The text of a manual · part 3 of 7

Video Multiplexer with Video Alarm Detection Installation and Operation Manual, pages 21 to 30

Pages 21 to 30 of 64

The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Sensormatic RV Duplex Multiplexer

Page 21

12

Video Multiplexer with Video Motion Detection

Alarm Hold Input

NOTE: The Alarm Hold Input is not normally used and is only provided for compatibility purposes. Alarm duration control is better managed by the multiplexer. See Alarm Recording Control for more details. The alarm hold input accepts a normally closed contact type or active high TTL/CMOS alarm signal. Connect alarms pin 36 to the alarm hold output of the VCR or other device. Connect the remaining side of the output to ground (post labeled gnd on back panel).

Alarm Output

The alarm output is a contact type signal between alarms pin 17 (common) and pin 18 (normally closed) or pin 19 (normally open). Connect the appropriate pins to the alarm input of the VCR or other device. See Appendix D – Technical Specifications for details.

Motion Alarm Outputs

The motion alarm outputs use a TTL/CMOS type signal. Connect each motion alarms pin (pins 20–35) to a TTL/CMOS compatible alarm input on the VCR or other device. Connect the remaining side of the output to ground (post labeled gnd on back panel). Motion alarm output polarity is menu selectable and defaults to active high.

Autodetect VCR Speed

Pin 37 connects to the VCR to get the timing signal (it may be named clock or trigger) so the multiplexer can switch to use the same recording speed as the VCR. If the VCR changes the recording speed, the multiplexer will automatically adjust the speed to match. Check your VCR manual to see if the VCR provides a timing signal.

Remote

The two RJ11 connectors are for the multiplexer remote control panel option or remote control commands.

Remote Control Panel Option

Connect the cable provided with the remote control panel to the remote in connector. If daisychaining to another multiplexer, connect the remote out of this multiplexer to the remote in of the next multiplexer in the chain. The remote control panel and the multiplexer front panel operate identically and may be used at the same time. See Remote Control Panel manual for details.

Page 22

Chapter 3, Installation

SYSTEM CHECKOUT

13

Multiplexer system operation can be checked immediately after installation with the multiplexer in the factory default state. While the multiplexer itself requires no adjustment, system components such as the monitor, cameras and video recorder should be checked for proper operation and adjustment. The system checkout procedure involves three steps: monitor calibration, camera check, and video recorder check. At least two video cameras are required to check system operation. Refer to Figure 1 – Basic Multiplexer System. Make certain that all required connections are in place. Apply power to all system equipment.

Monitor Calibration

This process involves adjusting monitor display brightness, contrast, hue and saturation based on the standard color bar pattern generated by the multiplexer. The procedure is as follows. 1.

Press Function+Zoom. The first setup menu appears over internally generated color bars (gray bars on B&W units).

2.

Turn off any automatic color control features on the monitor that might interfere with manual adjustment (except B&W units).

3.

Turn the monitor’s color level (saturation) control all the way down. The display is now black and white.

4.

Adjust the monitor’s contrast and brightness controls so that the bar pattern starts with white, darkens evenly through shades of gray and ends with black.

5.

Turn the monitor’s color level control to its midpoint (except B&W units).

6.

Adjust the monitor’s tint (hue) control until the colors are correct. The correct sequence of colors from left to right is white, yellow, cyan, green, magenta, red, blue and black.

7.

Press Function+Zoom to exit the setup menu system.

The main monitor is now correctly calibrated to the output of the multiplexer. To calibrate the call monitor, temporarily connect its video cable to the main mon output and perform monitor calibration again. While monitor adjustments can be changed to suit the viewer, the above procedure should be performed before attempting to adjust cameras or working on display or video quality problems.

Page 23

14

Video Multiplexer with Video Motion Detection

Camera Check

The multiplexer multicamera display capability makes checking camera performance as simple as comparing two pictures on one screen. This method is preferable to the direct camera to monitor technique because it allows precise adjustment of each camera against a chosen reference camera. This minimizes differences between cameras, and picture quality is optimized. NOTE: Before performing a camera check, complete the monitor calibration procedure described in the previous section. Adjusting camera picture quality is more effective on a monitor which is already calibrated. The camera check procedure is as follows: 1.

Complete the monitor calibration procedure.

2.

Connect all system cameras directly to the multiplexer camera inputs. Remove all connections to the looping (lower) camera outputs.

3.

Make sure that the multiplexer is set up for 75 ohm termination (the default state). The switches on the back panel should be down.

4.

Select the format (2x2, 3x3 or 4x4) which displays all of the attached cameras.

5.

Pick the best looking picture and use that camera as a reference. If necessary, adjust the camera for an optimum picture. Do NOT adjust the monitor.

6.

Adjust each remaining camera, in turn, for an optimum picture. Try to obtain the same picture quality as the reference camera.

The cameras are now correctly adjusted with respect to the calibrated monitor and each other. You may now adjust the monitor for the best overall display. If you choose to make further monitor adjustments, it is best to do so with all cameras displayed.

