The text of a manual · part 13 of 15
N-400 User's Manual: Multi-Drop Controller for BL Series, pages 121 to 130
Pages 121 to 130 of 150
The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Keyence N-400
Page 121
Chapter 6
PLC Link
Operation when a connection error occurs The power supply of the connected BL series is turned off: • The BL series is disconnected from the BL-U1 or N-48: • The cable is disconnected: • A communication error occurs: If a communication failure occurs between the BL series and N-400 when the N400 is in the multi-drop link mode, the N-400 operates as follows: Address
Contents
Operation during a connection error
A + 00
“Write Data” flag
The flag is turned on as data are area written.
A + 01
Reserved area
A + 02
ID number
“FFFF” is written.
A + 03
Number of bar code
“1” is written. (This indicates that the number of digits of the error code written in “A + 04” is “1”.)
A + 04
First digit of bar code data
During connection error: “N (ASCII codes: 4E)” is written. During communication error: “S (ASCII codes: 53)” is written.
*
The above specifications apply to the multi-drop link mode only. The same specifications do not apply to the multi-head scan mode. The addresses subsequent to “A + 04” retain the previous data.
*
Note: If the N-400’s power supply is turned on before the BL series is turned on, the N-400 starts communication before the BL series starts. This results in the above connection error. Create programs that ignore the connection error when the power supply is turned on in this case.
6
6.3.2 Device assignment in multi-head scan mode These areas are used to store the bar code data read in multi-head scan mode. Unlike multi-drop link mode, multi-head scan mode can control several BL series like a single unit. Therefore, this mode provides only one data memory area. Address
Description
Reference page
A + 00
Data memory flag area pp. 113 and 114
A + 01
Reading trigger area p. 114
A + 02
BL series ID number memory area
A + 03
Number of digits of bar code data
A + 04
1st digit of bar code data
A + 05
2nd digit of bar code data
:
:
:
:
A + 06
3rd digit of bar code data
A + 258
255th digit of bar code data p. 115
■ Detailed description on device assignment +00 Data memory flag area
This area is used as a flag that indicates if bar code data has been stored in the area. The flag area can be used for the following two purposes:
113
Page 122
Chapter 6
PLC Link
Real-time control •
To specify the flag area, use “0000” or “0001”.
•
While the N-400 is writing the bar code data read by the BL series in the PLC’s memory, the flag area is specified as “0001”.
•
When data writing is completed, the flag area becomes “0000”. This indicates that new data has been stored in the A+02 to A+258 addresses. When the A+00 address is “0000”, the stored data is available.
Example 1 Normally, the A+00 address is set to “0000”. While the N-400 is writing data, the flag area is “0001”. When the flag area becomes “0000”, the data stored in the A+02 to A+258 addresses can be processed. Example 2 Normally, the A+00 address is set to “0001”. When data writing is completed, the flag area becomes “0000”. The data stored in the A+02 to A+258 addresses can then be processed. Set the A+00 address to “0001” immediately after data processing is completed. When the A+00 address becomes “0000”, this indicates that writing new data is completed. Note: When the BL series continuously reads bar codes, the real-time processing mode may replace stored data with new data before the new data is processed in the PLC. This prevent this, use the sequential processing mode.
6
Sequential processing •
To specify the flag area, use “0002” or “0003”.
•
When the A+00 address is “0002”, new data can be stored.
•
When data writing is completed, the flag area becomes “0003”, and new data has been stored in the A+02 to A+258 addresses.
•
After data processing is completed, set the flag area to “0002”. Writing new data is impossible until the flag area is “0002.
•
Data which cannot be stored in the specified areas is retained in the BL series’ transmission buffer. (➮ For the capacity of the BL series’ transmission buffer, see p. 63.) If the amount of retained data exceeds the buffer capacity, the buffer overflow error occurs and the “OVER” code is stored in the corresponding area. +01 Reading trigger area
This area is used to send the trigger input signal to the BL series to start reading bar code data. You can set this area to “Used” or “Unused”, depending on the N400’s internal setting. (➮ See p. 41.) If you set this area to “Unused”, users can freely use it.
114
Page 123
Chapter 6
PLC Link
When a photoelectric sensor for trigger input is connected to the BL series, do not use this area. Specify this area as follows: • Start reading (Trigger ON): 0001 • End reading (Trigger OFF): 0000 Note: Specify this area as “0000” while the BL series is not reading bar code data. +02 to +258 Data (ID number, number of digits, data) memory area
•
The ID number of the BL series that read the data is stored in the +02 address. The number of data digits is stored in the +03 address as binary data.
