Total Access 1500 FT1 DP: Total Access 1500 Fractional T1 Data Port Installation and Maintenance, pages 10 to 18
Pages 10 to 18 of 18
The original document is the PDF (145 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Adtran TA-1500
Page 10
The Performance History Screen is illustrated in Figure 5.
Slot:
4
The FT1 DP Loopback Options Screen is illustrated in Figure 6. Loopbacks can be evoked or terminated using this Screen. A status of current loopback conditions is also provided.
TOTAL ACCESS SYSTEM 1500
10/05/01 10:10
Fractional T1 Performance History ***** 24 Hour Registers ***** ES SES UAS Current: 23 2 0 -1: 0 0 0 -2: 0 0 0 -3: 0 0 0 -4: 0 0 0 -5: 0 0 15 -6: N/A N/A N/A -7: N/A N/A N/A
***** 15 Minute Registers ***** ES SES UAS ES SES UAS Current: 0 0 0 -1: 0 0 0 -17: 0 0 0 -2: 0 0 0 -18: 0 0 0 -3: 0 0 0 -19: 0 0 0 -4: 0 0 0 -20: 0 0 0 -5: 0 0 0 -21: 0 0 0 -6: 0 0 0 -22: 0 0 0 -7: 0 0 0 -23: 0 0 0 -8: 0 0 0 -24: 0 0 0 -9: 4 0 0 -25: 0 0 0 -10: 19 2 0 -26: 0 0 0 -11: 0 0 0 -27: 0 0 0 -12: 0 0 0 -28: 0 0 0 1. LOCATION: FT1-DP DSL Rx -13: 0 0 0 -29: 0 0 0 2. CLEAR PM REGISTERS -14: 0 0 0 -30: 0 0 0 -15: 0 0 0 -31: 0 0 0 Selection: -16: 0 0 0 -32: 0 0 0 ‘?’ - System Help Screen
Figure 5. Performance History Screen
Slot:
4
TOTAL ACCESS SYSTEM 1500
10/05/01 10:12
Fractional T1 Loopback Options 1. 2. 3. 4.
Loopback to NETWORK at FT1-DP: Loopback to CUSTOMER at FT1-DP: Loopback to NETWORK at FNID: Loopback to CUSTOMER at FNID:
ACTIVE Unavailable Unavailable INACTIVE
Note: Several seconds are required to establish or clear a loopback.
Selection:
‘?’ - System Help Screen
Figure 6. Loopback Options Screen 10
Section 61180405L1-5, Issue 1
61180405L1-5A
Page 11
Figure 7 shows the Provisioning Options Screen. Provisioning changes can only be implemented through the FT1 DP.
Slot:
4
TOTAL ACCESS SYSTEM 1500
10/05/01 10:07
Fractional T1 Provisioning
1. 2. 3. 4. 5.
Number of DS0s: Line Code: Framing: Latching Loopback: Latching Loopback Timeout:
6.
Hardware A/B Signaling: 1 2 3 4 5 6 Off Off Off Off Off Off
6 (384kbps) B8ZS ESF Disabled 20 minutes
Selection:
‘?’ - System Help Screen
Figure 7. Provisioning Options Screen
61180405L1-5A
Section 61180405L1-5, Issue 1
11
Page 12
6. DSL DEPLOYMENT GUIDELINES The ADTRAN FT1 DSL system is designed to provide Fractional DS1 based services over loops designed to comply with Carrier Service Area (CSA) guidelines. CSA deployment guidelines are given below. 1. All loops are non-loaded only. 2. For loops with 26-AWG cable, the maximum loop length including bridged tap lengths is 9 kft. 3. For loops with 24-AWG cable, the maximum loop length including bridged tap lengths is 12 kft. 4. Any single bridged tap is limited to 2 kft. 5. Total bridged tap length is limited to 2.5 kft. 6. The total length of multi-gauge cable containing 26-AWG cable must not exceed 12 - {(3*L26)/9} - LBTAP (in kft) = Total length of 26-AWG cable excluding bridged taps (in kft) LBTAP = Total length of all bridged taps (in kft) L26
This deployment criteria is summarized in the chart shown in Figure 8.
WORKING LENGTH OF 24 GAUGE (OR COARSER) CABLE (KFT)
12 11
Recommended maximum local loop loss information for PIC cable at 70°F, 135 Ω resistive termination, is provided in Table 5. An approximation for the maximum amount of wideband noise on a DSL local loop as measured by a 50 kbps filter is ≤ 31 dBrn. An approximation for the maximum level of impulse noise as measured using a 50 kbps filter on a DSL loop is ≤ 50 dBrn. NOTE These approximations are to be used as guidelines only and may vary slightly on different loops. Adhering to the guidelines should produce performance in excess of 10-7 BER.
