For the Keyence BL-180 and Keyence BL-185
Page 85
BL-U1 Power Supply
Page 86
Introduction This User’s Manual describes the operation and functions of the BL-U1. Read this manual carefully to ensure safe use and maximum performance from your BL-U1. Note:
No part of this document is to be reproduced or utilized in any form or by any means without the written consent of KEYENCE Corporation. The contents of this document are subject to revision without notice. If you have any problems or questions regarding this document, please contact one of the KEYENCE offices listed on the last page of this document. KEYENCE is not responsible for any results of the application of the product. If the document contains incomplete printing, it can be exchanged for a complete one. • MS-DOS is a registered trademark of Microsoft U. S. A. • MS-Windows is a trademark of Microsoft U. S. A. • Other company names and product names are registered trademarks or trademarks of the respective companies.
Conventions This document uses the following conventions to help you easily recognize important and useful information.
CAUTION Note
Important information which must be read to avoid damaging the unit. Provides information for effective use of the unit. Read as required.
Page 87
System Configuration Using the RS-232C and RS-422A RS-232C null modem cable OP-22149 (1.5 m) + OP-25057 (25- to 9-pin adapter)
BL series
IBM PC/AT or compatible
BL-U1 Power supply unit RS-232C
Trigger input
BL-18H1E Setup software 3.5-inch version WINDOWS 3.1
OK/NG output
RS-422A Timing sensor
Equipment with RS-422A*
PLC etc.
• If not using the BL-U1, prepare an equivalent 5 VDC power supply unit separately. • To communicate through the RS-422A, you need a BL-U1 in your system.
Using the RS-485 multidrop link
BL series
Maximum number of connected units: 31 Maximum extension distance: 1.2 km
PC RS-485/RS-232C convertor
BL-U1
RS-485
RS-232C
• To communicate through the RS-485, you need a BL-U1 in your system. • Prepare a RS-485/RS-232C convertor separately. • When using the RS-485 multidrop link, you cannot use the Windows™ Setup software.
Other Options OP-22149 RS-232C null modem cable with D-sub 25-pin connector (1.5 m). To connect the BL-U1 to a IMB PC/AT compatible using the RS-232C port, use a 25- to 9-pin adapter (OP-25057).
79
Page 88
BL-U1 OK/NG LED OK output: Lights in green. NG output: Lights in red.
123
TIMING LED Lights when trigger input turns ON.
I/O terminal block Contains I/O terminals and RS-422A/RS-485 terminals.
Communication status indicator LEDs Indicate the communication status of each communication signal line. Each LED lights when the corresponding signal turns ON. Show SD, RD, RS, and CS from the top. POWER LED
Power switch Power cable (2 m) Use 100 to 240 VAC (50/60 Hz).
DIP switches
RS-232C port Connects to a PC. READER port Connects to a bar-code reader
80
Page 89
Power Supply BL-U1
1
BL-U1 Connections
1.1 Connecting the AC power supply Plug the BL-U1 power cable into the power receptacle. At the same time, ground the frame ground wire.
FG line
CAUTION
Make sure that the power supply provides 100 to 240 VAC ± 10%.
1.2 Connecting the BL-U1 to a BL series Use the READER port on the BL-U1. The pin assignment is shown in the table below: UL-U1 READER port pin assignment 1 2 3 4 5 D-sub 9-pin (male) DCE specification (defined as modem) #4-40 screw (female) 6 7 8 9
Pin No.
Symbol
Description
1 2 3 4
TIM RD (RXD) SD (TXD) OK
5
GND (SG)
6
NG
7
RS (RTS)
8
CS (CTS)
9
+5V
Trigger input Send data through RS-232C Receive data through RS-232C OK uotput Ground (common ground for respective signals) NG uutput Enable to send data through RS-232C (always ON) Request to send data through RS-232C (control method can be selected by DIP switches) + 5VDC power supply
Signal direction Output Output Input Input, - Input Input Output Output
83
Page 90
Power Supply BL-U1 Prepare the BL series for connection to the BL-U1 by soldering a D-sub 9-pin connector to the BL series cable. Then connect the cable to READER port of the BLU1. Prepare the D-sub 9-pin connector and its connector case separately. BL series - Connector case 1 TIM 2 RD 3 SD 4 OK 5 GND 6 NG 7 RS 8 CS 9 +5VDC D-sub 9-pin (female) #4-40 screw
Shield
Yellow Blown Purple White Black Gray Pink Blue Red
BL-U1
READER port
Use a metallic connector case for the D-sub 9-pin connector and connect the shielded line to the connector case. This allows connection to the earth ground of the AC power cable.
CAUTION
Take special care when soldering pin 5 (GND) and pin 9 (+5VDC). A wrong connection will damage the unit. Do not use a power cable over 2 meters long. A long power cable can cause a drop in voltage, preventing the BL series from starting up properly.