Page 24

Chapter 3, Installation

Making a Test Tape

15

The easiest way to verify multiplexer system operation is to make a test recording and play it back. This process effectively tests every piece of equipment in the system. Before proceeding with the test tape, it is recommended that you complete both the monitor calibration and camera check procedures. Make certain that the multiplexer monitor and all system cameras are correctly adjusted. Doing so will help to ensure the best results during the tape test. The tape test procedure is as follows: 1.

Place the VCR in the record mode at the 24-hour speed (this is the multiplexer default VCR record speed and can be changed). The VCR begins recording multiplexed camera video. You may select any viewing mode or display format while recording. Doing so will not affect the tape since camera recording and display are completely independent multiplexer functions.

2.

After several minutes, stop the VCR and rewind the tape.

3.

Place the VCR in the play mode.

4.

Press the Tape button on the multiplexer.

When the multiplexer detects the encoded VCR signal, it configures itself for tape playback and displays all recorded cameras in the multicamera format. To view one camera full screen, press the corresponding Camera (1–16) button. To view multiple cameras, press the desired display format (PIP, 2x2, 3x3 or 4x4) button. If the camera or cameras do not appear, check VCR operation and review all video connections. This completes the tape test. If it is not successful, repeat the steps outlined above. If you continue to have difficulties, turn to Appendix C – In Case of Trouble for assistance.

Page 25

16

Video Multiplexer with Video Motion Detection

Chapter 4, Setup SETUP MENU SYSTEM

The on-screen menus allow you to set up key features such as system time and date, day and night start times for motion detection, alarm message display, alarm message latch, video loss alarm, audible alarm, alarm input polarity, alarm output polarity, VCR record time, VCR alarm record time, alarm duration, global dwell time, camera titles, motion detection, and system security. All setup data is stored in nonvolatile memory where it is protected against loss due to power failure. NOTE: To perform multiplexer setup, you must first gain access to the on-screen menu system. Refer to Security Measures in the front of this manual. Once inside the menu system, multiplexer setup involves three basic operations: 1.

Selecting the menu.

2.

Positioning the flashing highlight.

3.

Setting the option.

Selecting a Menu

Press the Zoom button to go to the next setup menu. The next menu appears with the flashing highlight at the first option. If you press the Zoom at the last menu (SECURITY LOCK), the unit exits the setup mode and returns to normal operation.

Positioning the Highlight

Use the left and right arrow buttons to position the menu highlight. Press the right arrow to move the highlight to the next character or option. Press the left arrow to move the highlight to the previous character or option. When you reach one end of the menu, the highlight appears at the other.

Setting an Option

Press the up arrow or down arrow to scroll through the available settings or characters: 0–9 A–Z _(represents a space) / : = - + .(period) When you reach the first or last setting or character, the sequence begins again.

Page 26

Chapter 4, Setup

17

SETUP MENUS

There are eight menus in the setup menu system. The following paragraphs take you through the menu system step-by-step, describing each menu’s purpose and options.

Menu 1, System Time/Date

Menu 1 displays the system time and date (maintained by the multiplexer internal clock/calendar), the product firmware revision number and revision date. By default, the multiplexer displays the time and date at the top of the main monitor. In live mode, it displays the system (current) time and date. In tape mode, it displays the time and date of the recording (encoded on the tape). You can turn the time/date display off or on at any time by pressing Function+right arrow. To set the time and date, use the arrow buttons to position the flashing highlight over each character and set it. Enter the time in HH:MM:SS 24-hour format. Enter the date in MM/DD/YY format (DD.MM.YY format in the PAL version). The clock starts running when you move the highlight into the date field. NOTE: Be sure to turn off the VCR’s time/date display feature. If it is turned on, it may interfere with tape playback. Multicamera display during playback will have time and date over each image and at the top of the screen. If the time/date is too high on the screen, it overlaps the vertical interval. When finished, press the Zoom button to go to menu 2 or Function+Zoom to save all changes and leave the setup system.

Page 27

18

Video Multiplexer with Video Motion Detection

Menu 2, Day/Night Start Time

Menu 2 allows you to divide the multiplexer work day into two independent periods, based on start times. If the start times are the same, the day settings will be used for motion detection. Using different start times for day and night allows you to use different motion detection settings for each time span. Motion alarms (ALRM) can be set either ON or OFF, and SENSE, SIZE and DELAY settings can be different for each time as well. To set the day start time or night start time, use the arrow buttons to position the flashing highlight over each character and set it. Enter the time in HH:MM 24-hour format. In the example below: day is from 8 am to 5 pm, and night is from 5 pm to 8 am. DAY START TIME = 08:00 NIGHT START TIME = 17:00 NOTE: When day and night start times differ, you should set up both motion screens for each camera. When finished, press the Zoom button to go to menu 3 or Function+Zoom to save all changes and leave the menu system.

