Page 7

CPU Unit Descriptions

CQM1H CPU Units CQM1H-CPU@@

CPU Unit Descriptions CQM1H CPU Units

CQM1H-CPU@@ CPU Units The four models of CPU Units can be broadly divided into two groups: Models that support Inner Boards and the Controller Link Unit, and models that do not. The CPU Units also vary in their program capacities, I/O capacities, memory capacities, and the presence of an RS-232C port, as shown in the Basic Specifications table, below.

■ CPU Unit Overview The following illustration shows the main components of a CQM1H-CPU61 CPU Unit. Sliders Used to secure adjacent Units. Battery Compartment Cover Open this cover to access the battery, DIP switch, and Memory Cassette.

Connector Add on Units horizontally by joining connectors.

Peripheral Port Used to connect to Programming Devices such as a Programming Console or a computer running CX-Programmer. Also supports Host Link and no-protocol communications.

LED indicators Built-in Inputs There are 16 inputs built into CPU Unit. Inner Board Covers Remove these covers when installing or removing Inner Boards.

RS-232C Port (except CQM1H-CPU11) Used for Host Link, no-protocol, 1:1 Data Link, or NT link (1:1 mode) communications with external devices or other PLCs.

Inner Board Slot 2 (right slot) Use this slot to mount a High-speed Counter Board, Pulse I/O Board, Absolute Encoder Interface Board, Analog Setting Board, or Analog I/O Board. Inner Board Slot 1 (left slot) Use this slot to mount a High-speed Counter Board, Analog Setting Board, or Serial Communications

■ Basic Specifications Model

CQM1H-CPU61

I/O capacity (See note.) 512

CQM1H-CPU51 CQM1H-CPU21

256

Program capacity (words)

DM capacity (words)

EM capacity (words)

CPU Unit built-in inputs

Peripheral port

RS-232C port

DC: 16

Yes

Yes

15.2 K

6K

6K

7.2 K

6K

None

3.2 K

3K

Built-in serial ports

No

Note: I/O capacity = Number of input points (≤ 256) + Number of output points (≤ 256).

■ Maximum Number of Units CQM1H-CPU61

Controller Link Unit

Inner Boards

1 max.

2 max.

Not supported.

Not supported.

CQM1H-CPU51 CQM1H-CPU21 CQM1H-CPU11

10

Supported Not supported

CQM1H-CPU11

CPU Unit

Inner Boards

I/O Units and Dedicated I/O Units 11 max. (total)

Controller Link Unit

Page 8

CPU Unit Descriptions

Power Supply Units and I/O Expansion Units

Power Supply Units and I/O Expansion Units ■ Power Supply Units Both AC and DC Power Supply Units are available. The AC Power Supply Units require a power supply input from 100 to 240 V AC and two of the AC Power Supply Units are equipped with a 24-V DC power supply output. The CQM1H’s left End Cover is part of the Power Supply Unit.

CQM1-PA206 CQM1-PA203 CQM1-PA216

CQM1-PD026

Specifications Name

Model number

Specifications Supply voltage

AC Power Supply Units

CQM1-PA203

100 to 240 V AC, 50/60 Hz (wide range)

Operating voltage range 85 to 265 V AC

CQM1-PA206

DC Power Supply Units

CQM1-PA216

100 or 230 V AC (selectable), 50/60 Hz

CQM1-PD026

24 V DC

Output capacity

Service power supply

5 V DC: 3.6 A (18 W)

None

5 V DC: 6 A 24 V DC: 0.5 A (30 W total, see note)

24 V DC: 0.5 A

5 V DC: 6 A 24 V DC: 0.5 A (30 W total, see note) 20 to 28 V DC

30 W 5 V DC: 6 A

None

Note: The total power consumed at 5 V DC and 24 V DC must be less than 30 W. (5 × Current consumed at 5 V DC) + (24 × Current consumed at 24 V DC) ≤ 30 W

11

Page 9

CPU Unit Descriptions

Power Supply Units and I/O Expansion Units

■ I/O Expansion Units Use Expansion I/O Blocks to split the configuration into more than one group, allowing greater flexibility with mounting space as well as the use of at least 12 I/O Units or Dedicated I/O Units. Expansion Units can be used with any CQM1H CPU Unit.

