Appendix Appendix B B DL405 Error Codes ERM/Slave Error Codes

Appendix A DL405 Error Codes

B--8

ERM / Slave Error Codes

Current / Last State Slave Error Codes The following table lists the Current and Last State Slave error codes for Word 0 and Word 3 in the Slave Diagnostic Word Memory Table. Applies to 205/405 and Terminator EBC modules. Error Code (Decimal)

Description

E0

No error.

E121

Channel failure.

E122

Unused analog input channels exist.

E139

Broken transmitter on one of the analog input channels (if supported by analog module)

E142

Multiple channels failed.

E153

The module which was in this slot is no longer responding. User has removed a module in a Terminator I/O slave system. If Automatic Reset (default) is enabled for this slave, it will reset itself once the replacement module is inserted. If Manual Reset is enabled for this slave, the user must 1) SET the slave disable flag for that slave in the first diagnostic output word, 2) wait for bits 8--15 in second diagnostic input word to equal 1, then 3) RESET the slave disable flag in the first diagnostic output word.

E154

I/O configuration has changed. See E153 for reset methods.

E200-E216

Unused analog input channels exist at channel xx (1--16), where xx = Value --200. (example: E212 indicates unused analog channel exists at channel 12.

Extended Slave Error Codes The following table lists the Extended Slave error codes for Words 4--35 in the Slave Diagnostic Word Memory Table. Applies to 205/405 and Terminator EBC modules. Error Code (Decimal)

Description

E32-E63

Bitwise error where bit 5 is always SET. Look at bit 0 thru bit 4 to get a possible list of errors. Example 34 decimal =22 hexadecimal (Bit 5 SET and Bit 1 SET). BIT 0 1 2 3 4 5

Type of Error Terminal block off External P/S voltage low Fuse blown Bus error Module initialization error (intelligent module) Fault exists in module (this bit is SET if any of the above bits are SET)

E117

Write attempt to an invalid analog channel.

E121

Analog input channel error.

E122

Unused analog input channels exist.

E139

Broken transmitter on one of the analog input channels.

E142

Channel failure.

E153

The module which was in this slot is no longer responding. User has removed a module in a Terminator I/O slave system. If Automatic Reset is enabled for this slave, it will reset itself once the replacement module is inserted. If Manual Reset is enabled for this slave, the user must 1) SET the slave disable flag for that slave in the first diagnostic output word, 2) wait for bits 12--15 in second diagnostic input word to equal 1, then 3) RESET the slave disable flag in the first diagnostic output word.

E154

One or more new modules has been inserted into the base. See E153 for reset methods.

E200-E216

Unused analog input channels exist at channel xx (1--16), where xx = Value --200.

Page 72

ERM and ERM Workbench Default Settings

1C

In This Appendix. . . ., ERM and ERM Workbench Factory Default Settings

Page 73

Appendix C ERM/Slave Error Codes

Appendix B DL405 Error Codes

Appendix A DL405 Error Codes

C--2

ERM / Slave Error Codes

ERM and ERM Workbench Factory Default Settings The following factory default settings or values can be changed by using the tools within the ERM Workbench utility. Item

Default

Protocol

IPX

Address Mode

Ethernet Address

ERM Timeout to Slave

25ms

ERM Retries

1

Slave Watchdog

250ms

ERM Pet Slave Watchdog

0 (disabled)

ERM Consecutive Comm Failures to Slave Before Placing Slave in Standby Mode

5

Slave Padding

0

Bit Input Address

V40414 (X300)

Bit Output Address

V40514 (Y300)

Word Input Address

V2000

Word Output Address

V2100

Standby Cycle Time

500ms

Unsupported Slave Cycle Time

1000ms

Page 74

Mapping ERM Slave I/O in a Think & Do WinPLC System In This Appendix. . . ., Mapping ERM Slave I/O Points

1D

Page 75

D--2

Think & Do WinPLC / ERM Network

Appendix A

Mapping ERM Slave I/O Points This purpose of this appendix is to identify that the Think & Do ConnectivityCenter tool is used to configure (map) the ERM remote slave I/O points to Data Items. We recommend that you are familiar with the “Getting Started” and “Creating a Project” chapters in the Think & Do Studio Learning Guide before attempting to configure the ERM I/O in ConnectivityCenter.

Appendix D T&D WinPLC / ERM I/O

NOTE: The ERM and its slaves need to be configured using ERM Workbench before using Think & Do ConnectivityCenter to map the ERM slave I/O points to Data Items.

Launching Connectivity Center Tool

To launch ConnectivityCenter:

Connecting to the WinPLC Base I/O

ConnectivityCenter will draw a picture of your WinPLC / ERM I/O network. Clicking on the Backplane I/O Driver in the Board view window will display the WinPLC I/O base.

1) Launch Think & Do Studio ProjectCenter from the Windows desktop by clicking on Start > Programs > Think & Do Studio > ProjectCenter. Or, click on the ProjectCenter icon to start. 2) Click on the File Menu and either Open your Think & Do Project or select New. 3) Within ProjectCenter select Windows CE -- Think & Do WinPLC as the Runtime Target. 4) Then click Tools > ConnectivityCenter to launch ConnectivityCenter. Or, click on the ConnectivityCenter shortcut in the Project Explorer. 5) Once in ConnectivityCenter click on Configuration > Connect or click on the Connect toolbar button.

ERM module Board View

Clicking on Backplane I/O Driver displays the WinPLC base I/O.

Page 76

Think & Do WinPLC / ERM Network

Connecting to the ERM Slave I/O

D--3

Clicking on the Ethernet Remote Master Driver in the Board view window will display the ERM slave I/O base(s). ERM Slave 1 I/O Base

Board View

Clicking on Ethernet Remote Master Driver displays the ERM slave I/O bases.

ERM Slave 2 I/O Base

Board View

Mapping I/O Points This process is discussed in detail in the “Creating a Project” chapter in the Think & Do Studio Learning Guide. This will map your real world I/O to Data Items. to Data Items

Appendix D T&D WinPLC / ERM I/O

Clicking on Ethernet Remote Master Driver displays the ERM slave I/O bases.