The text of a spec sheet · part 3 of 3
Micro Programmable Controller CPM1A, pages 17 to 22
Pages 17 to 22 of 22
The original document is the PDF (432 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron CPM1A-TS101-DA
Page 17
CPM1A
CPM1A Program Example 1.
Analog timer for 0.0 to 20.0 seconds
2.
A
Analog timer for 0.0 to 60.0 seconds
25313(ON) TIM 000
250
BCD multiplication
MUL(32) 250 #0003 DM0500
Value of the analog setting 0 (0 to 200)
Value of the analog setting 0 (0 to 200) Triples the above value Multiplication result (0 to 600)
B TIM 001
DM 0500
J PULSE OUTPUT FUNCTION The CPM1A transistor output models have an output function capable of outputting a pulse of 20 Hz to 2 kHz (single-phase output). When used in combination with a Stepping Driver or Servodriver, positioning can be easily performed.
Program Example 1 scan turns ON. 25315 MOV(21) #5000 DM 0000
Application Example
MOV(21) #0002 DM 0001
Changing the speed of the Stepping Motor.
Sets the number of output pulses as 25,000 (times) in the data memory area.
DM 0001 0
0
0
DM 0000 2
5
0
0
MOV(21) #0200 DM 0100
Sets the initial frequency to 2,000 pulses/second.
PULS(65) 000 000 DM 0000
Pulse rate setting
@SPED(64) 000 000 DM 0100
Frequency conversion:
0
25315 Output point 01000 or 01001
1 scan turns ON.
00200 15000
Stepping Motor Driver
Speed change limit switch 00001 MOV(21) #0020 DM 0100
Stepping Motor
Pulse rate (BCD 8 digits)
Output port (output point 01000) Output mode (single) Frequency data (x 10 Hz) Changes to 200 Hz when the limit switch is turned ON.
25,000 pulses
ÉÉÉÉÉÉ ÉÉÉÉÉÉ ÉÉÉÉÉÉ ÉÉÉÉÉÉ
15000
Output 1 khzZ frequency
200 Hz
00000 turns ON
Pulse rate
0001 turns ON (limit switch)
17
Page 18
CPM1A
CPM1A
Communications J NT LINK FOR PROGRAMMABLE TERMINALS Use Omron’s high-speed NT Link for real-time communications between the CPM1A and a Programmable Terminal. Programmable Terminal
RS-232C Adapter
Communication Cable C200H-CN320-EU (2 m) C200H-CN520-EU (5 m) CPM1A CPU
J HOST LINK COMMUNICATIONS CPM1A Host Link communications consist of interactive procedures whereby the CPM1A returns a response to a command sent from the IBM PC/AT or compatible computer. These communications allow the IBM PC/AT or compatible computer to read and write in the CPM1A’s I/O Areas and Data Memory Areas as well as in areas containing the status of various settings.
Command
1:1 Host Link Communications
Response
C200HS-CN220-EU cable (2 m)
RS-232C Adapter
CPM1A CPU
1:N Host Link Communications
Response
Command
Computer with a RS-422/RS-485 communications port
RS-422 Adapter
18
CPM1A CPU
RS-422 Adapter
CPM1A CPU
RS-422 Adapter
CPM1A CPU
Page 19
CPM1A
CPM1A J 1:1 CONNECTIONS FOR DATA EXCHANGE
With a 1:1 Link, two CPM1As or a CPM1A and CQM1 or C200Hj are connected 1:1 with one side as the Master and the other as the Slave to provide an I/O link of a maximum of 256 points (LR 0000 to LR 1515).
Example of a 1:1 Link between CPM1As Communication Cable C200H-CN320-EU (2 m)
RS-232C Adapter
CPM1A CPU
RS-232C Adapter
CPM1A CPU
Master
Slave
Link bits
Link bits
WRITE area
READ area
LR 00 WRITE
LR 00
LR 07 LR 08 WRITE area
READ area
READ
READ LR 07 LR 08
LR 15
WRITE LR 15
Limitations of the CPM1A 1:1 Link CPM1A I/O links are limited to 16 words (LR 00 to LR 15). Therefore, use these 16 words (LR 00 to LR 15) on the CQM1 or C200Hj side when forming 1:1 links with a CQM1 or C200Hj.
J PROGRAM TRANSFER UNIT Use Omron’s EEPROM program transfer unit to update programs in machines or program multiple controllers with the same program. The CPM1-EMU01-V1 Expansion Memory Unit connects to the peripheral port of micro and small PLCs.