1.3 Setting the BL-U1 DIP switches According to the selected interface and timing input, change the DIP switch settings. OFF
ON
1
2
3
6
The switch settings at left are the factory default settings.
2
3
RS-232C
ON
OFF
OFF
RS-422A
OFF
ON
OFF
RS-485 multidrop
OFF
OFF
ON
4
5
RS-422A terminator (terminal resistance 100 Ω)
OFF
OFF
ON
ON
RS-485 terminator (terminal resistance 100 Ω)
OFF
OFF
ON
ON
READER port CS control method select
84
5
1
DIP switch setting Interface select
4
6
Reflect ON/OFF of CS at RS-232C port
OFF
Always ON
ON
Page 91
Power Supply BL-U1 1.4 Function and wiring on the I/O terminal block TIM
Trigger input
+12V OUT– COM
OK
NG
SDA
SDB
Power supply OK/NG output for sensors (12 VDC, 300 mA)
SG
TIM
Signal Direction Input
Timing input
+12V OUT
RDB
RS-422A/RS-485
Description
Symbol
RDA
Input
Power supply for sensors (+) (+12 VDC, 300 mA)
Output
Power supply for sensors (-) (0 V)
Output
COM
Common for OK/NG output, - OK
OK output
Output
NG
NG output
Output
SDA
Send RS-422A data (+)/RS-485 (+)
Output/Input and output
SDB
Send RS-422A data (-)/RS-485 (-)
Output/Input and output
SG
Signal ground, - RDA
Receive RS-422A data (+)
Input
RDB
Receive RS-422A data (-)
Input
The above list starts from the left edge terminal on the terminal block and sequentially goes to the right. • M 3.0 screws are used on the terminal block. • Use the clips shown below when wiring. Round-shape
Fork-shape
6.0 mm or less
Wiring the trigger input
6.0 mm or less
The trigger input signals the BL series to start reading. Turn on the trigger input by supplying 8.5 to 30 VDC between the trigger input terminals. You can use the “power supply for sensors” terminals of the BL-U1 as the input power supply. TIM
+12V OUT–
Contact or non-contact
+ + 8.5~30VDC
85
Page 92
Power Supply BL-U1 Wiring the OK/NG output
Use this output to determine OK/NG status by comparing the readout data with the preset data. It is NPN open-collector output. COM
OK
NG *Rated load: 30 V max. (100 mA) Load Load
+
Input/output circuit diagram
Output circuit
TIM
Internal circuit
3.3KΩ 2.4 KΩ
Internal circuit
Input circuit
OK/NG
COM
Load
+
1.5 RS-232C port pin assignment
86
13
1
25
14
Pin No.
Symbol
1 2 3
Shield SD (TXD) RD (RXD)
4
RS(RTS)
5 6 7 20
CS(CTS) DR(DSR) GND(SG) ER(DTR)
D-sub 25-pin connector (female) DTE specification (defined as terminal) N 2.6 screw (female)
Description Shield Send data through RS-232C Receive data through RS-232C Request to send data through RS-232C (Always ON) Enable to send to RS-232C Connect to pin 20 internally Signal Ground Connect to pin 6 internally
Signal direction, - Output Input Output Input Input, - Output
Page 93
Power Supply BL-U1 1.6 RS-232C port wiring When you want to connect the BL-U1 to a PC through the RS-232C port, the wiring is as shown below. You can use the optional OP-22149 cable (1.5 m) and OP-25057 (25- to 9-pin adapter). BL-U1 1 SD 2 RD 3 RS 4 CS 5 GND 7 DR 6 ER 20 D-sub 25-pin (male) M 2.6 screw
PC/AT 1 Shield 2 SD 3 RD 4 RS 5 CS 7 SG 6 DR 20 ER D-sub 25-pin (male) M 2.6 screw
1.7 RS-422A port wiring When you want to communicate using the RS-422A port, the wiring is as shown below. Use the BL-U1 input/output terminal block. Twisted pair cable BL-U1 SDA SDB RDA RDB GND
Shield RDA RDB SDA SDB SG External unit
• Set both terminators (terminal resistance 100 Ω) of the BL-U1 and external unit to ON (see P. 13). • The extended cable length must be within 1.2 km. You can prepare an equivalent cable which meets the following specifications: Item
Specification
Cable type
Shielded cable
Logarithm
3P
Conductor resistance (20°C)
88.0 Ω/km or less
Insulator resistance
10,000 MΩ.km or more
Withdraw voltage
500 VDC/minute
Static capacity (1 kHz)
60 nF/km or less (average)
Characteristic impedance (100 kHz)
110 ± 10 Ω
87