For the Intermec AI1620 and Intermec SmartPass Reader AI1620
Page 151
Commands
7 ms. The variable N specifies an output pulse duration of from 4 ms to 752 ms. Actual pulse length output of the reader may vary from the specified value by up to 4 ms. Uppercase or lowercase characters are allowed for NN; for example, hex digits A–F or a–f. Table 7-2 indicates the hex command for the output pulse durations. Table 7-2 Output Pulse Duration Hex Commands Command
Delay (ms)
670
4
671
8
672
12
673
16
674
20
675
24
676
32
677
40
678
48
679
60
67A
76
67B
152
67C
228 (factory default)
67D
300
67E
376
67F
752
For example, command 67F specifies an output pulse duration of 752 ms. Additional IDs may be acquired during the selected output pulse duration; however, the timing restarts upon each successive ID acquisition. This command should be used with discretion. For example, when the tag acquisition interval is short compared to the selected pulse duration, distinct pulses may not be generated. Reader message: Done or Error
690N Select Presence Without Tag Report Option This command selects the presence without the tag reporting option. If enabled using command 6901, input reports are transmitted when a presence is detected without the
7-37
Page 152
AI1620 SmartPass System Guide subsequent acquisition of a valid tag. The values for N specify the reports as indicated in Table 7-3. Table 7-3 Tag Reporting Option Commands Command
Report Option
6900
Disable presence without tag reports (factory default)
6901
Enable presence without tag reports
Reader message: Done
Refer to “Basic and ECP Protocol Format” on page 6-5 for message format information.
692N Select RF Control Algorithm This command selects the algorithm for turning off RF power when RF-by-input control is enabled using command 641. The values for N specify the following RF control algorithms, as indicated in Table 7-4. Table 7-4 RF Control Algorithm Commands Command
RF Power Off
6920
On timeout only
6921
Timeout or tag ID acquired
6922
Timeout or presence false (factory default)
Command 6920 turns off RF power based on the timeout established by command 693N. Command 6921 allows RF power to be turned off either after the timeout period or upon acquisition of a valid tag ID, whichever occurs first. Command 6922 turns off RF power either after the timeout period or upon the presence false condition, whichever occurs first. Reader message: Done
7-38
Page 153
Commands
7
693N Select RF Timeout Period Command 693N selects the RF timeout period used by RF control algorithm command 692N. Values for N range from 0 to E. Command 693F disables the RF timeout. The reader turns off the RF immediately following the acquisition of a valid tag, whether or not it is unique. This control algorithm may be used in Wiegand mode to ensure that the tag data is transmitted once and only once per presence on both serial and Wiegand ports. Uppercase or lowercase characters are allowed for NN; for example, hex digits A–F or a–f indicates the hex commands for the RF timeout periods. Table 7-5 RF Timeout Period Commands Command
Timeout (ms)
6930
0 (always expired)
6931
4
6932
8
6933
12
6934
20
6935
24
6936
32
6937
48
6938
60
6939
92
693A
152
693B
300
693C
452
693D
600
693E
752
693F
Infinite (never expires, factory default)
The reader returns an Error message if a valid hexadecimal digit is not substituted for N in command 693N. Reader message: Done or Error
7-39
Page 154
AI1620 SmartPass System Guide
694N Select Input Inversion Option Command 694N enables or disables input inversion. When inversion is enabled, an open circuit input is interpreted as a closed circuit, and a closed circuit input is interpreted as an open circuit. This feature allows greater flexibility in the attachment of external equipment to the reader inputs. For example, some proximity sensors indicate presence with an open circuit. In this instance, command 6941 can enable input inversion so that an open circuit input indicates a presence. The values for N represent the two inversion options. Table 7-6 presents the hex commands. Table 7-6 Input Inversion Enable/Disable Commands Command
Option
6940
Disable input inversion (factory default)
6941
Enable input inversion
Reader message: Done
695 Set Serial Number Command 695 assigns the reader serial number according to the format: 695SSSSSS where: SSSSSS is the serial number.
