Sick CDB420 Spec Sheet
Spec sheet4 pagesPDF 497 KB
All 4 pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
The SICK operating instructions for the CDB420 connection module, in German and English, covering the CDB420-001, CDB420-101 and CDB420-201. The module links one SICK 1D/2D code reader to a host, a CAN scanner network, sensors and power. It explains the configuration switches and LEDs, wiring, technical data and troubleshooting.
- Device
- Compact connection module linking one SICK 1D/2D code reader to host, CAN scanner network, peripherals and power p. 1
- Supported readers
- Bar code scanners CLV 42x to 45x and CLV480; image code readers ICR 84x-2 and ICR85x-2 p. 1
- Power supply
- 10 to 30 V DC, SELV or PELV; max. 16 W with a scanner connected p. 3
- Connections
- 15-pin HD D-Sub socket for the reader; internal 9-pin D-Sub "AUX" (RS 232) for a PC; screw and spring terminals p. 1, 3
- Fuse
- Glass tube fuse 0.8 A, type T p. 3
- Enclosure
- Polycarbonate housing, IP 65 (with the SICK standard scanner cable) p. 3
- Weight
- Approx. 250 g (approx. 8.75 oz) p. 3
- Temperature
- 0 to +40 °C operating; –20 to +70 °C storage p. 3
- Variants
- CDB420-001 (No. 1023885), CDB420-101 (No. 1024305), CDB420-201 (No. 1027094) p. 3
- CAN bus on M12
- CDB420-101: CAN bus also on a 5-pin M12 plug and a 5-pin M12 socket on the front p. 1, 3
- Cable glands
- For cables 4.5 to 10 mm; CDB420-001: 4, -101: 2, -201: 5 p. 3
- Cloning module
- Optional CMC400 stores the reader's configuration parameters externally p. 1
- Indicators
- 5 LEDs: Power, Sensor 1 and 2, Result 1 and 2 p. 2, 3
- Humidity
- Max. 90%, non-condensing p. 3
What this sheet walks you through
- Mounting the module and parking the removed cover p. 2
- Setting the configuration switches S 1 to S 7 p. 2
- Reading the Power, Sensor and Result LEDs p. 2
- Wiring the reader, host, CAN bus and sensors p. 3
- Terminating the CAN bus at the end of the line p. 3
- Activating the host or CAN driver in the reader with CLV-Setup p. 3
- Troubleshooting power, reading clock sensor and PC access problems p. 4
- Building a SICK CAN scanner network and the M12 pin assignment p. 4
Good to know
- Cable between the CDB420 and the code reader, with extension cables, is limited to 10 m (32.8 ft) because of RS 232. p. 1
- Connect or release wiring only with the power off. p. 2
- The power supply output must be isolated from its input by double insulation and a safety isolating transformer to IEC 742. p. 2
- Close unused cable glands with blanking plugs to keep IP 65. p. 3
- Keep the internal AUX connector reachable for configuring and diagnosing the reader. p. 1
Questions this sheet answers
Which SICK scanners work with the CDB420?
The CLV 42x to 45x and CLV480 bar code scanners and the ICR 84x-2 and ICR85x-2 image code readers. p. 1
How do I connect a PC to a scanner through the CDB420?
Connect the PC to the AUX connector in the CDB420 with a 3-core RS 232 null modem cable and use CLV-Setup. p. 3
Why does the CDB420 Power LED stay off with power connected?
Switch S 1 (Power) must be set to ON. p. 4
CLV-Setup cannot reach the scanner through the CDB420 AUX port. What should I check?
If no CMC400 is fitted, set switch S 4 to NO, and let the AutoBaudDetect function in CLV-Setup set the PC communication parameters. p. 4
What is the difference between the CDB420-001 and CDB420-101?