Table 5. Loop Insertion Loss Data Frequency (Hz)
Maximum Loss (dB)
3000 .................................... 12.0 10,000 .................................... 15.0 50,000 .................................... 25.5 100,000 .................................... 30.0 150,000 .................................... 32.75 200,000 .................................... 35.25
INVALID DSL CABLE LENGTHS
10
7. MAINTENANCE The ADTRAN FT1 DP does not require routine maintenance for normal operation. In case of equipment malfunction, use the features supplied with the FT1 DP to help locate the source of the problem.
TOTAL BRIDGED 2.5 TAP 2.0 1.5 LENGTH 1.0 (KFT) 0.5 0.0
9 8 7
ADTRAN does not recommend that repairs be performed in the field. Repair services may be obtained by returning the defective unit to ADTRAN Customer and Product Support (CAPS).
6 5 4 3 2 VALID DSL CABLE LENGTHS 1 0 0
1
2
3
4
5
6
7
8
9
WORKING LENGTH OF 26 GAUGE CABLE (KFT)
Figure 8. DSL Deployment Guidelines
12
Section 61180405L1-5, Issue 1
61180405L1-5A
Page 13
8. TROUBLESHOOTING PROCEDURES Use Table 6 to troubleshoot the FT1 DP. 9. PRODUCT SPECIFICATIONS Specifications for the FT1 DP are provided in Table 7. 10. WARRANTY AND CUSTOMER SERVICE ADTRAN will replace or repair this product within ten (10) years from the date of shipment if it does not meet its published specifications or fails while in service. Refer to ADTRAN U.S. and Canada Carrier Networks Equipment Warranty, document 60000087-10. Contact Customer and Product Service (CAPS) prior to returning equipment to ADTRAN. For service, CAPS requests, or further information, contact one of the following numbers:
ADTRAN Sales Pricing/Availability (800) 827-0807 ADTRAN Technical Support Pre-sales Applications/Post-sales Technical Assistance (800) 726-8663 Standard hours: Monday-Friday, 7 a.m. - 7 p.m. CST Emergency hours: 7 days/week, 24 hours/day ADTRAN Repair/CAPS Return for Repair/Upgrade (256) 963-8722 Repair and Return Address ADTRAN, Inc. CAPS Department 901 Explorer Boulevard Huntsville, Alabama 35806-2807
Table 6. Troubleshooting Guide Condition
Solution
All front panel indicators are OFF.
1.
Verify that the FT1 DP is properly seated in the shelf.
2.
Make sure power supply feeding the FT1 DP is good.
3.
If 1 and 2 pass, replace the FT1 DP.
1.
Verify that the loop conforms with CSA guidelines (not too long, etc.).
2.
Verify that the Loop Loss at 200 kHz is not greater than 36 dB.
3.
Verify that noise on the DSL Loop is within acceptable limits.
4.
If steps 1 - 3 pass and Loop Sync is still not available, replace the unit with an FT1 DP unit known to be in good working condition.
Power OK but does not achieve Loop Sync (DSL LED is Red).
61180405L1-5A
Section 61180405L1-5, Issue 1
13
Page 14
Table 7. FT1 DP Unit Specifications Loop Interface Modulation Type .................................. 2B1Q Mode ..................................................... Full Duplex, Echo Cancelling Number of Pairs ................................... One Bit Rate ................................................. 784 kbps Baud Rate ............................................. 392K baud Service Range ...................................... Defined by Carrier Service Area Guidelines Loop Loss ............................................. 36 dB maximum @ 200 kHz Bridged Taps ........................................ Single taps < 2 kft, total taps < 2.5 kft Performance ......................................... Compliant with Bellcore TA-NWT-001210 Return Loss .......................................... 20 dB (40 kHz to 200 kHz) DSL Tx Signal Level ........................... 13.5 dBm Input Impedance ................................... 135 Ω Return Loss .......................................... 20 dB (40 kHz to 200 kHz)
DS1 Facility Interface Fully compatible with D4 channel bank equipment
Power Total Power .......................................... -48 VDC @ 125 mA with FNID -48 VDC @ 215 mA with FNID and FT1 Repeater -48 VDC @ 300 mA with a locally-powered FNID and two FT1 Repeaters FT1 DP Power Dissipation .................. 3.7 W with FNID 5.2 W with FNID and FT1 Repeater 6.1 W with a locally-powered FNID and two FT1 Repeaters Span Power ........................................... -190 VDC nominal for voltage and current limit at 125 mA ±5% (internally generated)
Clock Sources Clock Sources ...................................... Internal, DS1 Derived Internal Clock Accuracy ...................... ±25 ppm, (exceeds Stratum 4). Meets T1.101 timing requirements.
