Spec sheet · Leuze
Leuze BCL-45 Spec Sheet
Spec sheet4 pagesPDF 375 KB
All 4 pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Leuze electronic technical description for the BCL 45 bar code scanner for DeviceNet and its MA 15 connector unit. It gives features, specifications, the connector unit's switches and terminals, the LED status meanings, network addressing and the order list of scanner versions.
- Type
- High-speed bar code scanner with integrated CAN bus interface, run on the Device-Net protocol p. 2
- Operating voltage
- 11 ... 30 V DC p. 1, 2
- Scanning rate
- 1200 scans/s, with automatic code type detection p. 1
- Codes read
- All standard bar codes, e.g. 2/5 Interleave and Code 39 p. 2
- Service interface
- RS 232 on a 9-pole SubD plug (2=RxD, 3=TxD, 5=GND), for setup and data monitoring p. 1, 3
- Housing
- Diecast aluminum, IP 65 p. 2
- Baud rate
- Set by rotary switch: 0 = 125 kb, 1 = 250 kb, 2 = 500 kb; above 2, set by software p. 3
- Node address
- Two rotary switches: tens 0 to 6, units 0 to 9; addresses above 63 set by software p. 4
- Network size
- 15 to 63 bar code readers can be linked in one Device-Net network p. 2
- Sensor input
- 12 ... 36 V DC/AC on terminals 7, 9, 11 and 12, to trigger the scanner p. 3
- Switching output
- 5 ... 48 V DC on terminals 13 to 16, e.g. for good read or bad read p. 3
- Versions
- Raster scanners with F, N or M optics; single-beam scanners with F or M optics p. 4
- Connector unit
- MA 15 150, connector unit for the Device-Net slave BCL 45 p. 4
- Environment
- Storage -20°C ... +60°C; max. 90% relative humidity, non-condensing p. 2
What this sheet walks you through
- Outline dimensions of the BCL 45 with the MA 15 p. 1
- Device-Net messages used to exchange data with the PLC master p. 2
- MA 15 switches, plugs and terminals p. 3
- Switching to service mode with DIP switch 3 p. 3
- Setting the baud rate and Device-Net address p. 3, 4
- Reading the LED status indicators p. 4
- Ordering scanner versions and the connector unit p. 4
Good to know
- Addresses above 63 are set by software rather than the rotary switches. p. 4
- A flashing red MNS LED means the message connection timed out; it clears when the connection is reestablished. p. 4
Questions this sheet answers
What does a steady red MNS LED mean on the Leuze BCL 45?
A serious error such as a buffer overflow; switch the unit off and on or reset the BCL 45. p. 4
How do I set the Device-Net address of a BCL 45?
Use the two rotary switches in the MA 15: the MSD switch sets the tens digit and the LSD switch the units; for address 32 set 3 and 2. p. 4
What baud rates does the BCL 45 support on Device-Net?
125 kb, 250 kb or 500 kb, chosen with the rotary switch (positions 0, 1, 2); higher positions leave it to software. p. 3
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
Leuze electronic Dimensioned drawing
BCL 45 / MA 15
Bar Code Scanner for Device-Net with Connector Unit 11 - 30 V DC
AODVAFeatures
We reserve the right to make changes
l Scanning rate 1200 scans/s l Automatic code type detection Automatic code quality check l Additional RS232 service interface l Scanner parameterization via Device-Net or service interface l MAC ID and baud rate set via rotary code switch l Device status visualization l Parameters are stored fail-safe in an EEPROM l Switching inputs and outputs l Simple mounting and fastening l Code and reference code are not equal
BCISO 9001IP 65IEC 801...
Leuze electronic GmbH + Co.