The CDB420-101 adds M12 plug and socket connectors for the CAN bus and has 2 cable glands instead of 4. p. 3
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
.. .. .. .. .CDB4201D/2D Code ReaderCDB420“Aux““CAN“ “Host“
Lichtschranke (Lesetakt)
“Result 1“ “Result 2“
Photo reflex switch (Reading clock)
“Sensor 1“
Schalter/switch Teach-in matchcode
PC
CAN bus HOST SPS/PLC SPS/PLC
10 ... 30 V DC
“Sensor 2“
Anschlussmodul Connection Module Betriebsanleitung
O p e r a t i n g
I n s t ru c t i o n s
1. Produkteigenschaften
1. Features
Kleines Anschlussmodul zum Anschluss eines SICK 1D/2DCodelesers an Host, CAN-Scanner-Netzwerk, Peripherie und Stromversorgung
- Unterstützte 1D/2D-Codeleser: Barcodescanner CLV 42 x . . .45 x , CLV480, CLV /X 4 9 0, Image Code Reader I C R 84x -2, ICR85x-2
- Basisgerät zur optionalen Aufnahme eines Cloning-Moduls CMC400 für externe Speicherung der Konfigurationsparameter des 1D/2D-Codelesers
- 9-pol. D-Sub-Stecker intern, für Anschluss der seriellen AuxSchnittstelle (RS-232) an PC zur Konfiguration/Diagnose des 1D/2D-Codelesers
- Klemmen für Host-Schnittstelle, CAN-Bus, Schaltein- und -ausgänge, Stromversorgung (Variante CDB420-101: CAN-Bus über 2 x M12-Steckverbindung an Frontseite, siehe Seite 4)
- Von außen sichtbar: LEDs zur Anzeige von aktiven Schaltein- und ausgängen sowie Schalterstellungen der Modulkonfiguration
- Schutzart IP 65
- Montierbar bei geschlossenem Deckel
- Wartungsfrei
- UL-zertifiziert bei Verwendung eines Class 2-Netzgeräts (geprüft nach UL 1310) zur Stromversorgung
Weitere Produktinformationen, Programm „CLV-Connect“:
Further Product Information, ”CLV-Connect” PC Program:
¾ Siehe www.sick.com
¾ See www.sick.com
EG-Konformitätserklärung:
- EC Conformity Declaration
- ¾ Auf Anforderung
¾ On request
2. Voraussetzungen zur Installation und Inbetriebnahme
2. Installation and Commissioning Requirements
Anschlusspläne in CLV-Connect (auf CD-ROM „Manuals & Software Bar Code Scanners“, die dem 1D/2D-Codeleser beiliegt, oder via Internet unter www.sick.com)
- Versorgungsspannung DC 24 V, erzeugt nach IEC 742
3. Montage3. Installation■
Stets freier Zugang zum internen Stecker „AUX“ erforderlich für Zugriff auf 1D/2D-Codeleser (Konfiguration/Diagnose)
- Maximale Leitungslänge zwischen CDB420 und 1D/2D-Codeleser beim Einsatz von Verlängerungsleitungen: 10 m (RS-232Schnittstelle!)
8010001/S012/2009-10
© SICK AG · Division Auto Ident · Germany · All rights reserved
Compact connection module for connecting one SICK 1D/2D code reader to the host, CAN scanner network, peripheral equipment, and power supply.
- Supported 1D/2D code reader: bar code scanner CLV 42x to 45x, CLV480, CLV /X 4 9 0 or image code reader I C R 8 4x-2, ICR85x-2.
- Basis device for CMC400 cloning module integration (optional) for external saving the 1D/2D code reader’s parameters.
- 9-pin internal D-Sub connector, for connecting the serial Aux interface (RS 232) to a PC for configuring/diagnosing the 1D/2D code reader.
- Terminals for host interface, CAN bus, switching inputs/outputs, and power supply (CDB420-101 variant: CAN bus via 2 x M12 connectors on front, see also page 4).
- Externally visible LEDs for displaying active switching inputs and outputs, as well as switch settings for module configuration.
- Enclosure rating IP 65.
- Installation possible with closed cover.
- Maintenance-free.
- UL certificated when a class 2 power supply according to UL 1310 is used.
