Page 7
CPU Unit Descriptions
CQM1H CPU Units CQM1H-CPU@@
CPU Unit Descriptions CQM1H CPU Units
CQM1H-CPU@@ CPU Units The four models of CPU Units can be broadly divided into two groups: Models that support Inner Boards and the Controller Link Unit, and models that do not. The CPU Units also vary in their program capacities, I/O capacities, memory capacities, and the presence of an RS-232C port, as shown in the Basic Specifications table, below.
■ CPU Unit Overview The following illustration shows the main components of a CQM1H-CPU61 CPU Unit. Sliders Used to secure adjacent Units. Battery Compartment Cover Open this cover to access the battery, DIP switch, and Memory Cassette.
Connector Add on Units horizontally by joining connectors.
Peripheral Port Used to connect to Programming Devices such as a Programming Console or a computer running CX-Programmer. Also supports Host Link and no-protocol communications.
LED indicators Built-in Inputs There are 16 inputs built into CPU Unit. Inner Board Covers Remove these covers when installing or removing Inner Boards.
RS-232C Port (except CQM1H-CPU11) Used for Host Link, no-protocol, 1:1 Data Link, or NT link (1:1 mode) communications with external devices or other PLCs.
Inner Board Slot 2 (right slot) Use this slot to mount a High-speed Counter Board, Pulse I/O Board, Absolute Encoder Interface Board, Analog Setting Board, or Analog I/O Board. Inner Board Slot 1 (left slot) Use this slot to mount a High-speed Counter Board, Analog Setting Board, or Serial Communications
■ Basic Specifications Model
CQM1H-CPU61
I/O capacity (See note.) 512
CQM1H-CPU51 CQM1H-CPU21
256
Program capacity (words)
DM capacity (words)
EM capacity (words)
CPU Unit built-in inputs
Peripheral port
RS-232C port
DC: 16
Yes
Yes
15.2 K
6K
6K
7.2 K
6K
None
3.2 K
3K
Built-in serial ports
No
Note: I/O capacity = Number of input points (≤ 256) + Number of output points (≤ 256).
■ Maximum Number of Units CQM1H-CPU61
Controller Link Unit
Inner Boards
1 max.
2 max.
Not supported.
Not supported.
CQM1H-CPU51 CQM1H-CPU21 CQM1H-CPU11
10
Supported Not supported
CQM1H-CPU11
CPU Unit
Inner Boards
I/O Units and Dedicated I/O Units 11 max. (total)
Controller Link Unit
Page 8
CPU Unit Descriptions
Power Supply Units and I/O Expansion Units
Power Supply Units and I/O Expansion Units ■ Power Supply Units Both AC and DC Power Supply Units are available. The AC Power Supply Units require a power supply input from 100 to 240 V AC and two of the AC Power Supply Units are equipped with a 24-V DC power supply output. The CQM1H’s left End Cover is part of the Power Supply Unit.
CQM1-PA206 CQM1-PA203 CQM1-PA216
CQM1-PD026
Specifications Name
Model number
Specifications Supply voltage
AC Power Supply Units
CQM1-PA203
100 to 240 V AC, 50/60 Hz (wide range)
Operating voltage range 85 to 265 V AC
CQM1-PA206
DC Power Supply Units
CQM1-PA216
100 or 230 V AC (selectable), 50/60 Hz
CQM1-PD026
24 V DC
Output capacity
Service power supply
5 V DC: 3.6 A (18 W)
None
5 V DC: 6 A 24 V DC: 0.5 A (30 W total, see note)
24 V DC: 0.5 A
5 V DC: 6 A 24 V DC: 0.5 A (30 W total, see note) 20 to 28 V DC
30 W 5 V DC: 6 A
None
Note: The total power consumed at 5 V DC and 24 V DC must be less than 30 W. (5 × Current consumed at 5 V DC) + (24 × Current consumed at 24 V DC) ≤ 30 W
11
Page 9
CPU Unit Descriptions
Power Supply Units and I/O Expansion Units
■ I/O Expansion Units Use Expansion I/O Blocks to split the configuration into more than one group, allowing greater flexibility with mounting space as well as the use of at least 12 I/O Units or Dedicated I/O Units. Expansion Units can be used with any CQM1H CPU Unit.