CQM1H-IC101

CQM1H-II101

Maximum Number of Units Mountable CPU Unit model

CPU Block only

CPU Block + I/O Expansion Block

CPU Block

CQM1H-CPU61 CQM1H-CPU51

CPU Block

I/O Expansion Block

Inner Boards

I/O Units + Dedicated I/O Units + Dedicated I/O Units I/O Units

I/O Units + Dedicated I/O Units

Controller Link Unit

11 Units max. (see note 1)

1 Unit

2 Boards max.

Not supported

Not supported

CQM1H-CPU21

5 Units max. (see note 2)

11 Units max. (see note 3)

CQM1H-CPU11 Note: 1. Ensure that the total current consumption of the mounted Units (CPU Unit, Controller Link Unit, Inner Boards, I/O Units, and Dedicated I/O Units) 2. Ensure that the total current consumption of the mounted Units (CPU Unit, Controller Link Unit, Inner Boards, I/O Units, Dedicated I/O Units, and I/O Control Units) does not exceed 3.0 A. 3. Ensure that the total current consumption of the mounted Units (I/O Interface Units, I/O Units, and Dedicated I/O Units) does not exceed 2.0 A.

5 Units max.

Total current consumption: 3.0 A max. (including CPU Unit) I/O Control Unit (CQM1H-IC101)

System Configuration Example

End Cover (included with CPU Unit) I/O Extension Cable CS1W-CN313 (0.3 m) or CS1W-CN713 (0.7 m)

I/O Interface Unit (CQM1H-II101)

End Cover (included with I/O Interface Unit)

11 Units max. Total current consumption: 2.0 A max. (I/O Units and Dedicated I/O Units)

12

Page 10

CPU Unit Descriptions

Memory Cassettes

Memory Cassettes An optional Memory Cassette can be used to store the user program, PLC Setup, and other data in ROM so that vital data will not be lost in the event of battery expiration or careless programming/monitoring operations. If the PLC’s settings need to be changed to execute another process, the entire software setup and user program can be changed just by exchanging the Memory Cassette and rebooting the PLC.

EEPROM:

Flash Memory:

EPROM:

CQM1-ME04K CQM1-ME04R CQM1-ME08K CQM1-ME08R

CQM1H-ME16K CQM1H-ME16R

CQM1-MP08K CQM1-MP08R

■ Available Memory Cassettes The following Memory Cassettes are available. Memory EEPROM

Model

Specifications

CQM1-ME04K

4 Kwords without clock

CQM1-ME04R

4 Kwords with clock

CQM1-ME08K

8 Kwords without clock

CQM1-ME08R

8 Kwords with clock

EPROM

CQM1-MP08K

Without clock (see below)

CQM1-MP08R

With clock (see below)

Flash

CQM1H-ME16K

16 Kwords without clock

CQM1H-ME16R

16 Kwords with clock

The following EPROM chips (sold separately) are required for EPROM Memory Cassettes. The chip is mounted in the I/O socket on the Memory Cassette. Model

ROM version

Capacity

Access speed

ROM-JD-B

27256 or equivalent

16 Kwords

150 ns

ROM-KD-B

27512 or equivalent

32 Kwords

150 ns

13

Page 11

CPU Unit Descriptions

Specifications

Specifications ■ General Specifications (Power Supplies and CPU Units) Item Supply voltage

CQM1-PA203

CQM1-PA206

100 to 240 V AC, 50/60 Hz

Operating voltage range 85 to 264 V AC

CQM1-PA216

CQM1-PD026

100 or 230 V AC (selectable), 50/60 Hz

24 V DC

85 to 132 V AC or 170 to 264 V AC

20 to 28 V DC

Operating frequency range

47 to 63 Hz

Power consumption

60 VA max.

Inrush current

30 A max.

Output capacity

5 V DC: 3.6 A (18 W)

Insulation resistance

20 MΩ min. (at 500 V DC) between AC external terminals and GR terminals (See note.)

Dielectric strength

2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals, leakage current: 10 mA max. (See note.) 1,000 V AC 50/60 Hz for 1 min between DC external and GR terminals, leakage current: 20 mA max. (See note.)