Connection diagrams in CLV-Connect (on the “Manuals & Software Bar Code Scanners“ CD-ROM, provided with the 1D/2D code reader or from the Internet: www.sick.com)
- 24 V DC power supply generated in accordance with IEC 742
Permanent access to internal “AUX” connector is required for access to scanner (configuration/diagnosis)
- Maximum cable length between CDB420 and 1D/2D code reader if extension cables are used: 10 m (32.8 ft) because of RS 232 interface.
1#4
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
Abgenommener Deckel mit Anschlussbild um 180° gedreht in Parkposition arretierbar
Cover with connection diagram can be removed, rotated through 180°, and locked in park position
¾ Bohrungs- und Gehäusemaße siehe Maßbild (Seite 4), max. Schraubendurchmesser 4 mm. ¾ Einbau und Inbetriebnahme des optionalen CMC400 siehe Betriebsanleitung CMC400 (Nr. 8010002).
¾ See dimensioned drawing (Page 4) for hole and housing dimensions, max. screw diameter 4 mm (0.15 in). ¾ For installing and commissioning the optional CMC400, see CMC400 Operating Instructions (no. 8010002).
4. Konfigurationselemente und Anzeigen
4. Configuration Elements and Displays
Funktion der Konfigurationsschalter:
- Configuration Switches
- Schalter
FunktionDefaultSwitchFunctionDefaultS 1 (Power)
Anliegende Versorgungsspannung: ON: Versorgungsspannung ein OFF: Versorgungsspannung aus
ON
S 1 (Power)
Power supply: ON: Power supply on OFF: Power supply off
ON
S 2 (CAN-Term)
Terminierung des CAN-Busses: ON: Widerstand 120 Ohm zugeschaltet OFF: keine Terminierung
OFF
S 2 (CAN-Term)
CAN bus termination: ON: 120 Ohm resistor connected OFF: No termination
OFF
S 3 (SGND-GND) Bezugspotenzial für Sensor-GND: ON: verbunden mit GND des 1D/2DCodelesers OFF: potenzialfrei
ON
S 3 (SGND-GND)
Reference potential for sensor GND: ON: Connected to 1D/2D code reader GND OFF: Floating
ON
S 4 (CMC)
Integration des CMC400: „YES“: CMC in Leitung der Aux-Schnittstelle des 1D/2D-Codelesers geschaltet „NO“: kein CMC400 gesteckt
NO
S 4 (CMC)
CMC400 integration: “YES”: CMC400 connected to Aux interface of 1D/2D code reader “NO”: CMC400 not connected
NO
S 6 (RS-485)
RS-422/485-Umschaltung ON: RS-485 OFF: RS-422
OFF
S 6 (RS 485)
RS 422/485 selector ON: RS 485 OFF: RS 422
OFF
S 7 (Term422)
RS-422-Terminierung (Empfänger) ON: Widerstand 120 Ohm zugeschaltet OFF: keine Terminierung
OFF
S 7 (Term422)
RS 422 termination (receiver): ON: 120 Ohm resistor connected OFF: No termination
OFF
Funktion der LEDs:
- LEDs
- LED
FarbeFunktionLEDColorFunctionPowergrün
leuchtet, wenn die Versorgungsspannung am CDB420 anliegt und Schalter S 1 auf „ON“
Power
green
Lights up when the power supply is connected to the CDB420 and switch S 1 is set to “ON“
Sensor 1, 2
gelb
leuchtet, wenn der entsprechende Eingang des 1D/2D-Codelesers schaltet
Sensor 1, 2
yellow
Lights up when the corresponding 1D/2D code reader input switches
Result 1, 2
gelb
leuchtet, wenn der entsprechende Ausgang des 1D/2D-Codelesers schaltet
Result 1, 2
yellow
Lights up when the corresponding 1D/2D code reader output switches
5. Elektrische Installation
5. Electrical Installation
Empfohlene max. Leitungslänge vom 1D/2D-Codeleser zum Host:
Recommended max. cable length from 1D/2D code reader to host:
SchnittstellentypDatenübertragungsrateEntfernung z. HostInterface typeData transfer rateDistance to hostRS-232
bis 19,2 kBd 38,4 ... 57,6 kBd
max. 10 m max. 3 m
RS 232
Up to 19.2 kBd 38.4 to 57.6 kBd
Max. 10 m (32.8 ft) Max. 3 m (9.84 ft)
RS-422
max. 38,4 kBd max. 57,6 kBd
max. 1.200 m max. 500 m
RS 422
Max. 38.4 kBd Max. 57.6 kBd
Max. 1,200 m (3,936 ft) Max. 500 m (1,640 ft)
Versorgungsspannung DC 10 .. 30 V:
- Power supply 10 to 30 V DC
- HINWEIS
NOTICE
Elektrische Trennung! Der Ausgangskreis des kundenseitigen Netzgerätes zur Erzeugung der Versorgungspannung muss gegenüber dem Eingangskreis eine sichere elektrische Trennung durch Doppelisolation und Sicherheitstrafo nach IEC 742 besitzen.