CQM1H-IC101
CQM1H-II101
Maximum Number of Units Mountable CPU Unit model
CPU Block only
CPU Block + I/O Expansion Block
CPU Block
CQM1H-CPU61 CQM1H-CPU51
CPU Block
I/O Expansion Block
Inner Boards
I/O Units + Dedicated I/O Units + Dedicated I/O Units I/O Units
I/O Units + Dedicated I/O Units
Controller Link Unit
11 Units max. (see note 1)
1 Unit
2 Boards max.
Not supported
Not supported
CQM1H-CPU21
5 Units max. (see note 2)
11 Units max. (see note 3)
CQM1H-CPU11 Note: 1. Ensure that the total current consumption of the mounted Units (CPU Unit, Controller Link Unit, Inner Boards, I/O Units, and Dedicated I/O Units) 2. Ensure that the total current consumption of the mounted Units (CPU Unit, Controller Link Unit, Inner Boards, I/O Units, Dedicated I/O Units, and I/O Control Units) does not exceed 3.0 A. 3. Ensure that the total current consumption of the mounted Units (I/O Interface Units, I/O Units, and Dedicated I/O Units) does not exceed 2.0 A.
5 Units max.
Total current consumption: 3.0 A max. (including CPU Unit) I/O Control Unit (CQM1H-IC101)
System Configuration Example
End Cover (included with CPU Unit) I/O Extension Cable CS1W-CN313 (0.3 m) or CS1W-CN713 (0.7 m)
I/O Interface Unit (CQM1H-II101)
End Cover (included with I/O Interface Unit)
11 Units max. Total current consumption: 2.0 A max. (I/O Units and Dedicated I/O Units)
12
Page 10
CPU Unit Descriptions
Memory Cassettes
Memory Cassettes An optional Memory Cassette can be used to store the user program, PLC Setup, and other data in ROM so that vital data will not be lost in the event of battery expiration or careless programming/monitoring operations. If the PLC’s settings need to be changed to execute another process, the entire software setup and user program can be changed just by exchanging the Memory Cassette and rebooting the PLC.
EEPROM:
Flash Memory:
EPROM:
CQM1-ME04K CQM1-ME04R CQM1-ME08K CQM1-ME08R
CQM1H-ME16K CQM1H-ME16R
CQM1-MP08K CQM1-MP08R
■ Available Memory Cassettes The following Memory Cassettes are available. Memory EEPROM
Model
Specifications
CQM1-ME04K
4 Kwords without clock
CQM1-ME04R
4 Kwords with clock
CQM1-ME08K
8 Kwords without clock
CQM1-ME08R
8 Kwords with clock
EPROM
CQM1-MP08K
Without clock (see below)
CQM1-MP08R
With clock (see below)
Flash
CQM1H-ME16K
16 Kwords without clock
CQM1H-ME16R
16 Kwords with clock
The following EPROM chips (sold separately) are required for EPROM Memory Cassettes. The chip is mounted in the I/O socket on the Memory Cassette. Model
ROM version
Capacity
Access speed
ROM-JD-B
27256 or equivalent
16 Kwords
150 ns
ROM-KD-B
27512 or equivalent
32 Kwords
150 ns
13
Page 11
CPU Unit Descriptions
Specifications
Specifications ■ General Specifications (Power Supplies and CPU Units) Item Supply voltage
CQM1-PA203
CQM1-PA206
100 to 240 V AC, 50/60 Hz
Operating voltage range 85 to 264 V AC
CQM1-PA216
CQM1-PD026
100 or 230 V AC (selectable), 50/60 Hz
24 V DC
85 to 132 V AC or 170 to 264 V AC
20 to 28 V DC
Operating frequency range
47 to 63 Hz
Power consumption
60 VA max.
Inrush current
30 A max.
Output capacity
5 V DC: 3.6 A (18 W)
Insulation resistance
20 MΩ min. (at 500 V DC) between AC external terminals and GR terminals (See note.)
Dielectric strength
2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals, leakage current: 10 mA max. (See note.) 1,000 V AC 50/60 Hz for 1 min between DC external and GR terminals, leakage current: 20 mA max. (See note.)
