Page 11

Chapter 1

Overview of The N-400

■ Mutual-interference suppression function (in multi-head scan mode) When several bar code readers are mounted close to each other, for example when reading multi-stage labels as shown below, the units’ light sources (laser beams) interfere with each other, affecting the reading stability. The mutual-interference suppression function allows the BL series’ laser beams to turn ON sequentially, thus suppressing the mutual interference to ensure stable readings. Since the laser beams turn ON sequentially, the duration of laser OFF time (when each unit is not reading a bar code) becomes longer as the number of connected units is increased. Therefore, the bar code readers may fail to read bar codes if the line speed is set too fast.

BL series N-400 N-48 or BL-U1

RS-232C

Sensor for trigger input

Host RS-485

■ PLC link function In the multi-drop link mode or multi-head scan mode, the PLC link function enables the BL series’ data to be sent to a PLC without a communication program. Using this function, you can reduce the number of steps for a PLC program.

No communication program is necessary, because the N-400 stores the data read by the BL series directly into the PLCs memory.

N-400 To BL

DM103 DM104 DM105 DM106

4 &30 &31 &32

• • •

• • •

3

1

Page 12

Chapter 1

1.2

Overview of The N-400

System Configuration The system configurations using the N-400 controller are as follows: This section describes multi-drop link mode and multi-head scan mode individually.

1

Multi-drop link mode • •

Maximum number of connectable units: 31 Maximum extension distance: 1.2 km Sensor for trigger input

N-400 setup software for Windows

BL series

N-400 RS-232C N-48 or BL-U1

* *

*

* RS-485

Host

The N-400 can be connected to the BL-700/BL-500/BL-180 series bar code readers. Additional 24 VDC power supply is required for the N-400 and N-48.

Multi-head scan mode (with the interference suppression function) • •

Maximum number of connectable units: 31 Maximum extension distance: 1.2 km N-400 setup software for Windows Sensor for trigger input

N-400 RS-232C

N-48 or BL-U1

*

Host

RS-485

* * *

4

Connect the sensor for trigger input to the N-400. The N-400 can be connected to the BL-700/BL-500/BL-180 series bar code readers. Additional 24 VDC power supply is required for the N-400 and N-48.

Page 13

Chapter 1

1.3

Overview of The N-400

Part Names

N-400

1

N-400

1 Display LEDs TEST

2 RS-232C port RS-232C

3 Communication status indicator LEDs

SD

RD

POWER TIMING

CS SD

RS

7 RS-485 terminal

RD RS-455

4 Test switch

6 Power supply terminal

8 Trigger input terminal

TERMINATOR ON OFF

5 Terminator switch

ON OFF

No. Name 1

Display LEDs

Function • Normally displays “00” (ID number of the N400). • Displays the ID number of the device being tested. (➮ See p. 26.) • Displays “S1 (51)” to indicate setup mode. (➮ See p. 75.) • Displays “S0 (50)” to indicate initial communication status after a setting change. (➮ See p. 48.) • Displays the N-400’s error condition. (➮ See 131.) • Displays the ID number of the device currently connected when sending a hotline command. (➮ See p. 73.)

2

RS-232C port

• Connect a host computer or PLC to this connector.

3

Communication status indicator LEDs

• POWER: Lit when power is ON. • TIMING: Lit when the trigger input connected to the N-400 is ON. (For the RS-232C connections) Lit when the SD, RD, RS and CS signals are ON. (For the RS-485 connections) SD: Lit when the N-400 is sending data. RD: Lit when the N-400 is receiving data. * Both the SD and RD indicators are lit when the N-400 is receiving data.

4

Test switch

Starts the connection test mode.

5

Terminator switch

Switches the terminator’s ON/OFF status.

6

Power supply terminal Connect a 24 VDC power supply.

7

RS-485 terminal

Used for the multi-drop link connection.

8

Trigger input terminal

Used for trigger input in multi-head scan mode.

5

Page 14

Chapter 1

Overview of The N-400

N-48 Note: BL-U1 is not available in the Europe area. 1 READER port

1 READER

2 POWER LED POWER

SD

RD

6 Communication status indicator LEDs 7 Terminator switch

3 I/O terminals

ON OFF

4 RS-485 terminals 5 Power supply terminals

No. Name

Function

1

READER port

Connect the BL series to this port.

2

POWER LED

Lit when power is ON.

3

I/O terminals

Includes the trigger input terminal and OK/NG output terminals.

4

RS-485 terminals Power supply terminals

Used for multi-drop link mode.