Electrical isolation! The output circuit of the power supply pack provided by the customer must be safely electrically isolated from the input circuit by means of double insulation and a safety isolating transformer according to IEC 742.
Verdrahtung des CDB420:
- CDB420 wiring
- Elektrische Verbindungen nur im spannungsfreien Zustand herstellen oder lösen. ■ Um den Kurzschluss-/Überlastungschutz der abgehenden Versorgungsleitungen sicherzustellen, müssen die verwendeten
2#4
© SICK AG · Division Auto Ident · Germany · All rights reserved
Connect or release current linkages only under de-energised conditions.
- To ensure that the outgoing supply cables are protected against short-circuits/overload, the core cross-sections must be 8010001/S012/2009-10
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
Aderquerschnitte unter Berücksichtigung der im CDB420 eingebauten Sicherung ausgelegt werden. Folgende Normen sind hierbei zu beachten: DIN VDE 0100 (Teil 430), DIN VDE 0298 (Teil 4) bzw. DIN VDE 0891 (Teil 1)
- Kundenseitige Schirmung am CDB420 auflegen (Kl. „Shield“)
- Klemmenbelegung siehe Anschlussbild auf Seite 4 u. im Deckel. Anschlusspläne für Host-Schnittstelle/CAN-Schnittstelle/Schaltein- und -ausgänge siehe CLV-Connect
- Um Störeinflüsse zu vermeiden, Leitungen möglichst nicht parallel zu Stromversorgungs- und Motorleitungen verlegen
- Bezugspotenzial für die Schalteingänge mit Schalter S 3 wählen
- Integration in CAN-Scanner-Netzwerk: siehe Betriebsanleitung „Anwendung der CAN-Schnittstelle“ (Nr. 8008179, dt. Ausgabe)
dimensioned in accordance with the fuse installed in the CDB420. The valid standards must be observed.
- Connect the shield of your system to the CDB420 („Shield“ terminal)
- For terminal assignment, see connection diagram on Page 4 or inside the cover. For host/CAN interface/ switching inputs/ outputs diagrams, see CLV-Connect
- To prevent interference, do not lay cables parallel to power supply or motor cables
- Choose reference potential for switching inputs with switch S 3
- Integration in CAN scanner network: see operating instructions “Using the CAN Interface” (No. 8008180, English)
1. Leitung des 1D/2D-Codeleser an 15-pol. D-Sub-HD-Buchse des CDB420 anschließen. 2. Alle anderen Leitungen über Kabel-Verschraubungen an den Klemmen des CDB420 auflegen. Um die Schutzart IP 65 zu erhalten, nicht verwendete Verschraubungen mit Blindstopfen versehen. 3. CAN-Bus: Falls CDB420 am Busende, Terminierungswiderstand mit Schalter S 2 zuschalten. 4. Mit PC-Programm „CLV-Setup“ Treiber für verdrahtete Host-/CANSchnittstelle im 1D/2D-Codeleser aktivieren. Hierzu PC mit 3-adriger RS-232-Datenleitung (Nullmodemleitung) an Stecker „AUX“ im CDB420 anschließen.