Noise immunity
Conforms to IEC61000-4-4, 2 kV (power lines)
Vibration resistance
10 to 57 Hz with an amplitude of 0.075 mm, and 57 to 150 Hz with an acceleration of 9.8 m/s2 in the X, Y, and Z directions for 80 minutes each (i.e., swept for 8 minutes, 10 times).
Shock resistance
147 m/s2 (118 m/s2 for Contact Output Units) 3 times each in X, Y, and Z directions
Ambient temperature
Operating: 0 to 55 °C Storage: –20 to 75 °C (except battery)
Ambient operating humidity
10% to 90% (no condensation)
Operating environment
No corrosive gas
Ground
Less than 100 Ω
--120 VA max.
50 W max.
5 V DC: 6 A 24 V DC: 0.5 A (30 W total)
5 V DC: 6 A (30 W)
Construction
Panel mounted
Weight
5 kg max.
Internal current consumption
CQM1H-CPU11: 820 mA max. at 5 V DC CQM1H-CPU21/51/61: 840 mA max. at 5 V DC
Dimensions (without cables)
CQM1H-CPU11/21: CQM1H-CPU51/61:
Accessories
RS-232C connector (one XM2A-0901 Plug and one XM2S-0911-E Hood) (except CQM1H-CPU11) CPM2A-BAT01 Battery Set (installed in CPU Unit when shipped)
187 to 571 × 110 × 107 mm (W×H×D) 187 to 603 × 110 × 107 mm (W×H×D)
Note: Disconnect the Power Supply Unit's LG terminal from the GR terminal when testing insulation and dielectric strength. Repeatedly testing the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage internal circuits in the CPU Unit.
14
Page 12
CPU Unit Descriptions
Specifications
■ CPU Unit Specifications Characteristics Item Control method
Specifications Stored program method
I/O control method
Cyclic scan and direct output/immediate interrupt processing
Programming language
Ladder-diagram programming
I/O capacity
CQM1H-CPU11/21: CQM1H-CPU51/61:
256 512
Program capacity
CQM1H-CPU11/21: CQM1H-CPU51: CQM1H-CPU61:
3.2 Kwords 7.2 Kwords 15.2 Kwords
Data memory capacity
CQM1H-CPU11/21: CQM1H-CPU51: CQM1H-CPU61:
3 Kwords 6 Kwords 12 Kwords (DM: 6 Kwords; EM: 6 Kwords)
Instruction length
1 step per instruction, 1 to 4 words per instruction
Number of instructions
162 (14 basic, 148 special instructions)
Instruction execution times
Basic instructions: Special instructions:
Overseeing time
0.70 ms
0.375 to 1.125 µs 17.7 µs (MOV instruction)
Mounting structure
No Backplane (Units are joined horizontally using connectors)
Mounting
DIN Track mounting (screw mounting not possible)
CPU Unit built-in DC input points
16
Maximum number of Units
CPU Block only: 11 Units (I/O Units and Dedicated I/O Units) max. CPU Block and Expansion I/O Block CPU Block: 5 Units max. Expansion I/O Block: 11 Units max.
Inner Boards
CQM1H-CPU11/21: CQM1H-CPU51/61:
None 2 Boards
Communications Units (Controller Link Unit)
CQM1H-CPU11/21: CQM1H-CPU51/61:
None 1 Unit
Types of interrupts
Input interrupts (4 inputs max.)
Input Interrupt Mode: Interrupts are executed in response to inputs from external sources to the CPU Unit’s built-in input points. Counter Mode: Interrupts are executed in response to reception of a set number of pulses (counted down) via the CPU Unit’s internal built-in input points (4 points).
Interval timer interrupts (3 timers max.)
Scheduled Interrupt Mode: Program is interrupted at regular intervals measured by one of the CPU Unit’s internal timers. One-shot Interrupt Mode: An interrupt is executed after a set time, measured by one of the CPU Unit’s internal timers.
