Page 61

Appendix A General Specifications In This Appendix

1A, H2--ERM and H4--ERM Specifications, H2--ERM--F and H4--ERM--F Specifications, Ethernet Standards

Page 62

Appendix A General Specifications

A--2

General Specifications

General Specifications ERM Specifications

H2--ERM / H4--ERM General Specifications Module Type

Ethernet I/O Communications Master Module

Quantity of Modules Per Base

Defined by CPU, base configuration and power budget

Quantity of Slaves per ERM

16 max.

Diagnostics

LEDs, ERM Workbench, NetEdit

Communications

10BaseT Ethernet

Data Transfer

10 Million bits per second

Extension Port

RJ45

Link Good Indicator (LINKGD)

Green LED

Activity Indicator (ACT)

Red LED

Error Indicator (ERROR)

Red LED

Power Consumption

530 mA @ 5VDC (Supplied by DL205/DL405 base)

Operating Temperature

32° to 140° F (0° to 60° C)

Storage Temperature

--4° to 158° F (--20° to 70° C)

Relative Humidity

30% -- 95% RH (non-condensing)

Environmental Air

No corrosive gases permitted

Networking Protocols Supported

IPX, UDP/IP

Manufacturer

Host Automation Products

Link Distance

100 meters (328 feet) H2--ERM--F / H4--ERM--F General Specifications

Module Type

Ethernet I/O Communications Master Module

Quantity of Modules Per Base

Defined by CPU, base configuration and power budget

Quantity of Slaves per ERM

16 max.

Diagnostics

LEDs, ERM Workbench , NetEdit

Communications

10BaseFL Ethernet (fiber optic)

Data Transfer

10 Million bits per second

Extension Port

ST-style fiber optic connector

Link Good Indicator (LINKGD)

Green LED

Activity Indicator (ACT)

Red LED

Error Indicator (ERROR)

Red LED

Power Consumption

670 mA @ 5VDC (Supplied by DL205/DL405 base)

Operating Temperature

32° to 140° F (0° to 60° C)

Storage Temperature

--4° to 158° F (--20° to 70° C)

Relative Humidity

30% -- 95% RH (non-condensing)

Environmental Air

No corrosive gases permitted

Networking Protocols Supported

UDP/IP, IPX

Manufacturer

Host Automation Products

Link Distance

Up to 2,000 meters (2Km), 6,560ft (1.2 miles)

Page 63

General Specifications

A--3

Various institutes and committees have been involved in establishing Ethernet data communication standards. These specification standards assure Ethernet network compatibility for products from a broad variety of manufacturers. The ERM module complies with American National Standards Institute (ANSI) and Institute of Electrical and Electronic Engineers standard ANSI/IEEE 802.3, Carrier Sense Multiple Access with Collision Detection (CSMA/CD) Access Methods and Physical Layer Specifications. This standard has been adopted by the International Organization for Standardization (ISO) as document ISO/IEC 8802--3. The Electronic Industries Association (EIA) and Telecommunications Industries Commercial Building Telecommunications Wiring Standard designated EIA/TIA--568A defines implementation of 10BaseT (twisted pair) and 10BaseF (fiber optics) for Ethernet communications. The same two organizations produced EIA/TIA TSB40--Additional Transmission Specifications for Unshielded Twisted-Pair Connecting Hardware. The purpose of this document is to specify transmission performance requirements and connecting hardware requirements.