Noise immunity

Conforms to IEC61000-4-4, 2 kV (power lines)

Vibration resistance

10 to 57 Hz with an amplitude of 0.075 mm, and 57 to 150 Hz with an acceleration of 9.8 m/s2 in the X, Y, and Z directions for 80 minutes each (i.e., swept for 8 minutes, 10 times).

Shock resistance

147 m/s2 (118 m/s2 for Contact Output Units) 3 times each in X, Y, and Z directions

Ambient temperature

Operating: 0 to 55 °C Storage: –20 to 75 °C (except battery)

Ambient operating humidity

10% to 90% (no condensation)

Operating environment

No corrosive gas

Ground

Less than 100 Ω

--120 VA max.

50 W max.

5 V DC: 6 A 24 V DC: 0.5 A (30 W total)

5 V DC: 6 A (30 W)

Construction

Panel mounted

Weight

5 kg max.

Internal current consumption

CQM1H-CPU11: 820 mA max. at 5 V DC CQM1H-CPU21/51/61: 840 mA max. at 5 V DC

Dimensions (without cables)

CQM1H-CPU11/21: CQM1H-CPU51/61:

Accessories

RS-232C connector (one XM2A-0901 Plug and one XM2S-0911-E Hood) (except CQM1H-CPU11) CPM2A-BAT01 Battery Set (installed in CPU Unit when shipped)

187 to 571 × 110 × 107 mm (W×H×D) 187 to 603 × 110 × 107 mm (W×H×D)

Note: Disconnect the Power Supply Unit's LG terminal from the GR terminal when testing insulation and dielectric strength. Repeatedly testing the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage internal circuits in the CPU Unit.

14

Page 12

CPU Unit Descriptions

Specifications

■ CPU Unit Specifications Characteristics Item Control method

Specifications Stored program method

I/O control method

Cyclic scan and direct output/immediate interrupt processing

Programming language

Ladder-diagram programming

I/O capacity

CQM1H-CPU11/21: CQM1H-CPU51/61:

256 512

Program capacity

CQM1H-CPU11/21: CQM1H-CPU51: CQM1H-CPU61:

3.2 Kwords 7.2 Kwords 15.2 Kwords

Data memory capacity

CQM1H-CPU11/21: CQM1H-CPU51: CQM1H-CPU61:

3 Kwords 6 Kwords 12 Kwords (DM: 6 Kwords; EM: 6 Kwords)

Instruction length

1 step per instruction, 1 to 4 words per instruction

Number of instructions

162 (14 basic, 148 special instructions)

Instruction execution times

Basic instructions: Special instructions:

Overseeing time

0.70 ms

0.375 to 1.125 µs 17.7 µs (MOV instruction)

Mounting structure

No Backplane (Units are joined horizontally using connectors)

Mounting

DIN Track mounting (screw mounting not possible)

CPU Unit built-in DC input points

16

Maximum number of Units

CPU Block only: 11 Units (I/O Units and Dedicated I/O Units) max. CPU Block and Expansion I/O Block CPU Block: 5 Units max. Expansion I/O Block: 11 Units max.

Inner Boards

CQM1H-CPU11/21: CQM1H-CPU51/61:

None 2 Boards

Communications Units (Controller Link Unit)

CQM1H-CPU11/21: CQM1H-CPU51/61:

None 1 Unit

Types of interrupts

Input interrupts (4 inputs max.)

Input Interrupt Mode: Interrupts are executed in response to inputs from external sources to the CPU Unit’s built-in input points. Counter Mode: Interrupts are executed in response to reception of a set number of pulses (counted down) via the CPU Unit’s internal built-in input points (4 points).

Interval timer interrupts (3 timers max.)

Scheduled Interrupt Mode: Program is interrupted at regular intervals measured by one of the CPU Unit’s internal timers. One-shot Interrupt Mode: An interrupt is executed after a set time, measured by one of the CPU Unit’s internal timers.