High-speed counter interrupts
Target Value Comparison: Interrupt is executed when the high-speed counter PV is equal to a specified value. Range Comparison: Interrupt is executed when the high-speed counter PV lies within a specified range. Note: Counting is possible for high-speed counter inputs from the CPU Unit’s internal input points, Pulse I/O Boards, or Absolute Encoder Interface Boards. (The High-speed Counter Board has no interrupt function, but can output bit patterns internally and externally.)
I/O allocations
I/O is automatically allocated in order from the Unit nearest to the CPU Unit. (Because there are no I/O tables, it is not necessary, and not possible, to create I/O tables from a Programming Device.)
Note: Analog Power Supply Units must also be counted.
15
Page 13
CPU Unit Descriptions
Specifications
Memory Area Structure Data area IR area
Size
Words
Bits
Function
Input area
256 bits
IR 000 to IR 015
IR 00000 to IR 01515
Input bits are allocated to Input Units or Dedicated I/O Units. The 16 bits in IR 000 are always allocated to the CPU Unit’s built-in inputs. Bits in IR 001 to IR 015 are allocated to I/O or Dedicated I/O Units connected to the CPU Unit.
Output area
256 bits
IR 100 to IR 115 IR 10000 to IR 11515
Output bits are allocated to Output Units or Dedicated I/O Units connected to the CPU Unit.
Work areas
2,528 bits min.
IR 016 to IR 089
Work bits do not have any specific function and they can be freely used within the program. (A minimum 2,528 bits are available as work bits. Most bits in the IR and LR areas can be used as work bits when they are not used for their allocated functions, so the total number of available work bits depends on the configuration of the PLC.)
IR 01600 to IR 08915
IR 116 to IR 189 IR 11600 to IR 18915 IR 216 to IR 219
IR 21600 to IR 21915
IR 224 to IR 229
IR 22400 to IR 22915
96 bits
IR 090 to IR 095
IR 09000 to IR 09515
Status Area 1: Stores the Controller Link data link status information.
96 bits
IR 190 to IR 195
IR 19000 to IR 19515
Status Area 2: Stores the Controller Link error and network participation information.
Input area
64 bits
IR 096 to IR 099
IR 09600 to IR 09915
Used when the MACRO instruction, MCRO(99), is used.
Output area
64 bits
IR 196 to IR 199
IR 19600 to IR 19915
Inner Board slot 1 area 256 bits
IR 200 to IR 215
IR 20000 to IR 21515
These bits are allocated to the Inner Board mounted in slot 1 of a CQM1H-CPU51/61. High-speed Counter Board: IR 200 to IR 213 Serial Communications Board: IR 200 to IR 207
Analog settings area
64 bits
IR 220 to IR 223
IR 22000 to IR 22315
Used to store the analog settings when a CQM1H-AVB41 Analog Setting Board is mounted.
High-speed Counter 0 32 bits PV
IR 230 to IR 231
IR 23000 to IR 23115
Used to store the present values of high-speed counter 0.
Inner Board slot 2 area 192 bits
IR 232 to IR 243
IR 23200 to IR 24315
These bits are allocated to the Inner Board mounted in slot 2. High-speed Counter Board: IR 232 to IR 243 Absolute Encoder Interface Board: IR 232 to IR 239 Pulse I/O Board: IR 232 to IR 239 Analog I/O Board: IR 232 to IR 239
SR area
184 bits
SR 244 to SR 255
SR 24400 to SR 25507
These bits serve specific functions such as flags and control bits.
HR area
1,600 bits
HR 00 to HR 99 HR 0000 to HR 9915
These bits store data and retain their ON/OFF status when power is turned OFF or when the operating mode is changed.
AR area
448 bits
AR 00 to AR 27 AR 0000 to AR 2715
These bits serve specific functions such as flags and control bits.
TR area
8 bits
---
These bits are used to temporarily store ON/OFF status at program branches.