Appendix AA Appendix DL205 Specifications Memory Map General

Ethernet Standards

Page 64

ERM / Slave Diagnostics and Error Codes In This Appendix. . . ., ERM Diagnostics, ERM Status Word Error Codes, Reading ERM Statistics, Reading Error Codes From Slaves, Slave Diagnostic Word Memory, Current / Last State Slave Error Codes, Extended Slave Error Codes

1B

Page 65

Appendix A DL405 Error Codes

B--2

ERM / Slave Error Codes

ERM Diagnostics Reserved PLC Memory for ERM

If a PLC is used as the CPU Interface, the first two words of V memory in the Discrete Input table is used for ERM/slave status information, and the first word of V memory in the Discrete Output table is for Disable Slave Command bits. The default memory addresses X300 and Y300 are used in this example. Slave Status Bits MSB

Appendix Appendix B B DL405 Error Codes ERM/Slave Error Codes

Slave 16

V40414

X 3 1 7

LSB X 3 0 0

Slave 1

ERM Status Word MSB

V40415

LSB

X 3 3 7

X X 3 3 3 2 0 7

X 3 2 0

Status Bits

The ERM Status Word contains the ERM error code and Status Bits. Refer to “Reserved PLC Memory for ERM” in Chapter 4. Bit 8 indicates that the ERM is disabling a slave.

Error Code

Disable Slave Bits MSB Slave 16 Y 3 1 7

The Slave Status Bits can be monitored to detect if a slave is in error.

V40514

LSB Y 3 0 0

Slave 1

The Disable Slave Bits can be used to disable a slave from communicating with the ERM module.

ERM Status Word / The ERM Status Word contains the current ERM Error Code in the Least Significant Resetting the Slave Byte and the Status Bits in the Most Significant Byte. Currently, only bit 8 is used in the MSB designating the ERM is disabling Slave. When using the Slave Disable Bits, the ERM must recognize the request to disable a slave before attempting to re--enable that slave. This closed loop feedback is necessary due to the asynchronous scans of the ERM and PLC. X330 is the only feedback bit for ALL slave disabling bits (Y300 -- Y317). Either disable multiple slaves all on the same scan or serialize the disable process by using ladder logic interlocks. Use the following ladder logic code to manually reset a slave. For example, use this resetting method when “Hot Swapping” a Terminator I/O module on a slave that is set up to be manually reset using ladder logic. The default for the Terminator EBC is automatic rescan after “Hot Swapping” and I/O module. DirectSOFT C200

C0 PD

Y300

C0

Y300

Event occurs to reset Slave 1

X330

SET

Disable Slave 1

Y300

Wait to re--enable Slave 1 until X330 (ERM Disable Request Bit) is ON.

RST

Page 66

ERM / Slave Error Codes

B--3

The following table describes the errors that will be reported to the ERM Status Word. Error Code Description (Decimal) No error.

E3

Configured bit inputs overlap system input bits.

E4

Configured bit outputs overlap system output bits.

E5

More than one device found with same module ID.

E6

More than one device found with same IP address.

E7

ERM could not read slave’s error information -- slave not responding.

E8

Device not supported; may be old firmware or configuration error.

E9

Device timed out on a function request after retrys.

E13

Gateway address needed, but not specified

E14

Subnet mask needed, but not specified.

E15

Configured module ID’s do not match modules in device.

E16

Number of bit inputs specified in ERM is less than actual in slaves.

E17

Number of bit outputs specified in ERM is less than actual in slaves.

E18

Number of word inputs specified in ERM is less than actual in slaves.

E19

Number of word outputs specified in ERM is less than actual in slaves.

E20

Invalid base definition for this device.

E21

ERM has not been configured

E22

Overflow of internal buffer E22.

E23

Overflow of internal buffer E23.

E24

Overflow of internal buffer E24.

E25

Overflow of internal buffer E25.

E26

Overflow of internal buffer E26.

E27

Configuration error: input words configured not enough.

E28

Configuration error: output words configured not enough.

E221

ERM to CPU backplane error.

E223

PLC family unknown.

E224

ERM to CPU backplane error.

E225

Backplane code error returned from PLC.

E226

General backplane error returned from PLC.

E227

Timeout on PLC backplane error.

E228

ERM to CPU backplane error.

E231

ERM to CPU backplane error.