High-speed counter interrupts

Target Value Comparison: Interrupt is executed when the high-speed counter PV is equal to a specified value. Range Comparison: Interrupt is executed when the high-speed counter PV lies within a specified range. Note: Counting is possible for high-speed counter inputs from the CPU Unit’s internal input points, Pulse I/O Boards, or Absolute Encoder Interface Boards. (The High-speed Counter Board has no interrupt function, but can output bit patterns internally and externally.)

I/O allocations

I/O is automatically allocated in order from the Unit nearest to the CPU Unit. (Because there are no I/O tables, it is not necessary, and not possible, to create I/O tables from a Programming Device.)

Note: Analog Power Supply Units must also be counted.

15

Page 13

CPU Unit Descriptions

Specifications

Memory Area Structure Data area IR area

Size

Words

Bits

Function

Input area

256 bits

IR 000 to IR 015

IR 00000 to IR 01515

Input bits are allocated to Input Units or Dedicated I/O Units. The 16 bits in IR 000 are always allocated to the CPU Unit’s built-in inputs. Bits in IR 001 to IR 015 are allocated to I/O or Dedicated I/O Units connected to the CPU Unit.

Output area

256 bits

IR 100 to IR 115 IR 10000 to IR 11515

Output bits are allocated to Output Units or Dedicated I/O Units connected to the CPU Unit.

Work areas

2,528 bits min.

IR 016 to IR 089

Work bits do not have any specific function and they can be freely used within the program. (A minimum 2,528 bits are available as work bits. Most bits in the IR and LR areas can be used as work bits when they are not used for their allocated functions, so the total number of available work bits depends on the configuration of the PLC.)

IR 01600 to IR 08915

IR 116 to IR 189 IR 11600 to IR 18915 IR 216 to IR 219

IR 21600 to IR 21915

IR 224 to IR 229

IR 22400 to IR 22915

96 bits

IR 090 to IR 095

IR 09000 to IR 09515

Status Area 1: Stores the Controller Link data link status information.

96 bits

IR 190 to IR 195

IR 19000 to IR 19515

Status Area 2: Stores the Controller Link error and network participation information.

Input area

64 bits

IR 096 to IR 099

IR 09600 to IR 09915

Used when the MACRO instruction, MCRO(99), is used.

Output area

64 bits

IR 196 to IR 199

IR 19600 to IR 19915

Inner Board slot 1 area 256 bits

IR 200 to IR 215

IR 20000 to IR 21515

These bits are allocated to the Inner Board mounted in slot 1 of a CQM1H-CPU51/61. High-speed Counter Board: IR 200 to IR 213 Serial Communications Board: IR 200 to IR 207

Analog settings area

64 bits

IR 220 to IR 223

IR 22000 to IR 22315

Used to store the analog settings when a CQM1H-AVB41 Analog Setting Board is mounted.

High-speed Counter 0 32 bits PV

IR 230 to IR 231

IR 23000 to IR 23115

Used to store the present values of high-speed counter 0.

Inner Board slot 2 area 192 bits

IR 232 to IR 243

IR 23200 to IR 24315

These bits are allocated to the Inner Board mounted in slot 2. High-speed Counter Board: IR 232 to IR 243 Absolute Encoder Interface Board: IR 232 to IR 239 Pulse I/O Board: IR 232 to IR 239 Analog I/O Board: IR 232 to IR 239

SR area

184 bits

SR 244 to SR 255

SR 24400 to SR 25507

These bits serve specific functions such as flags and control bits.

HR area

1,600 bits

HR 00 to HR 99 HR 0000 to HR 9915

These bits store data and retain their ON/OFF status when power is turned OFF or when the operating mode is changed.

AR area

448 bits

AR 00 to AR 27 AR 0000 to AR 2715

These bits serve specific functions such as flags and control bits.

TR area

8 bits

---

These bits are used to temporarily store ON/OFF status at program branches.