Menu 3, Toggle Options

Menu 3 allows you to set each menu item to one of two settings. To change a setting, position the highlight over it and press the up or down arrow. The alternate setting appears. To move to the next toggle option, press the right arrow; to go back to the previous toggle option, press the left arrow. The toggle options include the following:

Alarm Message Display

The ALARM MESSAGE DISPLAY option controls the ALARM or VIDLOSS graphic. It toggles as follows: ON – The multiplexer displays the ALARM or VIDLOSS graphic on both the main and call monitors. The multiplexer also switches to multicamera display on the main monitor to show all cameras with alarms. OFF – The ALARM or VIDLOSS graphic does not display on the main monitor, it only displays on the call monitor. The multiplexer does not change the display on the main monitor. The default ALARM MESSAGE DISPLAY setting is ON.

Page 28

Chapter 4, Setup

Alarm Message Latch

19

The ALARM MESSAGE LATCH option determines how long the ALARM and VIDLOSS (video loss) messages remain on screen. It toggles as follows: ON – ALARM messages remain on screen until you press Function to clear them. Pressing Function removes all video loss messages and messages for expired alarm events. Messages for current alarm events remain on screen. NOTE: If video is not restored before the VIDLOSS message is cleared, the monitor displays the last image received until the display format changes, or video is restored. OFF – Each message remains on screen until the Alarm Duration time expires (the default is 4 seconds) or the corresponding alarm event clears. The default ALARM MESSAGE LATCH setting is OFF.

Video Loss Alarm

The VIDEO LOSS ALARM option controls the multiplexer video loss detection feature. It toggles as follows: ON – The multiplexer responds to camera video loss as an alarm event and displays the message VIDLOSS in place of the camera’s picture on both monitors. If ALARM MESSAGE DISPLAY is set OFF, the message only displays on the call monitor. The alarm counter counts a video loss as an alarm for that camera input. OFF – Camera video loss is not treated as an alarm event, and a VIDLOSS message is not displayed on either monitor. The alarm counter does not count the video loss as an alarm. The only sign of video loss is that the monitor displays the last image received from that camera until you change the display format, when a blank window with the camera number displays. Refer to Video Loss Alarms for more details. The default video loss setting is ON.

Page 29

20

Video Multiplexer with Video Motion Detection

Audible Alarm

The AUDIBLE ALARM option controls the multiplexer alarm tone. It toggles as follows: ON – The multiplexer sounds an alarm tone when it detects a mechanical alarm, motion alarm or video loss. Press any button to turn the alarm tone off. OFF – The multiplexer is silent when it detects a mechanical alarm, motion alarm or video loss. The default AUDIBLE ALARM setting is OFF.

Alarm Input Polarity

The ALARM INPUT POLARITY option allows you to set the polarity of all multiplexer alarm inputs. It toggles as follows: ACT LOW – Active alarm inputs are “low”. The multiplexer recognizes a contact closure or TTL/CMOS logic low as an alarm event. ACT HI – Active alarm inputs are “high”. The multiplexer recognizes a contact opening or TTL/CMOS logic high as an alarm event. The default ALARM INPUT POLARITY setting is ACT LOW.

Alarm Output Polarity

The ALARM OUTPUT POLARITY option allows you to set the active polarity of the TTL/CMOS alarm signal for pins 20–35 (motion outputs 1 - 16) on the alarms connector. It toggles as follows: ACT LOW – The alarm output signal goes “low” when a motion alarm occurs or for an alarm input or vidloss when PASS-THRU EXTRNL ALRMS is set to YES. ACT HI – The alarm output signal goes “high” when a motion alarm occurs. NOTE: The duration of the alarm output signal is determined by the ALARM DURATION setting. The default ALARM OUTPUT POLARITY setting is ACT LOW.

Page 30

Chapter 4, Setup

Pass-Thru Extrnl Alrms

21

This menu option lets you loop (pass-thru) the external alarm inputs to the alarm outputs. YES, Alarm outputs represent all alarms for a particular camera; motion alarms, mechanical alarms and video loss alarms. NO, Alarm outputs are for motion alarms only. External alarms are not included (not passed-thru). The default PASS-THRU EXTRNL ALRMS setting is YES.

Image Tenderizer

This option reduces the shakiness and jitter associated with high resolution compressed multicamera images. ON, Uses the special filtering circuit when the multiplexer displays a multicamera image on the main monitor. OFF, Turns off the special filtering circuit. The default IMAGE TENDERIZER setting is ON. When finished, press the Zoom button to go to menu 4 or press Function+Zoom to save all changes and leave the setup system.

Menu 4, VCR Record Time

Menu 4 allows you to enter the VCR’s normal and alarm recording speeds. With autodetect VCR speed, these settings are used if that signal is lost. Use the up and down arrow buttons to set each speed as follows: VCR RECORD TIME – The VCR’s normal (nonalarm) operating speed (2 - 999 hours). The default VCR RECORD TIME is 024 HRS. VCR ALARM RECORD TIME – The VCR’s recording speed for alarms (2 - 999 hours). The default VCR ALARM RECORD TIME is 002 HRS. NOTE: If the multiplexer alarm output is not connected to the VCR’s alarm input, the VCR RECORD TIME and the VCR ALARM RECORD TIME should be set to the same value. When finished, press the Zoom button to go to menu 5 or Function+Zoom to save all changes and leave the setup system.