•
The read bar code data is stored in the +04 to +258 addresses using the ASCII codes (Hexadecimal numbers in two digits) by the digit. (See the ASCII code table on p.134.)
•
If a read error occurs, the “ERROR” code is stored in the corresponding area. (The read error code can be easily changed according to the BL series’ setting.)
•
If the buffer overflow error occurs with the BL series, the “OVER” code is stored in the corresponding area. A+02
ID number (1 to 31)
A+03
Number of digits of bar code data (1 to 255)
A+04
1st digit of read data
A+05
2nd digit of read data
:
:
A+258
255th digit of read data
6
Note: These data areas accept up to 255 digits. However, the BL series can read only 32 digits. Therefore, all of the areas for 255 digits are not used for the N-400. Only the areas corresponding to the number of the data digits are used.
Example: When the BL series reads bar code data as “KE12”: + 02
12
ID number
+ 03
4
Number of digits
+ 04
$004B
"K"
+ 05
$0045
"E"
+ 06
$0031
"1"
+ 07
$0032
"2"
Specified by ASCII codes (hexadecimal numbers)
Example: When a read error (ERROR) occurs: + 02
ID number
1
+ 03
5
+ 04
$0045
"E"
Number of digits
+ 05
$0052
"R"
+ 06
$0052
"R"
+ 07
$004F
"O"
+ 08
$0052
"R"
Specified by ASCII codes (hexadecimal numbers)
115
Page 124
Chapter 6
6.4
PLC Link
PLC Link Error When a communication error occurs during PLC link, communication stops and the N-400 displays the following code:
or
When this error occurs with the PLC link, check the following points: 1. Check if the RS-232C communication parameters (baud rate, data length, parity and stop bit) for the PLC are matched with the N400’s settings. 2. Check if the N-400’s communication mode is set to “KV”, “MELSEC” or “SYSMAC”. 3. Check if the PLC’s settings are correct. (See pp. 106 and 107.) 4. Check if the cable connections are correct, or if any cable is disconnected. Referring to pp. 14 to 16 of this manual, check the connections using a multimeter. 5. Check if the device setting range does not exceed the available data memory areas of the PLC. If the data memory areas used for the N-400 do not exist in the PLC, communication is impossible.
6
6. Check if the link unit operates normally. To re-start the PLC link, press the test switch. For the settings of the link unit, see the instruction manual for the link unit being used.
116
Page 125
Chapter 6
6.5
PLC Link
Communication Time Even in PLC link mode, the RS-485 communication between the N-400 and each BL series is regarded as the same as standard mode serial communication. (➮ See pp. 83 to 85.) The time required for the RS-232C communication between the N-400 and the PLC is described below: This communication time may change depending on the PLC’s scan time and the model of the PLC. ■ Time required for RS-232C data transmission in PLC link mode The time required for data transmission from the N-400 to the PLC is as follows: This time duration corresponds to the “RS-232C data transmission time in multidrop link mode” (B) described on p. 84. To obtain the total communication time, add the “RS-485 data transmission time” (A) described on p. 82. * When the RS-232C communication baud rate is 9600 bps: Number of data digits
MELSEC-A
SYSMAC-C
KV(KV mode)
10
Approx. 300 ms
Approx. 350 ms
Approx. 500 ms
20
Approx. 350 ms
Approx. 400 ms
Approx. 750 ms
32
Approx. 400 ms
Approx. 500 ms
Approx. 1050 ms
■ Communication time to start reading using reading trigger area To control the BL series’ reading operation using the reading trigger area, enter the trigger ON command on the PLC, and obtain the time duration until the command is received by the N-400. This time duration corresponds to the “RS-232C command transmission time”(C) described on p. 84. To obtain the total communication time, add the “RS-485 command transmission time” (D + b) described on p. 84. * When the RS-232C communication baud rate is 9600 bps: Number of connected BL series
MELSEC-A
SYSMAC-C
KV(KV mode)
1
Approx. 150 ms
Approx. 150 ms
Approx. 100 ms
31
Approx. 400 ms
Approx. 600 ms
Approx. 1.5 s
117
6
Page 126
Chapter 6
6
118
PLC Link
Page 127
Appendices Appendix A
Specifications ................................................... 120
Appendix B
Dimensions ....................................................... 122
Appendix C
Sample Programs ............................................. 124 Sample programs for multi-drop link ................... 124 Sample program for PLC link .............................. 126
Appendix D
Troubleshooting ............................................... 131
Appendix E
Indications on the N-400 .................................. 133
Appendix F
ASCII Code Table ............................................. 134
Appendix G
Checksum Calculation Method ....................... 135
Appendix H
Setup Parameter List ....................................... 137
Appendix I
Default Setting List .......................................... 139
Appendix J
Sample Printout of Setting List ....................... 140
Page 128
Appendices
Appendix A
Specifications
N-400 Model
N-400
Connectable bar code reader Rated input
15 to 26 VDC, 10 mA max.