LR area
1,024 bits
LR 00 to LR 63 LR 0000 to LR 6315
Used for 1:1 data link through the RS-232 port or through a Controller Link Unit.
Timer/Counter area
512 bits
TIM/CNT 000 to TIM/CNT 511 (timer/counter numbers)
The same numbers are used for both timers and counters. Timer numbers 000 to 015 can be used with TIMH(15) for interrupt-refreshed PVs to ensure proper timing without inaccuracy being caused by the cycle time.
Controller Link status areas
MACRO operand area
16
TR 0 to TR 7
Page 14
CPU Unit Descriptions Data area DM area
Read/ write
Size
Specifications Words
Bits
Function
3,072 words
DM 0000 to DM 3071
---
DM area data can be accessed in word units only. Word values are retained when the power is turned OFF.
3,072 words
DM 3072 to DM 6143
---
Available in CQM1H-CPU51/61 CPU Units only.
Readonly4
425 words
DM 6144 to DM 6568
---
Cannot be written from the program (only from a Programming Device). DM 6400 to DM 6409: Controller Link parameters DM 6450 to DM 6499: Routing tables DM 6550 to DM 6559: Serial Communications Board Setup
Error history area4
31 words
DM 6569 to DM 6599
---
Cannot be written from the program (only from a Programming Device). Stores the time of occurrence and error code of errors that occur.
PLC Setup4
56 words
DM 6600 to DM 6655
---
Cannot be written from the program (only from a Programming Device). Stores various parameters that control PLC operation.
6,144 words
EM 0000 to EM 6143
---
EM area data can be accessed in word units only. Word values are retained when the power is turned OFF or the operating mode is changed. (CQM1H-CPU61 CPU Unit only.)
EM area
Memory Cassette Specifications Item Memory Cassette (EEPROM or flash memory)
Details Mounted from the front of the CPU Unit and used to store and read the user’s program, DM (read-only DM and PLC Setup), and expansion instruction information as one block. It is possible to set the CPU Unit so that data stored in the Memory Cassette (user’s program, DM, expansion instruction information) is automatically sent to the CPU Unit (autoboot) at startup. Transfer and comparison of data between the CPU Unit and Memory Cassette are possible using AR area control bits.
Other Functions Item Macro instructions
Specification Subroutines called by instructions containing arguments.
Min. cycle time
1 to 9,999 ms (Unit: 1 ms)
Cycle time monitoring
When the cycle time exceeds 100 ms, the Cycle Time Over Flag turns ON, and operation continues. (A setting can be made in the PLC Setup so that this error is not generated.) When the cycle time exceeds the cycle monitor time, operation is stopped. Cycle monitor time settings: 0 to 990 ms in 10-ms units, 0 to 9,900 ms in 100-ms units, 0 to 99 s in 1-s units.
I/O refreshing
Cyclic refreshing, refreshing by IORF(97), direct output refreshing (set in the PLC Setup), interrupt input refreshing. (The inputs that are refreshed can be set separately for input interrupts, high-speed counter interrupts, and interval timer interrupts in the PLC Setup.)
I/O memory status when changing operating mode
Depends on the ON/OFF status of the I/O Hold Bit (SR 25212).
Load OFF
All outputs on Output Units can be turned OFF when the CPU Unit is operating in RUN, MONITOR, or PROGRAM mode. (Used for stopping output in emergencies, for debugging, etc.)
User-customized DIP switch setting
A pin setting on the DIP switch on the front of the CPU Unit is stored in AR 0712. This setting can be used as an ON/OFF condition (e.g., to switch between trial operation and actual operation).
Mode setting at power-up
Possible
Note: The maximum and current values of the cycle time are stored in the AR area.
Debugging
Forced set/reset, differential monitoring, data tracing (scheduled, cyclic, or when instruction is executed).
Online editing
User programs can be overwritten in program-block units when the CPU Unit is in MONITOR mode. With the CX-Programmer, more than one program block can be edited at the same time.
Program protection
Write-protection of user program and data memory (DM 6144 to DM 6655: read-only DM): Set using pin 1 of the DIP switch.