A B C
15-pole plug LED indicator 15-pole plug
Postbox 1111 D-73277 Owen-Teck Tel. ++49 7021 5730
–1–
BCL 45 MA 15
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
Leuze electronic Specifications
Tables BCL 45
MA 15
Bar code scanner for operation with Device-Net
Connector unit and parameter memory for BCL 45
11 ... 30 V DC 5 VA 12 ... 30 V DC Imax = 100 mA
11 ... 30 V DC 2 VA 12 ... 30 V DC Imax = 100 mA
Diecast aluminum 120 x 90 x 43 mm 0.418 kg
Diecast aluminum 130 x 90 x 78 mm 0.584 kg
Electrical data Operating voltage UB Power consumption Switching input Switching output
Mechanical data Housing Dimensions (WxHxD) Weight
Environmental data Operating temperature Storage temperature Protection class Electromagnetic compatibility Air moisture
0°C ... +40°C 0°C ... +50°C -20°C ... +60°C -20°C ... +60°C IP 65 IP 65 According to IEC 801 According to IEC 801 Max. 90% rel. humidity, non-condensing
Remarks
Description The BCL 45 bar code reader is a high-speed scanner with integrated CAN-data-bus interface and is operated with the Device-Net protocol. The integrated decoder can quickly and reliably read all standard bar codes, e.g. 2/5-Interleave, Code 39 etc. In combination with the MA 15 connector unit, a simple electrical connection can be established to the CAN bus as per the Device-Net specifications. According to these specifications, it is possible by means of line loops to connect 15 to 63 bar code readers to one another in the network. The CAN system is equivalent to a master-slave system in which the master, which is in the form of a PLC, manages the data transfer. The data are exchanged by means of various messages; which message is used is dependent on the type of situation. The used messages are: I/O-Poll Command Response / Request I/O-Change of State / Cyclic Message Explicit Response / Request Message The data structures transmitted with the messages can be assembled on demand by using predefined assembly instances.
BCL 45 MA 150010–2–
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
Leuze electronic Control elements Element
Function
Device-Net plug Terminals 1 to 5
- PIN 1 and 5: PIN 2 and 4: PIN 3
- voltage supply CAN-bus data lines shielding
Plug for BCL 45 Ribbon cable connection
Connects the SubD plug in the housing cover to the electronics in the MA 15 base
Service switch DIP switch 3
ON: Service mode OFF: Standard operation
Service plug 9-pole SubD plug
RS 232 interface for service/setup operation, monitoring of data in standard operation 2=RxD, 3=TxD, 5=GND
Sensor input Terminals 7, 9, 11 and 12
Input voltage 12 ... 36 V DC/AC for activation of the BCL 45
Switching output Terminals 13 to 16
Output voltage 5 ... 48 V DC for the display of e.g. "good read" or "bad read"
Data rate (1 rotary code switch)
Baud rate setting: switch position
0 = 125 kb 1 = 250 kb 2 = 500 kb >2 = baud rate can be set via software
Node address (2 rotary code switches)
Subscriber address settings (for settings, see chapter Addressing)
Reset Reset button
- press < 4s
- press > 4s
'warm-star' 'cold-start'
- ON: OFF
- on reset ('cold-start') the factory default parameter set is loaded. on reset ('cold-start') a customer-specific parameter set is loaded.
ParaDefault DIP switch 2
reserved DIP switch 4
not assigned in standard version
Electrical connection
We reserve the right to make changes
ACBDE
A Baud rate selector switch B Ribbon cable connection to the BCL C Addressing switch, tens D Addressing switch, single digits E CAN-interface connection plug
Leuze electronic GmbH + Co.
Postbox 1111 D-73277 Owen-Teck Tel. ++49 7021 5730
–3–
BCL 45 MA 15
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
Leuze electronic Indicators LED
ColorSignificanceMNSgreen / red
Device-Net status indicator
I/Ogreen / redScanner activeACTred
Scanner active (ACTive)
DEC
gr0010een
Decoding successful (DECoding)
Status conditions of the LEDs MNS green flashing
Device is ready, no message connection is established
MNS Device is ready, message connection is continuous light, green established MNS red flashing
Time-out of the message connection (corrected by reestablishing the message connection)
MNS continuous light, red
Serious error, e.g. a buffer overflow (corrected by switching on and off or by resetting the BCL 45)
ACT continuous light, red
Scanner is active - laser in operation
ACT flashes
During the ’autoControl’ function, a warning is output
DEC Approx. 1/2 second after successful continuous light, green completion of a decoding process.
Addressing Device-Net has the capability to link 63 subscribers to one another. These addresses are set in the MA 15 using rotary code switches. MSD rotary code switch: LSD rotary code switch:
For setting the tens digits of the subscriber address Possible values: 0 ... 6 For setting the single digits of the subscriber address Possible values: 0 ... 9
- Example for subscriber 32
- Set MSD rotary code switch to 3 Set LSD rotary code switch to 2
Address > 63
Address can be set via software (software selection)
Order guide Part designation
Description
Part No.
MA 15 150 BCL 45 R1 F 100 BCL 45 R1 N 100 BCL 45 SF 100 BCL 45 SM 100 BCL 45 R1 M 100
Connector unit for Device-Net slave BCL 45 Raster scanner with F optics Raster scanner with N optics Single-beam scanner with F optics Single-beam scanner with M optics Raster scanner with M optics
500 32909 500 32908 500 33621 500 35385 500 34493 500 34492
Additional scanner types on request
BCL 45 MA 150010–4–