LR area

1,024 bits

LR 00 to LR 63 LR 0000 to LR 6315

Used for 1:1 data link through the RS-232 port or through a Controller Link Unit.

Timer/Counter area

512 bits

TIM/CNT 000 to TIM/CNT 511 (timer/counter numbers)

The same numbers are used for both timers and counters. Timer numbers 000 to 015 can be used with TIMH(15) for interrupt-refreshed PVs to ensure proper timing without inaccuracy being caused by the cycle time.

Controller Link status areas

MACRO operand area

16

TR 0 to TR 7

Page 14

CPU Unit Descriptions Data area DM area

Read/ write

Size

Specifications Words

Bits

Function

3,072 words

DM 0000 to DM 3071

---

DM area data can be accessed in word units only. Word values are retained when the power is turned OFF.

3,072 words

DM 3072 to DM 6143

---

Available in CQM1H-CPU51/61 CPU Units only.

Readonly4

425 words

DM 6144 to DM 6568

---

Cannot be written from the program (only from a Programming Device). DM 6400 to DM 6409: Controller Link parameters DM 6450 to DM 6499: Routing tables DM 6550 to DM 6559: Serial Communications Board Setup

Error history area4

31 words

DM 6569 to DM 6599

---

Cannot be written from the program (only from a Programming Device). Stores the time of occurrence and error code of errors that occur.

PLC Setup4

56 words

DM 6600 to DM 6655

---

Cannot be written from the program (only from a Programming Device). Stores various parameters that control PLC operation.

6,144 words

EM 0000 to EM 6143

---

EM area data can be accessed in word units only. Word values are retained when the power is turned OFF or the operating mode is changed. (CQM1H-CPU61 CPU Unit only.)

EM area

Memory Cassette Specifications Item Memory Cassette (EEPROM or flash memory)

Details Mounted from the front of the CPU Unit and used to store and read the user’s program, DM (read-only DM and PLC Setup), and expansion instruction information as one block. It is possible to set the CPU Unit so that data stored in the Memory Cassette (user’s program, DM, expansion instruction information) is automatically sent to the CPU Unit (autoboot) at startup. Transfer and comparison of data between the CPU Unit and Memory Cassette are possible using AR area control bits.

Other Functions Item Macro instructions

Specification Subroutines called by instructions containing arguments.

Min. cycle time

1 to 9,999 ms (Unit: 1 ms)

Cycle time monitoring

When the cycle time exceeds 100 ms, the Cycle Time Over Flag turns ON, and operation continues. (A setting can be made in the PLC Setup so that this error is not generated.) When the cycle time exceeds the cycle monitor time, operation is stopped. Cycle monitor time settings: 0 to 990 ms in 10-ms units, 0 to 9,900 ms in 100-ms units, 0 to 99 s in 1-s units.

I/O refreshing

Cyclic refreshing, refreshing by IORF(97), direct output refreshing (set in the PLC Setup), interrupt input refreshing. (The inputs that are refreshed can be set separately for input interrupts, high-speed counter interrupts, and interval timer interrupts in the PLC Setup.)

I/O memory status when changing operating mode

Depends on the ON/OFF status of the I/O Hold Bit (SR 25212).

Load OFF

All outputs on Output Units can be turned OFF when the CPU Unit is operating in RUN, MONITOR, or PROGRAM mode. (Used for stopping output in emergencies, for debugging, etc.)

User-customized DIP switch setting

A pin setting on the DIP switch on the front of the CPU Unit is stored in AR 0712. This setting can be used as an ON/OFF condition (e.g., to switch between trial operation and actual operation).

Mode setting at power-up

Possible

Note: The maximum and current values of the cycle time are stored in the AR area.

Debugging

Forced set/reset, differential monitoring, data tracing (scheduled, cyclic, or when instruction is executed).

Online editing

User programs can be overwritten in program-block units when the CPU Unit is in MONITOR mode. With the CX-Programmer, more than one program block can be edited at the same time.

Program protection

Write-protection of user program and data memory (DM 6144 to DM 6655: read-only DM): Set using pin 1 of the DIP switch.

