Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeEnglishEspañolContact
Page 1 of SYSMAC Remote Vertical Module G72C-V

Spec sheet · Omron

SYSMAC Remote Vertical Module G72C-V

Spec sheet7 pagesPDF 206 KB

Spec sheet for the Omron G72C-V SYSMAC remote vertical module, the G72C-VID16 16-point input and G72C-VOD16 output terminals.

Download the PDF206 KB

Covers · 1 model

The models it covers

Summary

What is in it

A data sheet for the Omron G72C-V SYSMAC Remote Vertical Module, a slim terminal that combines a wiring block with remote I/O transmission over two-conductor cable to Omron wired remote I/O master modules. It covers the G72C-VID16 input and G72C-VOD16 output models with ordering information, ratings and characteristics, indicators and DIP switch settings, system configuration, dimensions, internal circuits and wiring examples, and precautions for combining G71 and G72C units.

Its parts

  1. Ordering Information
  2. Specifications
  3. Nomenclature
  4. Operation
  5. Dimensions
  6. Installation
  7. Precautions
  8. Contacting Omron

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

This is Omron's spec sheet for the G72C-V SYSMAC Remote Vertical Module, a slim terminal that combines a wiring block with remote I/O transmission. It covers the G72C-VID16 input model (filed on the site as G72C-V-ID16) and the G72C-VOD16 output model. It gives ratings, switch settings, dimensions, wiring examples and system precautions.

Device
G72C-VID16: SYSMAC remote I/O terminal with 16 inputs, NPN (+ common), 24 VDC p. 1, 5
Inputs
G72C-VID16: 16 points (8 points/common), 9.7 mA/point, ON/OFF delay 1.5 ms max., photocoupler insulated, green LEDs p. 2
Communication
Two-conductor, half duplex, RS-485; 187.5 kbps; 200 m total length p. 2
Master modules
Omron Wired Remote I/O Master Modules C200H-RM201 and C500-RM201 p. 1, 4
Power
24 VDC +10%/-15%; 200 mA max. with all 16 points ON p. 2
Transmission cable
Two-conductor cable, VCTF 0.75 x DPDT recommended p. 2
RUN output
SPST-NO contact, closed during operation; 2 A, 250 VAC p. 2
Size and mounting
202 x 63 x 45 mm max. (45 mm depth); DIN rail or screw panel mounting p. 1, 4
Operating environment
0°C to 55°C; 35% to 85% humidity p. 2
Weight
Approx. 380 g p. 2
Addressing
Word number 0 to 31 set by pins 1 to 5 (factory-set to 31); terminator setting (factory-set OFF) p. 3, 4
Diagnostics
Transmission error check (BCC plus inverted two-transmission verification), CPU error monitor p. 2
Approvals
The spec sheet states UL recognized (File No. E41515) and CSA certified (File No. LD31928) p. 2
Output version
G72C-VOD16: NPN (- common), 16 outputs, 0.3 A/point, 2.4 A/module p. 2, 5

What this sheet walks you through

  • Setting the word number with the DIP switch pins p. 3, 4
  • Setting the terminator on the unit farthest from the Master p. 3
  • Choosing output HOLD or STOP mode on the output version p. 3
  • Reading the POWER and T/R ERR indicators p. 3
  • Wiring sensors, switches and loads to the terminals p. 5
  • Building a remote I/O system with a Master Module, G71 interfaces and G7TC blocks p. 4, 6
  • Wiring the transmission line in order without branches p. 6

Good to know

  • Three-wire PNP output sensors cannot be connected. p. 5
  • Set only one terminator per Master, on the unit farthest from it. p. 3
  • Turn on all G71 and G72C units before powering the Master. p. 6
  • The DC supply must cover the power drawn by the LED indicators and all I/O devices. p. 5

Questions this sheet answers

How far can the G72C-V transmit?

Up to 200 m total length, at 187.5 kbps over two-conductor cable. p. 1, 2

Which PLC master modules work with the G72C-V?

Omron Wired Remote I/O Master Modules C200H-RM201 and C500-RM201. p. 1

Can PNP sensors be wired to the G72C-VID16?

No for three-wire PNP output sensors, which cannot be connected. The examples show 3-wire NPN sensors and 2-wire devices such as limit switches. p. 5

How many remote terminals can one Master Module take?

Each Remote I/O Subsystem connected to a Master Module can contain up to 32 nodes. p. 6

What power does the G72C-V need?

24 VDC +10%/-15%, drawing 200 mA max. with all 16 points ON. p. 2

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Front Page1
  2. Ordering Information1
  3. Specifications2
  4. Nomenclature3
  5. Operation3
  6. Dimensions4
  7. Installation5
  8. Precautions6
  9. Contacting Omron7

From the PDF’s own bookmarks.

The whole text · 1 part

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 71-7

The file

Revision and size

RevisionCat. No. GC RIO-1, 04/00
PublisherOmron Electronics, Inc.
Pages7
PDF206 KB
TextText from the PDF itself.

The first pages · 4 of 7

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 7
Page 2
Page 2of 7
Page 3
Page 3of 7
Page 4
Page 4of 7