Appendix B B Appendix DL405 Error Codes ERM/Slave Error Codes

E0

Appendix A DL405 Error Codes

ERM Status Word Error Codes

Page 67

Appendix Appendix B B DL405 Error Codes ERM/Slave Error Codes

Appendix A DL405 Error Codes

B--4

ERM / Slave Error Codes

Reading ERM Statistics Reading ERM Statistics using Ladder Logic

The following ladder logic example reads the ERM statistics from the ERM module. 12 words (24 bytes) of statistical data are stored in the ERM’s memory starting at V0 (TA0). Use slave address of 90 when reading ERM statistics. In the example below, the RX instruction stores the statistical data from the ERM module to V1400 -- V1413 in the CPU’s memory. More information on the RX network instruction can be found in the PLC User Manual. The ERM module is located in slot 2 of the I/O base in this example. Refer to the Special Relays Appendix in the PLC User Manual to identify each slot’s Module Busy and Comm Error bits. The format of the ERM’s statistics is as follows: PLC Address

Description of Statistic

Format

Addr + 0

Minimum I/O Scan in milliseconds

Word / Decimal

Addr + 1

Maximum I/O Scan in milliseconds

Word / Decimal

Addr + 2,3

Total accumulated time in milliseconds

DWord / Decimal

Addr + 4,5

Total number of I/O Scans

DWord / Decimal

Addr + 6,7

Number of PLC Read Retries

DWord / Decimal

Addr + 10,11

Number of PLC Write Retries

DWord / Decimal

Addr + 12,13

Number of Slave Retries

DWord / Decimal

DirectSOFT Module Busy Slot 2 SP124

Comm Error Slot 2 SP125

C200

LD K0290 The constant value K0290 specifies the slot number (2) and to read ERM statistics (90). LD K24 The constant value K24 specifies the number of bytes to be read (12 words). LDA O 1400 Octal address 1400 is converted to 300 HEX and loaded into the accumulator. V1400 is the starting location for the Master CPU where the specified data will be read into. RX TA0 V0 (TA0) is the starting location in the ERM where the specified data will be read from. C200 SET

Module Busy Slot 2 SP124

C200 RST

Page 68

ERM / Slave Error Codes

B--5

Reading Error Codes from Slaves using Ladder Logic

DirectSOFT

Module Busy K0

VC60

SR

=

C60 C77

K0

VX300

SP124

SP7

Module Busy Slot 2 SP124

Comm Error Slot 2 SP125

= C63

Slave 1 Error bit X300

C60

K0201

The constant value K0201 specifies the slot number (2) and slave 1.

K24

The constant value K24 specifies the number of bytes to be read (12 words).

LD

LD

LDA O 2000

RX

Continued on next page

TA0

Octal address 2000 is converted to 400 HEX and loaded into the accumulator. V2000 is the starting location for the Master CPU where the specified data will be read into. V0 (TA0) is the starting location in the slave module where the specified data will be read from.

Appendix B B Appendix DL405 Error Codes ERM/Slave Error Codes

The following ladder logic example reads the Error Codes from a specific slave (1--16). The slave’s error data is stored in its memory starting at V0 (TA0). Up to 36 words (72 bytes) of error codes can be read from a slave depending upon the amount of bases and I/O modules (slots) used per slave. In the example below, the RX instruction stores the Error data read from Slave 1 to V2000 -- V2013 and from Slave 2 to V2020 -- V2033, etc. in the CPU’s memory. More information on the RX network instruction can be found in the PLC User Manual The ERM module is located in slot 2 of the 205 I/O base in this example. Refer to the Special Relays Appendix in the PLC User Manual to identify each slot’s Module Busy and Comm Error bits. Refer to the Slave Diagnostic Word Memory Table on the following page for a description of the word information read from the slaves. This example reads words V0 -- V11 (24 bytes) from the slaves.

