Page 21

C-BOX 200

DATALOGIC

2.4.5 RS485 Bus Termination

ON OFF S2

Figure 2.11 - Termination resistance switch

The switch S2 enables or disables the insertion of the bus termination resistor for RS485 Half Duplex Multidrop applications. CAUTION In Multiplexer applications the termination resistor must be enabled ONLY on the last device of the chain, the farthest away from the Multiplexer (assuming the Multiplexer is the first device of the chain). On all the other devices this resistor MUST NOT be enabled (S2 = OFF). Normally it is not necessary to enable the terminator resistor (S2 always OFF); it is suggested only in applications where the communication speed or the bus length are critical parameters.

12 - Installation

Page 22

DATALOGIC

C-BOX 200

2.4.6 Connection to a Multiplexer The following figure shows a multidrop layout with C-BOX 200 devices connected to a Multiplexer: (*) SCANNER

C-BOX 200 12 RTX485#N 11 RTX485+ (up to 31)

10 RS485 REF 9 CABLE SHIELD

EARTH GROUND

13 CABLE SHIELD 14 RS485 REF 15 RTX485+ 16 RTX485-

C-BOX 200

SCANNER

#1

12 RTX48511 RTX485+ 10 RS485 REF 9 CABLE SHIELD max 1200 m

EARTH GROUND 13 CABLE SHIELD 14 RS485 REF 15 RTX485+ 16 RTX485-

SCANNER

C-BOX 200 #0

EARTH GROUND

12 RTX48511 RTX485+ 10 RS485 REF 9 CABLE SHIELD

Three wires + shield

MULTIPLEXER

CABLE SHIELD RS485 REF RTX485+ RTX485-

EARTH GROUND

120 Ohm

(*) If necessary enable the termination resistor only in the last device.

Figure 2.12 - Multiplexer connection

Installation - 13

Page 23

C-BOX 200

DATALOGIC

2.4.7 OM4000 Jumper Settings

J1

J2

Figure 2.13 - OM4000 jumpers

The jumpers allow connection to the EXT TRIG signals on separate spring clamp terminals for applications which use the OM4000 Oscillating Mirror in Trigger Mode. They are used together and they have the following significance: when a jumper is in the J1 position (see Figure above) pin 40 is connected to pin 27 (EXT TRIG+); a jumper in J2 position connects pin 20 to pin 28 (EXT TRIG-). If the jumpers are removed pin 20 and pin 40 are disconnected.

14 - Installation

Page 24

DATALOGIC

C-BOX 200

2.5 9-PIN SCANNER AUXILIARY SERIAL INTERFACE The scanner auxiliary serial interface available on the internal 9-pin connector can be used either for configuration through WinHost or for data monitoring. The details of the connector pins are indicated in the following table:

Figure 2.14 - 9-pin male connector

Pin 1 2 3 4 5 6 9

Name

9-pin connector pinout Function

RXA TXA SGND

N.C. Auxiliary RS232 Auxiliary RS232 N.C. Signal Ground N.C. N.C. DS2100 - DS2400

7

CTSA

Auxiliary Handshake RS232

8

RTSA

Auxiliary Handshake RS232

7

SGND AUX

Auxiliary Signal Ground

8

GND

Ground

DS4300 - DS4600

Installation - 15

Page 25

C-BOX 200

DATALOGIC

2.6 SCANNER REQUIREMENTS 1)

The C-BOX 200 can be connected to the following scanners through the 25-pin connector illustrated in Figure A. DS2100

DS4300

DS2400

DS4600

It is necessary to use RS232 model (X0XX) for DS2100 and DS2400 scanner, while DS4300 and DS4600 RS232 interface must be selected by the user. 2)

At least one Terminator Character should be enabled in the connected scanner (see the Terminator parameters in the Data Format section of the Help On Line).

3)

It is necessary to set the scanner main interface communication speed (Baud Rate), so that it is the same as the Multidrop bus speed. In fact, during the connection procedure, the C-BOX 200 gets its main interface speed from the scanner to initialize its RS485 Multidrop optocoupled serial interface. If both the baud rate and the device address are correct the communication takes place which causes the green LED to blink slightly.

The device address must be pre-set through the two rotary switches S4 and S5 (see Figure 2.10).

2.7 OPERATING MODES Once the connection procedure is completed (the warning LED is OFF), the C-BOX 200 is ready to receive code strings from the scanner's RS232 main interface. Then, it converts them to the RS485 multidrop network by using MUX32 protocol. Through the C-BOX 200 internal buttons, it is possible to communicate with the scanner to perform one of the following functions: •

Get scanner configuration

• Send a configuration to the scanner At the end of each function the scanner returns to the previous operating mode.

16 - Installation

Page 26

DATALOGIC

C-BOX 200

2.7.1 GET/SEND Buttons The C-BOX 200 has two internal function buttons (GET, SEND). The procedure to enable the GET/SEND function is the following: 1.

Press both the buttons GET and SEND at the same time for at least one second; the warning LED is turned ON.

2.

Release the buttons.

GET 3.

SEND

Press the left button corresponding to the GET function or press the right button corresponding to the SEND function.

GET –

(left button): the C-BOX 200 reads the current scanner configuration and permanently copies it in its own memory support (EEPROM). The C-BOX 200 preserves this configuration also when switched off.

SEND -

(right button): the C-BOX 200 sends the configuration previously stored in its own permanent memory support to the scanner’s EEPROM. NOTE Once the buttons are released in step 1, a ten-second timeout starts. If no button is pressed within this time, the procedure will be cancelled. In any case, the warning LED is turned OFF at the end of each procedure.

Installation - 17

Page 27

C-BOX 200

DATALOGIC

2.7.2 LED Indicators

Power on Warning

Tx

Figure 2.15 - LED Indicators

The three internal LEDs of the C-BOX 200 (see Figure 2.15) indicate the following: POWER ON

(red) indicates the C-BOX 200 is connected to the power supply and the power switch is ON.

WARNING

(red) indicates a warning or error condition: it is ON when a connection procedure is in progress (the system is busy) or during a GET/SEND procedure. It blinks when an error condition occurs. Normally this LED should be OFF.

TX

(green) indicates the RS485 Multidrop activity. When communication takes place, this LED will blink slightly.

18 - Installation

Page 28

DATALOGIC

C-BOX 200

3 TECHNICAL FEATURES ELECTRICAL FEATURES Power Supply voltage

10 to 30 Vdc

Power consumption max.

1.4 W + scanner

USER INTERFACE LED indicators

Power ON, Warning, Tx (RS485 Multidrop activity)

PHYSICAL FEATURES Mechanical dimensions Weight

167 x 115 x 40 mm (6.57 x 4.53 x 1.57 in.) about 340 g. (12 oz.)

SOFTWARE FEATURES Parameter storage

Non-volatile internal memory

ENVIRONMENTAL FEATURES Operating temperature

-10 to 50 °C (14 to 122 °F)

Storage temperature

-20 to 70 °C (-4 to 158 °F)

Humidity max. Vibration resistance

90% non condensing IEC 68-2-6 test FC 1.5 mm; 10 to 55 Hz; 2 hours on each axis

Shock resistance

IEC 68-2-27 test EA 30G; 11 ms; 3 shocks on each axis

Protection class

IP64 (when correctly connected to the scanner) NOTE The features given are typical at a 25 °C ambient temperature (if not otherwise indicated).

Technical Features - 19