Tests Diagnostics ........................................... Self-Test, Local Loopback (FT1 DP), Remote Loopback (FNID)
Mechanical Dimensions ........................................... 3.0 in. High, 1.25 in. Wide, 9.5 in. Deep, nominal Plugs into Total Access 1500
Environment Temperature ......................................... Operating (Standard) .... -40°C to +70°C Storage .......................... -40°C to +85°C Relative Humidity ................................ Up to 95 percent noncondensing
Part Number ................................... 1180405L1
14
Section 61180405L1-5, Issue 1
61180405L1-5A
Page 15
Appendix A FT1 Loopbacks There are two loopbacks available to the FT1 DP: • FT1 DP network loopback loops the FT1 signal back to the network. • FT1 DP CPE loopback loops the FT1 signal back to the customer.
1. GENERAL
This Appendix is an overall reference to the loopback capabilities of the ADTRAN Fractional T1 system. Included in this Appendix are descriptions of the FT1 loopbacks and the methods for activating the FT1 loopbacks.
The FT1 DP network loopback is a digital loopback toward the CO (see Figure A-2). This loopback is initiated by the OCU DP latching loopback command (N1010101) or by the Total Access 1500 craft interface. The OCU DP latching loopback code is detected in the primary DS0 of the FT1 circuit (the channel where the FT1 DP is physically installed) to control the FT1 circuit looping. When the FT1 circuit is looped, all DS0s in use will be looped back toward the network. AIS will be sent to the customer.
2. FT1 LOOPBACKS
Figure A-1 shows the application from the central office (CO) to customer premises. The FT1 Repeater is shown for convenience and not as a necessary part of the FT1 network. The loopbacks shown are as follows: A. FT1 DP network loopback B. FT1 DP CPE loopback C. FT1 Repeater #1 network loopback D. FT1 Repeater #1 customer loopback E. FT1 Repeater #2 network loopback F. FT1 Repeater #2 customer loopback G. FNID network loopback H. FNID CPE loopback
DSX-1 Interface
FT1 Repeater #1
FT1 DP
The FT1 DP CPE loopback is a digital loopback toward customer premises as shown in Figure A-3. This loopback is initiated by the REM LBK button on the FNID, or by the Total Access 1500 craft interface. When the FT1 circuit is looped, all DS0s in use will be looped back toward the customer. All DS0s will be transmitted on to the network.
FT1 Repeater #2
FNID T1 NIU
Central Office
A
D4 Channel Bank
B
C
D
E
F
Customer Premises Equipment
H
G
Figure A-1. FT1 Loopbacks DSX-1 Interface Central Office
FT1 DP
HDSL
DS1 Interface FNID
Local Loop
Customer Premises
D4 Channel Bank
Figure A-2. FT1 DP Network Loopback DSX-1 Interface
Central Office
FT1 DP
HDSL
DS1 Interface FNID
Local Loop D4 Channel Bank
Customer Premises
Figure A-3. FT1 DP CPE Loopback
61180405L1-5A
Section 61180405L1-5, Issue 1
A-1
Page 16
The FT1 Repeater CPE loopback is a digital loopback toward customer premises as shown in Figure A-4. This loopback is initiated by the Total Access 1500 craft interface, when available. When the FT1 circuit is looped, all DS0s in use will be looped back toward the customer. The DS0s will be transmitted toward the network.
There are two loopbacks available to the FT1 Repeater: • FT1 Repeater network loopback loops the FT1 signal back toward the network. • FT1 Repeater CPE loopback loops the FT1 signal back toward the customer. The FT1 Repeater Network loopback is a digital loopback toward the CO as shown in Figure A-4. The loopback is initiated by the DDS latching loopback code NEI Loopback 1 for repeater #1 or NEI Loopback 2 for repeater #2 (N1000001). The NEI #1 or NEI #2 latching loopbacks are detected in the primary DS0 of the FT1 circuit, the channel where the FT1 DP is physically installed, to control the looping of the FT1 circuit. When the FT1 circuit is looped, all DS0s in use will be looped back toward the network. AIS will be sent to the customer.