1. Connect the 1D/2D code reader cable to the 15-pin D-Sub HD socket on the CDB420. 2. Connect all other cables to the terminals provided using cable glands. To remain enclosure rating IP 65, use blanking plugs to close any unused cable glands. 3. CAN bus: If CDB420 is integrated at bus end, connect termin. resistor with switch S 2 4. Using the “CLV-Setup” program, activate the driver for the connected host/CAN interface in the 1D/2D code reader. To do so, connect the PC to the “AUX” connector on the CDB420 using a 3-core RS 232 data cable (null modem cable).
6. Technische Daten6. Technical DataTyp
CDB420-001 (Nr. 1023885) CDB420-101 (Nr. 1024305) CDB420-201 (Nr. 1027094)
Type
CDB420-001 (No. 1023885) CDB420-101 (No. 1024305) CDB420-201 (No. 1027094)
Optische Anzeigen5 x LEDVisual indicators5 x LEDsElektrische Anschlüsse
D-Sub: 15-pol. HD-Buchse/9-pol. Stecker (CDB420-101: zusätzlich 1 x 5-pol. M12Stecker/1 x 5-pol. M12-Buchse für CAN-Bus) Schraubklemmen, für Adern 0,14 ... 2,5 mm2 Federkraftklemmen, für Adern 0,14...1 mm2
Electrical connections
Kabel-Verschraubungen
(für Leitungen ∅ 4,5 ... 10 mm) CDB420-001: 4 x, CDB420-101: 2 x; CDB420-201: 5 x
D-Sub: 15-pin HD socket/9-pin plug (CDB420-101: additionally 1 x 5-pin M12 plug/1 x 5-pin M12 socket for CAN bus) Screw terminals, for cores 0.14 to 2.5 mm2 (approx. 26 to 13 AWG) Spring terminals, for cores 0.14 to 1 mm2 (approx. 26 to 17 AWG)
Cable glands
DC 10 ... 30 V, SELV bzw. PELV nach IEC 60364-4-41 (2005)
for cables ∅ 4.5 to 10 mm (0.18 to 0.39 in) CDB420-001: 4 x; -101: 2 x; -201: 5 x
Power supply1)
10 to 30 V DC, SELV respectively PELV according to IEC 60364-4-41 (2005)
Versorgungsspannung1)Leistungsaufnahme
bei angeschlossenem Scanner: max. 16 W
Sicherung
Glasrohrsicherung 0,8 A träge
Power consumption2)
With connected scanner: max. 16 W
Gehäuse / PrüfzeichenPolycarbonat / CE, ULFuse
Glass tube fuse 0.8 A, type T
Elektrische Sicherheit
nach EN 61010-1 (2001-03)
Housing / Conformity
Polycarbonate / CE, UL1)
Schutzklasse
III, nach EN 61140 (2002-03)
Electrical safety
According to EN 61010-1 (2001-03)
Schutzart
IP 653), nach EN 60529 (1991-10); A1 (2002-02)
Protection class
III, accord. to EN 61140 (2002-03)
Enclosure rating
nach EN 61000-6-2 (2001-10); EN 55011 (1998-05), A1 (1999-08)
IP 653), accord. to EN 60529 (1991-10); A1 (2002-02)
EMC tested
Schwing-/Schockprüfung
nach IEC 600068-2-27 (1993)/ nach 600068-2-6 (1995)
According to EN 61000-6-2 (2001-10); EN 55011 (1998-05), A1 (1999-08)
Vibration/shock testedGewichtca. 250 g
Accord. to IEC 600068-2-27 (1993)/ accord. to 600068-2-6 (1995)
2)EMV-Prüfung1)
Temperatur (Betrieb/Lager) 0 ... +40 °C/ –20 ... +70 °C
Weight
Approx. 250 g (approx. 8.75 oz)
Rel. Luftfeuchtigkeit
Temperature (operation/storage)
0 to +40 °C/ –20 to +70 °C (32 to +104 °F/ –4 to +158 °F)
Rel. air humidity
Max. 90%, non-condensing
max. 90 %, nicht kondensierend