Error check
User-defined errors (i.e., user can define fatal errors and non-fatal errors using the FAL(06) and FALS(07) instructions.) (It is possible to stop operation using FALS(07) for fatal errors. User-defined error logs can be created in specific bits (logging) when using FAL(06).
Error log
Up to 10 errors (including user-defined errors) are stored in the error log. Information includes the error code, error details, and the time the error occurred.
17
Page 15
CPU Unit Descriptions Item
Specifications Specification
Serial communications Built-in peripheral port: Programming Device (including Programming Console) connections, Host Links, no-protocol communications Built-in RS-232C port: Programming Device (excluding Programming Console) connections, Host Links, no-protocol communications, NT Links (1:1 mode), 1:1 Data LInks RS-232C port and RS-422A/485 port on Serial Communications Board (sold separately): Programming Device (excluding Programming Console) connections, Host Links, no-protocol communications, NT Links (1:1 mode, 1:N mode), 1:1 Data LInks, protocol macros Serial communications CQM1H CPU Unit’s built-in port modes
Built-in Built-in Serial peripheral port RS-232C port Communications Board ports
Programming Console bus
Connects to Programming Console.
YES (pin 7 OFF)
No
No
Peripheral bus
Connects to a computer running CX-Programmer or other Support YES Software. (Automatically used if the network type is set to periph- (pin 7 ON) eral bus on the Support Software.)
No
No
Host Link (SYSMAC WAY)
Enables reading/writing CPU Unit I/O memory or program using Host Link commands. Computers running Support Software or OMRON Programmable Terminals can also be connected. PLCinitiated communications are possible.
YES (pin 7 ON)
YES
YES
No-protocol
Enables sending or receiving up to 256 bytes of data without a pro- YES tocol or data conversion. A start code, end code, and transmission (pin 7 ON) delay can be set.
YES
YES
1:1 data link
Enables 1:1 data link with a CQM1H, CQM1, CPM-series, C200HX/HG/HE, C200HS, or SRM1 PLC.
YES
YES
NT links (1:1 and 1:N)
Enables 1:1 or 1:N communications with OMRON Programmable No Terminals without additional programming.
YES (1:1 only)
YES (1:1 and 1:N)
Protocol macros
Enables user-created protocols to communicate with essential any No device equipped with a serial communications port (e.g., RS232C). Standard protocols are also provided.
No
YES
No
Clock
Some Memory Cassette are equipped with a clock. (The time of the error will recorded if a clock is used.
Input time constants
Used to set the ON (or OFF) response times for DC Input Units. Settings: 1, 2, 4, 8, 16, 32, 64, and 128 ms.
Power OFF detection time
AC power supply: 10 to 25 ms (not fixed), DC power supply: 5 to 25 ms (not fixed)
Memory protection
Held Areas: Holding bits, contents of Data Memory and Extended Data Memory, and status of the counter Completion Flags and present values. Note: If the I/O Hold Bit (SR 25212) is turned ON, and the PLC Setup is set to maintain the I/O Hold Bit status when power is turned ON, the contents of the IR area and the LR area will be saved.
Commands to a host computer
Host Link command responses can be sent to a computer connected via the Host Link System using the TXD(––) (communications port output) instruction.
Remote programming and monitoring
Host Link or peripheral bus communications via a CPU Unit’s serial communications port can be used for remote programming and remote monitoring of the PLC through a Controller Link System. (This function is, however, not supported for the serial communications ports on the Serial Communications Board.)
Program check
Program is checked at the beginning of operation for items such as no END(01) instruction and instruction errors. CXProgrammer can also check programs. (The level of program checking can be set.)
Battery life
5 years at 25°C (Depends on the ambient temperature and power supply conditions. Min.: 1 yr) Battery replacement must be performed within 5 minutes.
Errors from self-diagnostics
CPU (watchdog timer), I/O verification, I/O bus, memory, FALS system (FALS execution or cycle monitor time over), FAL system (FAL execution or PLC Setup error etc.), battery, cycle time over and communications port.
Other functions
Storage of number of times power has been interrupted. (Stored in AR area.)
18