Appendix Appendix B B DL405 Error Codes ERM/Slave Error Codes
Appendix A DL405 Error Codes
B--8
ERM / Slave Error Codes
Current / Last State Slave Error Codes The following table lists the Current and Last State Slave error codes for Word 0 and Word 3 in the Slave Diagnostic Word Memory Table. Applies to 205/405 and Terminator EBC modules. Error Code (Decimal)
Description
E0
No error.
E121
Channel failure.
E122
Unused analog input channels exist.
E139
Broken transmitter on one of the analog input channels (if supported by analog module)
E142
Multiple channels failed.
E153
The module which was in this slot is no longer responding. User has removed a module in a Terminator I/O slave system. If Automatic Reset (default) is enabled for this slave, it will reset itself once the replacement module is inserted. If Manual Reset is enabled for this slave, the user must 1) SET the slave disable flag for that slave in the first diagnostic output word, 2) wait for bits 8--15 in second diagnostic input word to equal 1, then 3) RESET the slave disable flag in the first diagnostic output word.
E154
I/O configuration has changed. See E153 for reset methods.
E200-E216
Unused analog input channels exist at channel xx (1--16), where xx = Value --200. (example: E212 indicates unused analog channel exists at channel 12.
Extended Slave Error Codes The following table lists the Extended Slave error codes for Words 4--35 in the Slave Diagnostic Word Memory Table. Applies to 205/405 and Terminator EBC modules. Error Code (Decimal)
Description
E32-E63
Bitwise error where bit 5 is always SET. Look at bit 0 thru bit 4 to get a possible list of errors. Example 34 decimal =22 hexadecimal (Bit 5 SET and Bit 1 SET). BIT 0 1 2 3 4 5
Type of Error Terminal block off External P/S voltage low Fuse blown Bus error Module initialization error (intelligent module) Fault exists in module (this bit is SET if any of the above bits are SET)
E117
Write attempt to an invalid analog channel.
E121
Analog input channel error.
E122
Unused analog input channels exist.
E139
Broken transmitter on one of the analog input channels.
E142
Channel failure.
E153
The module which was in this slot is no longer responding. User has removed a module in a Terminator I/O slave system. If Automatic Reset is enabled for this slave, it will reset itself once the replacement module is inserted. If Manual Reset is enabled for this slave, the user must 1) SET the slave disable flag for that slave in the first diagnostic output word, 2) wait for bits 12--15 in second diagnostic input word to equal 1, then 3) RESET the slave disable flag in the first diagnostic output word.
E154
One or more new modules has been inserted into the base. See E153 for reset methods.
E200-E216
Unused analog input channels exist at channel xx (1--16), where xx = Value --200.
Page 72
ERM and ERM Workbench Default Settings
1C
In This Appendix. . . ., ERM and ERM Workbench Factory Default Settings
Page 73
Appendix C ERM/Slave Error Codes
Appendix B DL405 Error Codes
Appendix A DL405 Error Codes
C--2
ERM / Slave Error Codes
ERM and ERM Workbench Factory Default Settings The following factory default settings or values can be changed by using the tools within the ERM Workbench utility. Item
Default
Protocol
IPX
Address Mode
Ethernet Address
ERM Timeout to Slave
25ms
ERM Retries
1
Slave Watchdog
250ms
ERM Pet Slave Watchdog
0 (disabled)
ERM Consecutive Comm Failures to Slave Before Placing Slave in Standby Mode
5
Slave Padding
0
Bit Input Address
V40414 (X300)
Bit Output Address
V40514 (Y300)
Word Input Address
V2000
Word Output Address
V2100
Standby Cycle Time
500ms
Unsupported Slave Cycle Time
1000ms
Page 74
Mapping ERM Slave I/O in a Think & Do WinPLC System In This Appendix. . . ., Mapping ERM Slave I/O Points
1D
Page 75
D--2
Think & Do WinPLC / ERM Network
Appendix A
Mapping ERM Slave I/O Points This purpose of this appendix is to identify that the Think & Do ConnectivityCenter tool is used to configure (map) the ERM remote slave I/O points to Data Items. We recommend that you are familiar with the “Getting Started” and “Creating a Project” chapters in the Think & Do Studio Learning Guide before attempting to configure the ERM I/O in ConnectivityCenter.
Appendix D T&D WinPLC / ERM I/O
NOTE: The ERM and its slaves need to be configured using ERM Workbench before using Think & Do ConnectivityCenter to map the ERM slave I/O points to Data Items.
Launching Connectivity Center Tool
To launch ConnectivityCenter:
Connecting to the WinPLC Base I/O
ConnectivityCenter will draw a picture of your WinPLC / ERM I/O network. Clicking on the Backplane I/O Driver in the Board view window will display the WinPLC I/O base.
1) Launch Think & Do Studio ProjectCenter from the Windows desktop by clicking on Start > Programs > Think & Do Studio > ProjectCenter. Or, click on the ProjectCenter icon to start. 2) Click on the File Menu and either Open your Think & Do Project or select New. 3) Within ProjectCenter select Windows CE -- Think & Do WinPLC as the Runtime Target. 4) Then click Tools > ConnectivityCenter to launch ConnectivityCenter. Or, click on the ConnectivityCenter shortcut in the Project Explorer. 5) Once in ConnectivityCenter click on Configuration > Connect or click on the Connect toolbar button.
ERM module Board View
Clicking on Backplane I/O Driver displays the WinPLC base I/O.
Page 76
Think & Do WinPLC / ERM Network
Connecting to the ERM Slave I/O
D--3
Clicking on the Ethernet Remote Master Driver in the Board view window will display the ERM slave I/O base(s). ERM Slave 1 I/O Base
Board View
Clicking on Ethernet Remote Master Driver displays the ERM slave I/O bases.
ERM Slave 2 I/O Base
Board View
Mapping I/O Points This process is discussed in detail in the “Creating a Project” chapter in the Think & Do Studio Learning Guide. This will map your real world I/O to Data Items. to Data Items
Appendix D T&D WinPLC / ERM I/O
Clicking on Ethernet Remote Master Driver displays the ERM slave I/O bases.