2 3 4 5 6

R x+ R xTx+ TxG ND

TX + 1 TX - 2 RX+ 3 RX- 4 5 GND 6 up to 1200 m

Figure 5.4: Connection of the MA 21130 to an RS 422 host computer

5.2

Connecting the multiNet plus interface Connection terminals: 1-6 RS 485

RS 485 interface (MA 21 100 and MA 21 100.2) TNT 35/7-24V

5.2.1

RS 485 Host interface module Host

Shield 485A

485B

485B

GND

GND

R S48 5 1 2 3 4 5 6

485A

485A 485A 485B 485B GND GND

1 2 3 4 5

6 up to 1200 m

Figure 5.5: Connection of the MA 21100 to an RS 485 host computer

Leuze electronic

MA 21

23

Page 26

Connection multiNet plus interface The multiNet plus interface establishes the connection between the subscriber. Note that the RS 485 interface module must be plugged in. The two-wire RS 485 with galvanic decoupling is passed through from slave to slave. Recommended network cable:

twisted pair cross section: min. 0.2 mm2 shielded copper resistance <100 Ω/km e.g. LiYCY 2 x 0.2 mm2 multiNet plus wiring Master MA 30/31

Connection with MA 30 only BCL 40 or BCL 80

485 A

GND

485 B multiNet plus interface

Terminal resistance 220 Ω

GND 485 B 485 A

GND GND 485 B 485 B 485 A 485 A

GND GND 485 B 485 B 485 A 485 A

GND GND 485 B 485 B 485 A 485 A

GND 485 B 485 A

GND GND 485 B 485 B 485 A 485 A

GND 485 B 485 A

RS 485

RS 485

RS 485

RS 485

MA 10

MA 2

MA 90

MA 21

BCL 40 or BCL 80

BCL 21 or BCL 31

BCL 90

HS or RS 232 device

Figure 5.6: multiNet plus wiring

24

MA 21

Leuze electronic

Page 27

Connection Hints for connecting the multiNet plus interface: • The RS 485 A, 485 B and GND lines are passed through in the network; for the MA 30, MA 21, MA 10 and MA 90 the corresponding terminals are doubly provided for this purpose. • Connect the shielding to the slaves with GND. • The maximum wire length in the network is 1200 m. • The (physically) last slave in the network should be fitted with a 220 Ω terminating resistor between 485 A and 485 B. This prevents reflections and improves resistance to interference. • 485 A and 485 B wires must in no case be exchanged within the network. The multiNet will otherwise not function.

5.3

Connecting the voltage supply Connection terminals: 17-21 (for all MA 21) Voltage supply

Input voltage:

18 … 36 V DC

Power consumption:

4 VA max., MA 21 without BCL

Terminal 17, 18:

V_IN

Terminal 19, 20:

GND_IN

(Reference potential, Ground)

Terminal 21:

PE

(protective conductor; earth)

TNT 35/7-24V

Connection terminals for the voltage supply of MA 21

(pos. operating voltage)

Notice! The terminals for V_IN and GND_IN are doubly supplied for ease of wiring. Thus the supply voltage can be passed through from one read station to the next.

Leuze electronic

MA 21

25

Page 28

Connection 5.4

Connecting an external device

5.4.1

Connecting the RS 232 client interface Connection terminals: 26-28 (not for MA 21 100.2) RS 232 Connection terminals for the RS 232 interface of an external device such as a hand-held scanner

5.4.2

Terminal 26:

RXD

Terminal 27:

TXD

Terminal 28:

GND

Connecting the voltage supply Connection terminals: 15, 16, 30, 31 (not for MA 21 100.2) Voltage supply Various voltages are available: 5.2 V and 24 V fixed. Terminals 15:

24 V

Terminals 16:

GND

Terminals 30:

5.2 V ± 5 %

Terminals 31:

GND

The 24 V client voltage supply is potential-free relative to the MA 21 voltage supply as well as the client interface.

26

MA 21