For the Intermec AI1620 and Intermec SmartPass Reader AI1620

Page 81

Testing and Configuring SmartPass Before Installation

4

Note: This is referring to transmission of data from the SmartPass to the host, not to transmitting RF energy. 5.

To verify that the RF has been changed to the proper setting, select the Tag & RF drop-down menu and click the RF Frequency option to see the current frequency setting.

RF Transmission The RF transmission can be controlled by any of the following methods:

•

A vehicle detector using one of the two sense input circuits

•

Software commands sent to SmartPass by the host

•

The sense input0 wire pair twisted together, as in the test configuration

As a factory default, SmartPass is configured to control the RF power with a vehicle detector. The vehicle detector can be a loop detector, an infrared sensor, or an ultrasonic detector that is connected to sense input0 to turn on the SmartPass RF transmitter.

4-29

Page 82

AI1620 SmartPass System Guide

Figure 4-20 illustrates the three methods of controlling RF sense output.

Figure 4-20 SmartPass RF Control Options

Vehicle Detector Controlling RF Transmission Figure 4-20, Option A, shows a vehicle detector controlling the RF transmitter. This operation is preferred because then the RF transmits only when a vehicle is in the SmartPass read zone.

4-30

Page 83

Testing and Configuring SmartPass Before Installation

4

Use the following procedure to set the option of the vehicle detector controlling SmartPass. 1.

Select the RF Control option from the Tag & RF pull-down menu. This displays the Select RF Control dialog box shown in Figure 4-21.

Figure 4-21 Set Sensor Control of RF

2.

Click on 3 RF-By-Sensor; then click OK.

Host Controlling RF Transmission Figure 4-20, Option B, shows the host controlling the RF transmitter. Note: For information and instructions on executing software commands, refer to Chapter 8, “Commands.” If the vehicle detector is connected to the host computer, as shown in Figure 4-20, Option B, commands 6400 (RF transmitter off) and 6401(RF transmitter on) from the host control the SmartPass RF transmitter. Leave the setting on RF-By-Sensor.

Continuous RF Transmission To test SmartPass, as described in the section “Testing Using an Audible Circuit Tester” on page 4-4, you can turn on the SmartPass RF transmitter continuously by twisting the red and green sense input0 wire pair together. SmartPass must be in command mode 6401, which enables the RF-by-input control (factory default). Sense Inputs Both the RS–232 and RS–422 configurations used by SmartPass have two sense inputs, sense input0 and sense input1. The default configuration uses sense input0 as the presence detection device line. RF power is automatically turned on only when the presence detection device (loop detector or other device) detects a presence. Sense input1 is not used directly by the reader; it is used by the host. SmartPass sense inputs are designed to connect to a dry contact closure.

4-31

Page 84

AI1620 SmartPass System Guide

You can configure SmartPass to generate input status change reports, which are transmitted like tag IDs. The host can then respond based on the true/false (closed/ open) status of the sense inputs. See the section “Reports” on page 4-23. The following example shows how to set sense inputs using SmartPass Host. See the section “526 Display I/O Status” on page 7-18, the section “694N Select Input Inversion Option” on page 7-40, and the section “82N Select Input Status Change Report Option” on page 7-42. 1.

Select the I/O drop-down menu and click the Input Status option to display the current status, as shown in Figure 4-22.

Note: This dialog box is for display only; you cannot make any changes to sense input using this dialog box.

Figure 4-22 Sense Input Status Dialog Box

4-32

Page 85

Testing and Configuring SmartPass Before Installation

2.

4

Click OK to clear the screen; then select the I/O drop-down menu again and click the Input Mode option. This will display the Select Input Mode dialog box, as shown in Figure 4-23.

Figure 4-23 Select Input Mode Dialog Box

3.

Click on Enable Input Inversion to switch the sense input status; then click OK.