There are two loopbacks available to the FNID: • FNID network loopback loops the FT1 signal back toward the network: • FNID CPE loopback loops the FT1 signal back toward the customer. The FNID network loopback is a digital loopback toward the CO as illustrated in Figure A-5. This loopback is initiated by the DDS latching loopback code for NEI Loopback 1 (N1000001) for a non-repeatered loop and for a repeatered loop or by the craft interface. HDSL
DSX-1 Interface
Central Office
FT1 Repeater #1 or #2
FT1 DP
DS1 Interface FNID Customer Premises
D4 Channel Bank
Local Loop
Figure A-4. FT1 Repeater Network and CPE Loopbacks
DSX-1 Interface
HDSL
FNID
DS1 Interface
FT1 DP Central Office
Local Loop
Customer Premises
D4 Channel Bank
Figure A-5. FNID Network Loopback
DSX-1 Interface
FNID HDSL
DS1 Interface
FT1 DP Central Office
Local Loop D4 Channel Bank
Customer Premises
Figure A-6. FNID CPE Loopback
A-2
Section 61180405L1-5, Issue 1
61180405L1-5A
Page 17
The NEI latching loopback is detected in the primary DS0 of the FT1 circuit to control the looping of the FT1 circuit. When the FT1 circuit is looped, all DS0s in use will be looped back toward the network. AIS will be sent to the customer. The FNID CPE loopback is a digital loopback toward customer premises as shown in Figure A-6. This loopback is initiated by the Total Access 1500 craft interface, when available. When the FT1 circuit is looped, all DS0s in use will be looped back toward the customer. The DS0s will be transmitted toward the network. 3. LOOPBACK ACTIVATION/DEACTIVATION
This section describes loopback activation and deactivation methods for the ADTRAN Fractional T1 system. Loopback activation and deactivation is controlled with the pushbutton located on the front panel, through craft interface, or latching loopback codes.
The craft interface on the FNID can activate and deactivate the FNID network loopback and the FNID CPE loopback. The FNID craft interface can also remotely activate and deactivate the FT1 DP network loopback and the FT1 DP CPE loopback and the repeat loopback. FT1 DP, FT1 Repeater, and FNID network loopbacks can be activated by the DDS latching loopback sequence. The latching loopback sequence is detected in the primary DS0 of the FT1 system. When the loopback is activated on the device, the whole FT1 bandwidth is looped. The FT1 DP, FT1 Repeater, and FNID each respond to a different loopback select code allowing for sectionalization of the network during testing. Table A-1 is a list of FT1 devices and their loopback select codes. Latching loopbacks for the FT1 system are activated by transmitting the following latching loopback sequence in the primary DS0 of the FT1 system:
The FNID front panel REM LBK pushbutton controls remote loopback activation. Pressing REM LBK activates FT1 DP CPE loopback. Remote loopback is deactivated by again pressing the REM LBK or waiting for the 20-minute loopback time out, if enabled. The FNID has a craft interface located on the front panel of the device. The FT1 DP is controlled by the craft interface on the Total Access 1500. The craft interface allows access to the FT1 device through an RS-232-type interface. All loopbacks for the FT1 DP and FNID can be controlled from the craft interface. The Total Access 1500 craft interface can activate and deactivate the FT1 DP network loopback and the FT1 DP CPE loopback in the FT1 DP. The Total Access 1500 craft interface can also remotely activate and deactivate the FNID network loopback, FNID CPE loopback, and the repeater loopbacks.
A. Minimum of 35 transition in progress (TIP) bytes (N0111010). B. Minimum of 35 loopback select code (LSC) bytes as defined in Table A-1. C. Minimum of 100 loopback enable (LBE) bytes (N1010110). D. Minimum of 35 all 1s bytes (S1111111), plus a minimum of 100 LBE bytes. (N-1) iterations, where N is the number of channel units of the same type (i.e., same LSC) that lie between the test center and the loopback to be operated. This step is only used when there are identical channel units in tandem. E. Minimum of 32 far end voice (FEV) bytes (N1011010).
Table A-1. FT1 Loopback Select Codes FT1 Device
Loopback Select Code Name
Loopback Select Code Byte
FT1 DP ............................................................... DDS OCU DP .......................................................... N1010101 FT1 Repeater #1 ................................................. NEI Loopback 1 ...................................................... N1000001 FT1 Repeater #2 ................................................. NEI Loopback 2 ...................................................... N1000001 FNID without Repeater ...................................... NEI Loopback 1 ...................................................... N1000001 FNID with one Repeater .................................... NEI Loopback 2 ...................................................... N1000001
61180405L1-5A
Section 61180405L1-5, Issue 1
A-3
Page 18
A 25-second watchdog timer is activated between the 35 TIP bytes and 35 LSC bytes, between the 35 LSC bytes and 100 LBE bytes, and between the 100 LBE bytes and 32 FEV bytes. The timer requires the correct receipt of the latter sequences less than 25 seconds after receipt of the prior sequence. This prevents inadvertent setting of the latching loopbacks. Latching loopbacks for the FT1 system are deactivated by transmitting the following latching loopback sequence in the primary DS0 of the FT1 system: Minimum of 35 TIP bytes (N0111010). 4. LOOP UP STATE
In the loop up state, the active FT1 loopback will provide a continuous loop for the FT1 bandwidth. The data flow is continuously monitored for the loop deactivation commands to deactivate the loopbacks. Also, a 20-minute loopback time out is checked. If the loopback time out is enabled, any loopback that is in the loop up state for 20 minutes will be deactivated.
A-4