Max. OFF current
1.0 mA
RS-232C
Applied standards
EIA, RS-232C standards
Synchronization
Start-stop (full-duplex)
Transmission code
ASCII code
Baud rate
600/1200/2400/4800/9600/19200/31250/38400bps
Data length
7 or 8 bits
Parity check
Even/Odd/None
Stop bit length
1 or 2 bits
Appendices
RS-485
120
BL-700 series, BL-500 series, BL-180 series
Trigger input
Applied standards
EIA, RS-485 standards
Synchronization
Start-stop (full-duplex)
Transmission code
ASCII code
Baud rate
600/1200/2400/4800/9600/19200/31250/38400 bps
Data length
7 or 8 bits
Parity check
Even/Odd/None
Stop bit length
1 or 2 bits
Max. number of connectable units
31
Max. total extension distance
1.2 km
Ambient temperature
0 to 50°C (32 to 122°F), No freezing
Relative humidity
35 to 85%, No condensation
Ambient atmosphere
No dust or corrosive gas
Vibration resistance
10 to 55 Hz, 1.5 mm double amplitude in X, Y and Z directions, respectively
Power supply voltage
24 VDC +10%/-20%
Current consumption
140 mA max.
Weight
Approx. 180 g
Page 129
Appendices
N-48 Model
N-48
Conversion interface
RS-232C & RS-485 (Level conversion)
Connectable bar code reader
BL-500 series BL-180 series
Power supply for bar code reader Trigger Rated input input Max. OFF current
5 VDC ±5% (600 mA)
OK/NG output
Output form
NPN open-collector
Rated load
30 VDC, 100 mA
15 to 26 VDC, 10 mA max. 1.0 mA
Leakage current (at OFF) 0.1 mA max. Residual voltage (at ON)
1 V max.
Interface
RS-485 multi-drop (Max. number of connectable units: 31) (Max. total extension distance: 1.2 km)
Ambient temperature
0 to 50°C (32 to 122°F), No freezing
Relative humidity
35 to 85%, No condensation
Ambient atmosphere
No dust or corrosive gas
Vibration resistance
10 to 55 Hz, 1.5 mm double amplitude in X, Y and Z directions, respectively
Power supply voltage
24 VDC +10%/-20%
Current consumption
260 mA max.
Weight
Approx. 100 g
Model
BL-U1
Power supply for bar code reader
5 VDC ±5% (1.5 A)
Power supply for sensor
12 V ±10% (300 mA)
Trigger input
Rated input
8.5 to 30 VDC, 10 mA max.
Max. OFF current
0.5 mA
OK/NG output
Output form
NPN open-collector
Rated load
30 VDC, 100 mA
Appendices
BL-U1
Leakage current (at OFF) 0.1 mA max. Residual voltage (at ON)
1 V max.
Interface
RS-232C, RS-422A, RS-485 multi-drop (Max. number of connectable units: 31) (Max. total extension distance: 1.2 km)
Ambient temperature
0 to 50°C (32 to 122°F), No freezing
Relative humidity
35 to 85%, No condensation
Ambient atmosphere
No dust or corrosive gas
Vibration resistance
10 to 55 Hz, 1.5 mm double amplitude in X, Y and Z directions, respectively
Power supply voltage
100 to 240 VAC (50/60 Hz)
Power consumption
40 VA (100 VAC), 50 VA (240 VAC)
Weight
Approx. 615 g (including cable)
121
Page 130
Appendices
Appendix B
Unit: mm
Dimensions
N-400
N-400
27.3
TEST
RS-232C
SD
RD
POWER TIMING
CS SD
RS RD RS-455
35.4
112 100 90 TERMINATOR ON OFF
4 x ø4.5 mounting hole
40 60
(70)
51
Appendices
N-48
(70) 2 x ø4.5 mounting hole
5.5
43.2 55
5.9 5.9
26 63.2 75
122