Communication status indicator LEDs

Allows you to monitor the communication status of the READER port.

5 6

Connect a 24 VDC power supply to these terminals.

SD: Lit when the BL series is sending data. RD: Lit when the BL series is receiving a command. 7

6

Terminator switch

Turns the terminator ON/OFF.

Page 15

Chapter 1

Overview of The N-400

BL-U1 Note:

The BL-U1 is not available in Europe 1 OK/NG LED 2 TIMING LED

1

3 Communication status indicator LEDs 4 POWER LED 5 I/O terminal block

6 Power switch 7 Power supply cable (2 m)

8 RS-232C port 9 READER port 0 DIP switches

No. Name 1

OK/NG LED

Function • When OK output is ON: The green LED lights. • When NG output is ON: The red LED lights.

2

TIMING LED

3

Communication status • Allows you to monitor the communication status of the RS232C port. indicator LEDs • The SD, RD, RS and CS indicators are provided in this order from the top.

4

POWER LED

Lit when power is ON.

5

I/O terminal block

Includes the trigger input terminal, OK/NG output terminals, RS-422A terminal and RS-485 terminal.

6 7

Power switch Power supply cable (2 m)

8

RS-232C port

Connect a personal computer to this port. This port is unused in multi-drop link mode.

9

READER port

Connect the BL series to this port.

0

DIP switche

Switches the communication port, and turns the terminator ON/OFF.

Lit when trigger input is ON.

Turns the power ON/OFF. Use a 100 to 240 VAC (50/60 Hz) power supply.

7

Page 16

Chapter 1

1

8

Overview of The N-400

Page 17

Chapter 2 Installation Procedure 2.1

Installing the N-400 ............................................................. 10

2.2

Connecting N-400 and Wiring ............................................ 12

2.2.1 Terminals of I/O terminal block and wiring ............................. 12 2.2.2 Connecting RS-232C ............................................................. 13 2.3

Connecting N-48 and Wiring .............................................. 16

2.3.1 Connecting the BL series ....................................................... 16 2.3.2 Terminals of I/O terminal block and connection ..................... 16 2.3.3 Connecting RS-485 ............................................................... 19 2.4

Connecting BL-U1 and Wiring ........................................... 21

2.4.1 2.4.2 2.4.3 2.4.4 2.4.5

Connecting power supply ...................................................... 21 Connecting BL series ............................................................. 21 Setting BL-U1 DIP switches ................................................... 22 Terminals of I/O terminal block and wiring ............................. 23 Connecting RS-485 ............................................................... 25

2.5

Using Connection Test Mode ............................................ 26

2.6

Mounting Procedure ........................................................... 27

2.6.1 2.6.2 2.6.3 2.6.4

Precautions for mounting environment .................................. 27 Mounting N-400 ..................................................................... 28 Mounting N-48 ....................................................................... 28 Mounting BL-U1 ..................................................................... 29

Page 18

Chapter 2

2.1

Installation Procedure

Installing the N-400 ■ Equipment used • N-400 multi-drop controller

2

•

BL series bar code readers The N-400 can be connected to the BL-700, BL-500 and BL-180 series bar code readers.

•

N-48 (or BL-U1) power supply unit for BL series (RS-485 mode) Each bar code reader requires one N-48 (or BL-U1) power supply.

•

BL-U2 (or BL-U1) power supply unit for BL series (RS-232C mode) To change the BL series’ settings, one BL-U2 or BL-U1 power supply unit is required. To use the N-48 for multi-drop link, an additional BL-U2 24 VDC power supply unit is required. (The N-48 does not provide an RS-232C port.) (The BL-U1 can be used as an RS-232C or RS-485 power supply.)

•

RS-232C cable for the N-400 This cable is used to connect the N-400 and the host computer. Use a cable appropriate for the personal computer and the PLC’s pin assignment. OP-98769 cable and OP-25057 connector are available.

•

RS-232C cable for BL series setup This cable is used to connect the BL-U2 (or BL-U1) and the host computer to change the BL series’ settings. Since the wiring of this cable is different from that of the RS-232C cable for the N-400, both cables must be prepared. For wiring the BL-U2 and BL-U1, see the “BL-U2 Instruction Manual” and “BL series User’s Manual”, respectively. OP-27937 cable is available for BL-U2. (OP-22149 cable and OP-25057 are available for BL-U1.)

•

Twisted pair cable for the RS-485 Prepare the recommended cable. (➮ See pp. 19, 20 and 25.)

