Page 31
Chapter 2
Installation Procedure
2.4.4 Terminals of I/O terminal block and wiring TIM
Trigger input
+12V OUT– COM
OK
NG
SDA
SDB
Power supply OK/NG output for sensors (12 VDC, 300 mA)
SG
RDA
RDB
RS-422A/RS-485
Symbol
Description
Signal direction
TIM
Trigger input
Input
+12 V OUT
+ terminal of power supply for sensor (12 VDC, 300 mA) Output – terminal of power supply for sensor (0 V)
Output
COM
Common terminal for OK/NG output, OK
OK output
Output
NG
NG output
Output
SDA
+ terminal for RS-422A data transmission/ RS-485 + terminal
Output, Input/Output
SDB
– terminal for RS-422A data transmission/ RS-485 - terminal
Output, Input/Output
SG
Signal ground, RDA
+ terminal for RS-422A data reception
Input
RDB
– terminal for RS-422A data reception
Input
Input
* Viewed from the left of the terminal block • M3.0 screws are used for the terminal block. • Use the following crimp terminals for connections. Round-shape 6.0 mm or less
Fork-shape 6.0 mm or less
Connecting trigger input The trigger input allows the BL series to start reading bar codes (turn on the laser beam). The trigger input is turned ON when 8.5 to 30 VDC input is activated between the trigger input terminals. The BL-U1 power supply for the sensor can be used as the input power supply. TIM
+12V OUT–
Contact or solid-state
+ + 8.5~30VDC
23
2
Page 32
Chapter 2
Installation Procedure
Connecting OK/NG output The OK/NG output is used to differentiate between acceptable and unacceptable results based on the comparison with the preset data, and to indicate whether or not the BL series successfully read bar codes. The OK/NG output is an open-collector output.
COM
OK
NG *Rated load: 30 V max. (100 mA)
2
Load Load
+
I/O circuit diagram
3.3KΩ
TIM
2.4 KΩ
Internal circuit
Input circuit diagram
Internal circuit
Output circuit diagram
OK/NG
COM
24
Load
+
Page 33
Chapter 2
Installation Procedure
2.4.5 Connecting RS-485 For the RS-485 connections, use the “SDA” and “SDB” terminals provided on the terminal block.
*
* N-400
BL-U1
BL-U1
BL-U1
SDA
SDA
SDA
RS-485 +
SDB
SDB
SDB
RS-485 –
SG
SG
SG
RS-485 SG
2
Recommended RS-485 cable • 0.75 mm2 x 2 cores, shielded
•
Up to thirty-one BL-U1 (BL series) units can be connected in multi-drop link mode.
•
The total extension length of the RS-485 cable must be within 1.2 km.
•
Turn ON the equipment terminator (termination resistance: 100 Ω) at both ends of the RS-485 connection (marked with * in the above diagram).
•
Turn ON/OFF the BL-U1 terminator using the terminator switch. (See p. 22.)
•
Turn ON/OFF the N-400 terminator using the terminator switch. (See p. 6.)
Note: Be sure not to connect the RS-485 cable using the terminal block.
Incorrect
Correct
BL-U1
BL-U1
Note 1: Do not place the RS-485 cable in the same conduit as a power cable. Note 2: Do not branch the RS-485 connection as shown below. Incorrect (Connection with branch)
BL-U1
BL-U1
Correct (Connection without branch)
N-400
BL-U1
BL-U1
N-400
*
* BL-U1
BL-U1 * Terminator ON
25
Page 34
Chapter 2
2.5
Installation Procedure
Using Connection Test Mode This section describes the procedure for performing a connection test after the N400 and the BL series (N-48 or BL-U1) are connected with the RS-485 cable. Note: To use the connection test mode, ensure that the settings of the connected BL series and those of the N-400 are switched to “multidrop link” mode. 1) When you press and hold the N-400 test switch for approximately 2 seconds after the power to all devices is turned ON, the connection test mode is activated. The N-400 displays the ID number of the device being tested. If the devices are properly connected, the ID number is automatically incremented.
2
2) If any device is not connected or is improperly connected, the ID number corresponding to the device flashes. To go to the next step during the connection test, press the test switch once.
Example 1 When ten BL series (ID Nos. 1 to 10) are connected: The displayed ID number automatically changes from “1” to “10”, and then “11” will flash if the connection test result is “OK”. Example 2 When fourteen BL series (ID Nos. 3 to 16) are connected: When “1” flashes, press the test switch once. When “2” flashes, press the test switch again. The displayed number changes from “3” to “16”, and then “17” will flash if the connection test result is “OK”. 3) If an ID number of any BL series flashes, the BL series unit is not properly connected. After checking the following points, perform the connection test again. •
Check that the RS-485 communication parameters (baud rate, data length, parity and stop bit length) of the N-400 match to those of the BL series.
•
Check that the BL series is set to “multi-drop link” mode.