1) UL-zertifiziert bei Verwendung eines Class 2-Netzgerätes (geprüft nach UL 1310) 2) abhängig vom Scanner-Typ 3) bei Verwendung der SICK-Scanner-Standardanschlussleitung
(gültig bei entsprechender Gerätekennzeichnung auf dem Typenschild)
8010001/S012/2009-10
1) UL certificated when a Class 2 power supply according to UL 1310 is used 2) Type specific 3) With SICK standard scanner cable
(valid only with corresponding product marking on the nameplate)
© SICK AG · Division Auto Ident · Germany · All rights reserved
3#4
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
SICK AG · Waldkirch · Germany · www.sick.com · 8010001/S012/2009-10 · 5M/TR <PM 6.5> · KE · Printed in Germany · Subject to change without prior notice · The specified product features and technical data do not represent any guarantee · Aftint34sw
7. Fehlersuche7. TroubleshoootingStörungAbhilfeMalfunctionRemedy
- Versorgungsspg. angeschlossen, aber LED „Power“ leuchtet nicht
- Schalter S 1 (Power) in Position „ON“ bringen
- “Power” LED does not light up when power supply is connected
- Set switch S 1 (Power) to “ON”
- Signale des angeschlossenen Lesetaktsensors bleiben wirkungslos
- Sensor gemäß CLV-Connect anschließen
- Stellung des Schalters S 3 prüfen (SGND–GND)
- Mit Hilfe von CLV-Setup die Quelle des Lesetaktes im 1D/2D-Codeleser auf „Sensor 1“ einstellen. Download zum 1D/2D-Codeleser!
- Signals from connected reading clock sensor have no effect
- Connect reading clock sensor in accordance with CLV-Connect
- Check switch S 3 (SGND–GND)
- Using CLV-Setup, set the reading clock source on the 1D/2D code reader to “Sensor 1”. Download to scanner
- Nach Anschluss des PCs an den Stecker „AUX“ kein Zugriff auf den 1D/2D-Codeleser mit CLVSetup
- Wenn kein CMC400 gesteckt, Schalter S 4 in Pos. „NO“ bringen
- Mit Hilfe der Funktion „AutoBaudDetect“ in CLV-Setup die Kommunikationsparameter des PC automatisch wählen
- Cannot access 1D/2D code reader with CLV-Setup after connecting the PC to the “AUX” connector
- If no CMC400 is connected, set switch S 4 to “NO”
- Using the “AutoBaudDetect” function in CLV-Setup to configure the PC communication parameters automatically
Aufbau, Klemmenbelegung/design, terminal assignment Konfigurationsschalter Configuration switches
LEDs
Steckplatz für CMC400 Plug-in slot for CMC400
Anschluss PC PC connection
Schema: Aufbau eines SICK CAN-Scanner-Netzwerks Diagram: Building a SICK CAN scanner network “Host“
Klemmenleisten Terminal strips
- CDB420-101
- 1D/2D Code Reader
CDB4201D/2D Code ReaderCDB4201D/2D Code ReaderCDB420“Result 1“ “Sensor 1“CAN bus
Anschluss 1D/2D-Codeleser 1D/2D code reader connection
Maßbild/dimensioned drawing
Pinbelegung M12-Steckverbindungen Pin assignment of M12 connectors (Buchse/socket)
CAN bus(Stecker/plug)CAN busPinSignal1Schirm/Shield2Vs3GND4CAN H5CAN LPinSignal1Schirm/Shield2Vs3GND4CAN H5
CAN L Alle Angaben in mm (inch)/All dimensions in mm (inch)
4#4
© SICK AG · Division Auto Ident · Germany · All rights reserved