Error check

User-defined errors (i.e., user can define fatal errors and non-fatal errors using the FAL(06) and FALS(07) instructions.) (It is possible to stop operation using FALS(07) for fatal errors. User-defined error logs can be created in specific bits (logging) when using FAL(06).

Error log

Up to 10 errors (including user-defined errors) are stored in the error log. Information includes the error code, error details, and the time the error occurred.

17

Page 15

CPU Unit Descriptions Item

Specifications Specification

Serial communications Built-in peripheral port: Programming Device (including Programming Console) connections, Host Links, no-protocol communications Built-in RS-232C port: Programming Device (excluding Programming Console) connections, Host Links, no-protocol communications, NT Links (1:1 mode), 1:1 Data LInks RS-232C port and RS-422A/485 port on Serial Communications Board (sold separately): Programming Device (excluding Programming Console) connections, Host Links, no-protocol communications, NT Links (1:1 mode, 1:N mode), 1:1 Data LInks, protocol macros Serial communications CQM1H CPU Unit’s built-in port modes

Built-in Built-in Serial peripheral port RS-232C port Communications Board ports

Programming Console bus

Connects to Programming Console.

YES (pin 7 OFF)

No

No

Peripheral bus

Connects to a computer running CX-Programmer or other Support YES Software. (Automatically used if the network type is set to periph- (pin 7 ON) eral bus on the Support Software.)

No

No

Host Link (SYSMAC WAY)

Enables reading/writing CPU Unit I/O memory or program using Host Link commands. Computers running Support Software or OMRON Programmable Terminals can also be connected. PLCinitiated communications are possible.

YES (pin 7 ON)

YES

YES

No-protocol

Enables sending or receiving up to 256 bytes of data without a pro- YES tocol or data conversion. A start code, end code, and transmission (pin 7 ON) delay can be set.

YES

YES

1:1 data link

Enables 1:1 data link with a CQM1H, CQM1, CPM-series, C200HX/HG/HE, C200HS, or SRM1 PLC.

YES

YES

NT links (1:1 and 1:N)

Enables 1:1 or 1:N communications with OMRON Programmable No Terminals without additional programming.

YES (1:1 only)

YES (1:1 and 1:N)

Protocol macros

Enables user-created protocols to communicate with essential any No device equipped with a serial communications port (e.g., RS232C). Standard protocols are also provided.

No

YES

No

Clock

Some Memory Cassette are equipped with a clock. (The time of the error will recorded if a clock is used.

Input time constants

Used to set the ON (or OFF) response times for DC Input Units. Settings: 1, 2, 4, 8, 16, 32, 64, and 128 ms.

Power OFF detection time

AC power supply: 10 to 25 ms (not fixed), DC power supply: 5 to 25 ms (not fixed)

Memory protection

Held Areas: Holding bits, contents of Data Memory and Extended Data Memory, and status of the counter Completion Flags and present values. Note: If the I/O Hold Bit (SR 25212) is turned ON, and the PLC Setup is set to maintain the I/O Hold Bit status when power is turned ON, the contents of the IR area and the LR area will be saved.

Commands to a host computer

Host Link command responses can be sent to a computer connected via the Host Link System using the TXD(––) (communications port output) instruction.

Remote programming and monitoring

Host Link or peripheral bus communications via a CPU Unit’s serial communications port can be used for remote programming and remote monitoring of the PLC through a Controller Link System. (This function is, however, not supported for the serial communications ports on the Serial Communications Board.)

Program check

Program is checked at the beginning of operation for items such as no END(01) instruction and instruction errors. CXProgrammer can also check programs. (The level of program checking can be set.)

Battery life

5 years at 25°C (Depends on the ambient temperature and power supply conditions. Min.: 1 yr) Battery replacement must be performed within 5 minutes.

Errors from self-diagnostics

CPU (watchdog timer), I/O verification, I/O bus, memory, FALS system (FALS execution or cycle monitor time over), FAL system (FAL execution or PLC Setup error etc.), battery, cycle time over and communications port.

Other functions

Storage of number of times power has been interrupted. (Stored in AR area.)

18