•
Check that all cables are properly connected. Ensure that the connections are not branched and that no cables are connected using the terminal block. (➮ See pp. 19, 20 and 25.)
•
Check that the equipment terminators at both ends of the connection are ON and the terminators of other equipment are OFF.
•
Check that the BL series’ ID numbers are properly assigned. Make sure that the same ID number is not assigned to different devices.
4) Pressing and holding the test switch for approximately 2 seconds again resets the connection test mode.
26
Page 35
Chapter 2
2.6
Installation Procedure
Mounting Procedure
2.6.1 Operating environment precautions CAUTION
This unit is a precision instrument and you must take care in choosing the operating environment. ■ Ambient environments Do not install the unit in place as shown below
2
•
The unit is exposed to direct sunlight, or the ambient temperature may fall below 0°C (32°F) or exceed 50°C (122°F);
•
The relative humidity may exceed the range of 35 to 85%, or condensation may occur due to rapid temperature changes;
•
Corrosive gas or inflammable gas is present, or a high level of dust, salt, iron particles or soot is present;
•
The unit is subject to vibration or impact;
•
Water, oil or chemicals may splash the unit;
•
A strong magnetic field or electric field is generated.
•
Do not place the cables in the same conduit as a power cable.
■ In-panel installation To mount the N-400 in a panel, carefully observe the following instructions. •
Provide enough ventilation space.
•
If the ambient temperature may fall below 0°C (32°F) or exceed 50°C (122°F), provide a fan or air conditioner.
•
Do not mount this unit in a panel where a high voltage device is installed.
•
Place this unit as far away from power lines as possible.
27
Page 36
Chapter 2
Installation Procedure
2.6.2 Mounting N-400 To mount the N-400, you can use one of the following two methods:
Direct mounting Pull the brackets provided at four positions on the rear of the N-400, and fix them with screws.
N-400
2
TEST
RS-232C
SD
100
CS
RD
RS RD
SD
POWER TIMING
RS-455
TERMINATOR ON OFF
4 x ø5 mounting hole
40
DIN-rail mounting To mount the N-400 on a DIN-rail, press the unit against the DIN rail until it clicks. To remove the unit, pull the hook in the direction indicated by arrow.
N-400 TEST
RS-232C
SD
RD
POWER TIMING
CS SD
RS RD RS-455
TERMINATOR ON OFF
2.6.3 Mounting N-48 To mount the N-48, use the mounting hole.
4 x ø5 mounting hole
POWER
43.2
5.9 5.9
28
63.2 75
SD
RD
Page 37
Chapter 2
Installation Procedure
2.6.4 Mounting BL-U1 To mount the BL-U1, you can use one of the following two methods:
Positions of direct mounting Pull the brackets provided at four positions on the rear of the BL-U1, and fix them with screws.
4 x ø5
2
98
150
DIN-rail mounting 1. Hook the BL-U1 in the groove of the DIN rail from the top, and press the bottom of the BL-U1 against the DIN rail until it clicks. 2. Make sure that the DIN-rail mounting hook is set in condition “A”. If it is not, push it inward. 3. To remove the BL-U1 from the DIN rail, pull the hook so that it is set in condition “B”. 4. To mount the unit on the DIN rail again, restore the hook to condition “A”.
A
B
29
Page 38
Chapter 2 __ Installation Procedure ee
30
Page 39
Chapter 3 N-400 Setup Procedure 3.1
Installing Setup Software ................................................... 32
3.2
Setup Software Operating Procedure ............................... 34
3.2.1 Operating procedure .............................................................. 34 3.2.2 Description on each setup screen ......................................... 35 3.2.3 Outline of operation ............................................................... 36 3.3
Details of Operating Procedure ........................................ 38
3.3.1 Setting procedure .................................................................. 38 3.3.2 Reading/Saving/Printing File ................................................. 44 3.4
Sending/Receiving Settings .............................................. 48
3.5
Using Terminal .................................................................... 52
3.6
List of Error Messages ....................................................... 55
Page 40
Chapter 3
3.1
N-400 Setup Procedure
Installing Setup Software The N-400 includes the setup software for the Windows version only. The operating environments and the procedure for installing this setup software are described below. ■ Hardware requirments • IBM PC/AT 100% compatible CPU: 80386 or higher Memory: 4 MB or more Floppy disk drive: 3.5 inch floppy disk drive (1.44 Mb compatible) Serial port: A minimum of one RS-232C port is required. ■ OS requirements • MS-Windows 3.1 or MS-Windows 95
3 Installation procedure
1. Insert the N-400 setup software system disk into the floppy drive. 2. Perform the following procedure. •
Windows 3.1: Execute “Run” in the icon menu of the program manager.
•
Windows 95: Select “Run” from the "Start" menu. 3. Run the “SETUP” file from the floppy disk drive. (This step is common to both the Windows 3.1 and Windows 95.) Type in as follows: A: \SETUP
32