•

Host computer Use a personal computer with an RS-232C port. When large quantities of data are sent from several BL series, they may exceed the host computer’s data processing capacity. If this occurs, reduce the number of the connected BL series units, or enhance the data processing capacity (including the programming language) of the host computer.

■ Setup and connection 1) Setting the BL series bar code readers Prepare the BL series unit, the BL-U2 (or BL-U1) RS-232C power supply unit, the RS-232C cable used for setup, and a personal computer. Set up the BL series using the BL series setup software. For connection and setup procedures, see the “BL series User’s Manual”. For the pin assignment of the connection cable between the BL-U2 and the host computer, see the “BL-U2 Instruction Manual”. The setting contents vary slightly depending on the mode being used. Refer to the following pages for more information. • •

10

Multi-drop link mode: p. 60 Multi-head scan mode: p. 87

Page 19

Chapter 2

Installation Procedure

2) Setting the N-400 Prepare the N-400, the RS-232C cable for the N-400, and a personal computer. Set up the N-400 using the N-400 setup software. For the setup software operating procedure, see pp. 32 and following. The setting contents vary slightly depending on the mode being used. • • •

Multi-drop link mode: p. 60 Multi-head scan mode: p. 88 PLC link: p. 102

3) Setting a host computer/PLC For the RS-232C communication, set the baud rate, data length, parity and stop bit length according to the settings of the N-400. To use a PLC link, set up the PLC according to pp. 104 and 105. 4) Connection between the BL series and N-400 (See pp. 19, 20 and 25.) Connect the N-48 (or BL-U1) power supply unit to the BL series. Then connect the specified cable (twisted pair cable) between the power supply and the N400. Turn ON the equipment terminator at both ends of the connection. When using the BL-U1, set the DIP switch to “RS-485”. (See p. 22.) 5) Connection between the N-400 and host computer/PLC (See pp. 13 to 15.) To connect the N-400 to the host computer or PLC, use the RS-232C cable whose pin assignment conforms to that of the host computer and PLC. 6) Checking the RS-485 connection between the N-400 and the BL series The N-400 provides a connection test mode that checks whether the RS-485 connection is correct or not. Using this function, check whether the RS-485 communication can be correctly performed. For the procedure for using this function, see p. 26. 7) Connecting a sensor for trigger input Connect a sensor for trigger input to each N-48 or BL-U1 unit. (This sensor is not required when controlling the BL series’ reading operation using the read start/end commands.) To use the BL series in multi-head scan mode, connect a sensor for trigger input to the N-400. (This sensor is not required when controlling the BL series’ reading operation using the read start/end commands.) If the sensor for trigger input is directly connected to each BL series, the BL series cannot operate normally. 8) Checking operation Using the terminal software included in the N-400 setup software, check whether the RS-232C communication between the N-400 and host computer can be performed correctly. (See p. 52.) To use a PLC link, check whether data is stored in the PLC’s memory.

11

2

Page 20

Chapter 2

2.2

Installation Procedure

Connecting N-400 and Wiring This section describes the procedure for connecting the N-400 to external equipment.

TIM COM SG

2

RS-485 + -

24V DC IN + –

24V DC IN + –

2.2.1 Terminals of I/O terminal block and wiring Symbol

Description

Signal direction

TIM

Trigger input

Input

COM

Common terminal for trigger input

Input

RS-485 SG

RS-485 signal ground

–––

RS-485 +

RS-485 + terminal

Input/Output

RS-485 -

RS-485 - terminal

Input/Output

24 VDC OUT

24 VDC power output + terminal

Output

24 VDC power output - terminal

Output

24 VDC IN

24 VDC power input + terminal

Input

24 VDC power input - terminal

Input

* Viewed from the left of the terminal block.

•

The following I-type clips can be used for the connections.

2.0 mm max.

5 mm max.

6 mm min

Connecting power supply The N-400 operates with a 24 VDC power supply.

–

24V DC IN + –

24V DC IN + –

24 VDC +

When a 24 VDC power supply is connected to the power supply “IN” terminal, the “OUT” terminal can be used as the 24 VDC power supply output terminal. (Note: The power supply connected to the “IN” terminal must have a capacity high enough to supply power to the equipment connected to the “OUT” terminal.) Using this function, the “OUT” terminal can be used as a 24 VDC power supply for each BL series connected in the multi-drop link configuration. (For a connection example, see p. 19.)

CAUTION

To operate the N-400, be sure to use a 24 VDC power supply. Using a power supply exceeding 24 VDC or using an AC power supply may damage the unit. If your system must comply with UL regulations, be sure to use the power supply with NEC class 2 output.

12