The serial number may contain as many as six uppercase or lowercase ASCII alphanumeric characters. Once assigned, the serial number is preserved during powerdown and the loading of default parameters. Reader message: Done
696S...S Store Hardware Configuration String Command 696S...S stores hardware configuration information into reader memory. Note: Once assigned, configuration information is preserved during power-down and the loading of default parameters. The hardware configuration string is assigned according to the following format: 696S...S where: S...S
7-40 is the hardware configuration string that may contain as many as 20 uppercase or lowercase ASCII alphanumeric characters.
Page 155
Commands
7
Reader message: Done
Auxiliary Reader Control, Command Group 8 Group 8 commands provide control of reader functions such as the system check tag and sense input lines.
810 Disable Periodic Check Tag (Factory Default) Command 810 disables the periodic operation of the system check tag. Reader message: Done
8110 Perform System Check Tag Test Command 8110 performs a single system check tag test. It may be executed either in data mode or command mode. Internal check tag circuitry emits a single ID that will be acquired and stored by the reader in the normal manner. If a real tag is in the field at the time, the check tag operation is aborted. Command 8110 disables the periodic check tag function, which is enabled by command 8120. Reader message: Done
8120 Enable Periodic Check Tag Command 8120 enables the periodic operation of the system check tag. The reader performs a system check tag test every 30 minutes. These tests continue until either the disable periodic check tag command 810 or the perform system check tag test command 8110 is received. Reader message: Done
8160 Select Internal Check Tag (Factory Default) Command 8160 selects the internal check tag option. Upon receiving command 8110 or 8120, the reader begins a check tag operation using internal check tag circuitry. This circuitry emits a single ID (system check tag) that is acquired and stored in the normal manner. Reader message: Done
7-41
Page 156
AI1620 SmartPass System Guide
82N Select Input Status Change Report Option Command 82N selects the input lines to be monitored to report any change in input status. The enabled input lines are monitored for any changes in their logic states. If a change is detected, the reader generates an input status change message and treats it as a tag ID. If the auxiliary information option is enabled, the input status field displays the current input values. The values for N specify the report options as indicated in Table 7-7. Table 7-7 Report Option Commands Command
Report Option
820
Disable status change reports (factory default)
821
Report change on input0
822
Report change on input1
823
Report changes on input0 and input1
Reader message: Done
Flash Memory Control, Command Group 9 Group 9 commands enables testing, erasing, and updating flash memory with new software versions.
90 Load Program Block Command 90 transfers one Intel hex data record from an external host to the reader flash memory. This command loads an entire program file into reader memory, one block at a time. The flash memory must have been previously erased using command 96. The reader must be operating in download mode (command 05) before it will accept the load program block command (command 90). Refer to “Program Download” on page 5-5 for download information and the download procedure. Reader message:
7-42
Done
Intel hex record has been received, stored, and verified with no errors detected.
Read Error
Error occurred during the transfer of the record.
Program Error
Error occurred during the programming of the flash memory.
Verify Error
Error occurred during the verification of the programmed data.
Page 157
Commands
7
91 Verify Flash Checksum Command 91 calculates a checksum on the flash memory and then compares it against the stored checksum. Reader message: Done flash checksum verified
Error flash checksum failed
96 Erase Flash Memory Command 96 erases the flash memory. Once this command is executed, exit from download mode is not possible until a new program is loaded into flash memory. Reader message: Done
97 Perform Destructive Flash Test Command 97 performs a test on the flash memory. Various patterns are programmed into the memory and verified. This test writes over any program previously stored in the flash memory; therefore, a download of software is required afterwards. Once this command is executed, exit from download mode is not possible until a new program is loaded into flash memory. Reader message: Done flash memory OK
Error flash memory failed
99 Exit Download Mode Command 99 instructs the reader to exit download mode. The reader will re-execute startup to ensure proper initialization of the reader. If the flash memory checksum verifies, the reader displays the sign-on message shown below and enters data mode. Reader message: Model SP2-ACC Ver X.XXD SNYYYYYY Copyright 1996 AMTECH Corp.
where: X.XXD is the version number.
YYYYYY is the serial number expressed in decimal digits (0 to 9) with the first two digits representing the year.
If the flash checksum is not verified, the reader comes up in download mode and transmits the sign-on message shown above.
7-43
Page 158
AI1620 SmartPass System Guide
7-44
Page 159
8 Installing SmartPass