Serial Port Communications SmartPass supports one communications port, which can be ordered as either RS–232/ Wiegand or RS–422/Wiegand. For the RS–232 and RS–422 communications specifications, SmartPass maintains the following three sets of parameters that affect serial port communications:

•

Port configuration parameters (baud rate, data bits, stop bits, parity)

•

Communication protocols (basic, data inquiry, error correcting)

•

Flow control scheme (none, software, hardware)

The default serial port configuration for each of these three parameters is as follows:

•

9600 baud, 8 data bits, 1 stop bit, no parity

•

Basic communications protocol

•

Software flow control (XON/XOFF)

You can change these parameters in data mode and command mode operation by issuing commands with the host or through SmartPass Host. Use the following procedures to set serial port communications parameters using SmartPass Host.

4-33

Page 86

AI1620 SmartPass System Guide

Port Configuration Parameters Use this procedure to set port configuration parameters using SmartPass Host. See the section “100N Select Baud Rate” on page 7-7 through the section “102N Select Parity” on page 7-8. 1.

Select the Communications drop-down menu and click the Parameters option. Figure 4-24 illustrates the options for port configuration parameters.

Figure 4-24 Port Configuration Parameters Dialog Box

2.

Click the option you want; then click OK to make the change.

Communications Protocol Use the following procedures to set communications protocol. Chapter 6 contains detailed reference information relevant to developing host software. Also, see the section “610 Select Basic Protocol (Factory Default)” on page 7-26 through the section “613 Select Data Inquiry Protocol” on page 7-27 for more information.

4-34

Page 87

Testing and Configuring SmartPass Before Installation

1.

4

Select the Communications drop-down menu and click the Protocol option. Figure 4-25 illustrates the two options available.

Figure 4-25 Protocol Parameters Submenu

2.

The Select Protocol option displays the Select Communications Protocol dialog box shown in Figure 4-26.

Figure 4-26 Select Communications Protocol Dialog Box

3.

Click the option you want; then click OK to make the change.

Software Flow Control Two modes of flow control are supported, software (XON/XOFF) and hardware (CTS - clear to send). The host can enable or disable flow control with command 614N.

4-35

Page 88

AI1620 SmartPass System Guide

The host can use software control characters (XON/XOFF) or the hardware CTS handshake line to interrupt reader transmissions. When the reader is configured for software flow control, it stops transmitting if it receives the XOFF character from the host (command 13H). It resumes transmitting only when it receives the XON character (command 11H) from the host. Likewise, when the reader is configured for hardware flow control, it stops transmitting if it detects that the CTS line is no longer asserted. It resumes transmitting when this line is asserted. If flow control is not needed, the reader should be configured for no flow control (command 6140). Note: Amtech recommends that XON/XOFF flow control be disabled while using the error correcting protocol.

Use the following procedure to set software flow control parameters using SmartPass Host. See the section “614N Select Flow Control Option” on page 7-27. 1.

Select the Communications drop-down menu and click the Flow Control command. Figure 4-27 illustrates the two options for flow control.

Figure 4-27 Port Configuration Parameters Submenu

4-36

Page 89

Testing and Configuring SmartPass Before Installation

4

If you select the Flow Control Modes option, the Select Flow Control dialog box, as shown in Figure 4-28, displays.

Figure 4-28 Select Flow Control Option Dialog Box

If you select the Flow On/Off option, the Select Option dialog box as shown in Figure 4-29 is displayed.

Figure 4-29 Select Option Dialog Box

2.

Click the option you want; then click OK to make the change.

Tag Translation Tag translation mode directs SmartPass whether or not to translate data received from half- or dual-frame tags. If tag translation mode is enabled, AAR or ATA tag format will be translated. If a non-ATA tag is read while in translate mode, no data will be displayed.

4-37

Page 90

AI1620 SmartPass System Guide

Use the following procedure to set tag translation options using SmartPass Host. See the section “452 Disable Tag Translation Mode (Factory Default)” on page 7-13 and the section “453 Enable Tag Translation Mode” on page 7-13. 1.

Select the Tag & RF drop-down menu and click the Tag Translation option. Figure 4-30 illustrates the options for translating tag data.

Figure 4-30 Select Translation Option Dialog Box

2.

4-38

Click the option you want to select; then click OK to make the change.