Appendix A DL405 Error Codes

Reading Error Codes from Slaves

Page 69

Appendix Appendix B B DL405 Error Codes ERM/Slave Error Codes

Appendix A DL405 Error Codes

B--6

ERM / Slave Error Codes

Continued from previous page DirectSOFT Slave 2 Error bit X301

C61

Module Busy Slot 2 SP124

Comm Error Slot 2 SP125

K0202

The constant value K0202 specifies the slot number (2) and slave 2.

K24

The constant value K24 specifies the number of bytes to be read (12 words).

LD

LD

LDA O 2020

RX TA0

Slave 3 Error bit X302

C62

Module Busy Slot 2 SP124

Comm Error Slot 2 SP125

LD K0203

LD K24

LDA O 2040

RX TA0

Octal address 2020 is converted to HEX and loaded into the accumulator. V2020 is the starting location for the Master CPU where the specified data will be read into. V0 (TA0) is the starting location in the slave module where the specified data will be read from.

The constant value K0203 specifies the slot number (2) and slave 3. The constant value K24 specifies the number of bytes to be read (12 words). Octal address 2040 is converted to HEX and loaded into the accumulator. V2040 is the starting location for the Master CPU where the specified data will be read into. V0 (TA0) is the starting location in the slave module where the specified data will be read from.

Page 70

ERM / Slave Error Codes

B--7

The following table describes the Word information that is obtained when a slave’s diagnostic information is read (RX) by the PLC CPU into its memory. Applies to 205/405 and Terminator EBC modules. Description

V +0

Current slave error code: Bits 0 -- 11 Type of Error: Bits 12--15: ( Bit 12 SET = I/O Error Condition; Bit 13 SET = I/O Warning)

V +1

Slave module slot in error (slots 0 -- 15).

V +2

Slave module slot in error (slots 16 -- 31).

V +3

Slave’s Last error code

V +4

Extended error code module in slot 0.

V +5

Extended error code for module in slot 1.

V +6

Extended error code for module in slot 2.

V +7

Extended error code for module in slot 3.

V +8

Extended error code for module in slot 4.

V +9

Extended error code for module in slot 5.

V +10

Extended error code for module in slot 6.

V +11

Extended error code for module in slot 7.

V +12

Extended error code for module in slot 8 or base 1 slot 0.

V +13

Extended error code for module in slot 9 or base 1 slot 1.

V +14

Extended error code for module in slot 10 or base 1 slot 2.

V +15

Extended error code for module in slot 11 or base 1 slot 3.

V +16

Extended error code for module in slot 12 or base 1 slot 4.

V +17

Extended error code for module in slot 13 or base 1 slot 5.

V +18

Extended error code for module in slot 14 or base 1 slot 6.

V +19

Extended error code for module in slot 15 or base 1 slot 7.

V +20

Extended error code for module in slot 16 or base 2 slot 0.

V +21

Extended error code for module in slot 17 or base 2 slot 1.

V +22

Extended error code for module in slot 18 or base 2 slot 2.

V +23

Extended error code for module in slot 19 or base 2 slot 3.

V +24

Extended error code for module in slot 20 or base 2 slot 4.

V +25

Extended error code for module in slot 21 or base 2 slot 5.

V +26

Extended error code for module in slot 22 or base 2 slot 6.

V +27

Extended error code for module in slot 23 or base 2 slot 7.

V +28

Extended error code for module in slot 24 or base 3 slot 0.

V +29

Extended error code for module in slot 25 or base 3 slot 1.

V +30

Extended error code for module in slot 26 or base 3 slot 2.

V +31

Extended error code for module in slot 27 or base 3 slot 3.

V +32

Extended error code for module in slot 28 or base 3 slot 4.

V +33

Extended error code for module in slot 29 or base 3 slot 5.

V +34

Extended error code for module in slot 30 or base 3 slot 6.

V +35

Extended error code for module in slot 31 or base 3 slot 7.

Appendix B B Appendix DL405 Error Codes ERM/Slave Error Codes

Word

Appendix A DL405 Error Codes

Slave Diagnostic Word Memory