Uploading Downloading
EEPROM Omron SRM1, CPM1A, CPM2A, CPM2B, CPM2C and CQM1H programmable controllers
19
Page 20
CPM1A
CPM1A
Instruction Set J SEQUENCE INSTRUCTIONS
J DATA CONVERSION INSTRUCTIONS
Sequence Input Instructions
Instruction
Mnemonic
Code
Instruction
Code
BCD TO BINARY
BIN(@)
23
BCD(@)
24
Mnemonic
LOAD
LD f
BINARY TO BCD
LOAD NOT
LD NOT f
4 TO 16 DECODER
MLPX(@)
76 f
16 TO 4 DECODER
DMPX(@)
77
ASC(@)
86
AND
AND
AND NOT
AND NOT f
ASCII CODE CONVERT
OR
OR f
Data Comparison Instructions
OR NOT
OR NOT f
Mnemonic
Code
AND LD f
Instruction
AND LOAD
CMP
20
OR LOAD
OR LD f
COMPARE DOUBLE COMPARE
CMPL
60
Sequence Output Instructions
BLOCK COMPARE
BCMP(@)
68
Instruction
Mnemonic
Code
TABLE COMPARE
TCMP(@)
85
OUTPUT
OUT f
OUT NOT
OUT NOT f
J BCD/BINARY CALCULATION
SET
SET f
Instruction
Mnemonic
Code
RESET
RSET f
BCD ADD
ADD(@)
30
KEEP
KEEP
11
BCD SUBTRACT
SUB(@)
31
DIFFERENTIATE UP
DIFU
13
BCD MULTIPLY
MUL(@)
32
DIFFERENTIATE DOWN
DIFD
14
BCD DIVIDE
DIV(@)
33
BINARY ADD
ADB(@)
50
BINARY SUBTRACT
SBB(@)
51
BINARY MULTIPLY
MLB(@)
52
BINARY DIVIDE
DVB(@)
53
DOUBLE BCD ADD
ADDL(@)
54
DOUBLE BCD SUBTRACT
SUBL(@)
55
DOUBLE BCD MULTIPLY
MULL(@)
56
DOUBLE BCD DIVIDE
DIVL(@)
57
Sequence Control Instructions Instruction
Mnemonic
Code
NO OPERATION
NOP
00
END
END
01
INTERLOCK
IL
02
INTERLOCK CLEAR
ILC
03
JUMP
JMP
04
JUMP END
JME
05
J DATA MOVEMENT INSTRUCTIONS
J TIMER/COUNTER INSTRUCTIONS
Instruction
Mnemonic
Code
Instruction
Mnemonic
Code
MOVE
MOV(@)
21
TIMER
TIM f
MOVE NOT
MVN(@)
22
COUNTER
CNT f
BLOCK TRANSFER
XFER(@)
70
REVERSIBLE COUNTER
CNTR
12
BLOCK SET
BSET(@)
71
HIGH-SPEED TIMER
TIMH
15
DATA EXCHANGE
XCHG(@)
73
SINGLE WORD DISTRIBUTE
DIST(@)
80
J STEP INSTRUCTIONS Instruction
Mnemonic
DATA COLLECT
COLL(@)
81
Code
MOVE BIT
MOVB(@)
82
MOVD(@)
83
STEP DEFINE
STEP
08
MOVE DIGIT
STEP START
SNXT
09
Note: f:
Instruction
Mnemonic
Code
INCREMENT
INC(@)
38
DECREMENT
DEC(@)
39
J INCREMENT/DECREMENT
20
Instruction keys allocated to the Programming Console. (@): Instruction can be differentiated using input rise time to execute the instruction in just one cycle.
Page 21
CPM1A
CPM1A J LOGIC INSTRUCTIONS
J PERIPHERAL DEVICE CONTROL
Instruction
Mnemonic
Code
I/O Unit Instructions
COMPLEMENT
COM(@)
29
Instruction
Mnemonic
Code
LOGICAL AND
ANDW(@)
34
7-SEGMENT DECODER
SDEC(@)
78
LOGICAL OR
ORW(@)
35
I/O REFRESH
IORF(@)
97
EXCLUSIVE OR
XORW(@)
36
EXCLUSIVE NOR
XNRW(@)
37
Instruction
Mnemonic
Code
MESSAGE
MSG
46
J SHIFT INSTRUCTIONS
Display Instruction
Instruction
Mnemonic
Code
High-speed Counter Control Instructions
SHIFT REGISTER
SFT f/10
Instruction
Mnemonic
Code
WORD SHIFT
WSFT(@)
16
MODE CONTROL
INI(@)
61
ASYNCHRONOUS SHIFT REGISTER
ASFT(@)
17
PV READ
PRV(@)
62
ARITHMETIC SHIFT LEFT
ASL(@)
25
COMPARE TABLE LOAD
CTBL(@)
63
ARITHMETIC SHIFT RIGHT
ASR(@)
26
ROTATE LEFT
ROL(@)
27
ROTATE RIGHT
ROR(@)
28
Instruction
Mnemonic
Code
ONE DIGIT SHIFT LEFT
SLD(@)
74
SPEED OUTPUT
SPED(@)
64
ONE DIGIT SHIFT RIGHT
SRD(@)
75
SET PULSES
PULS(@)
65
REVERSIBLE SHIFT REGISTER
SFTR(@)
84
Pulse Output Control Instructions
J DAMAGE DIAGNOSIS INSTRUCTIONS
J SPECIAL CALCULATION INSTRUCTION
Instruction
Mnemonic
Code
Instruction
Mnemonic
Code
FAILURE ALARM
FAL(@)
06
BIT COUNTER
BCNT(@)
67
SEVERE FAILURE ALARM
FALS
07
J SPECIAL SYSTEM INSTRUCTIONS
J SUBROUTINE INSTRUCTIONS Instruction
Mnemonic
Code
Instruction
Mnemonic
Code
SUBROUTINE ENTER
SBS(@)
91
SET CARRY
STC(@)
40
SUBROUTINE ENTRY
SBN
92
CLEAR CARRY
CLC(@)
41
SUBROUTINE RETURN
RET
93
MACRO
MCRO
99
J INTERRUPT CONTROL INSTRUCTIONS Instruction
Mnemonic
Code
INTERVAL TIMER
STIM(@)
69
INTERRUPT CONTROL
INT(@)
89
Note: f:
Instruction keys allocated to the Programming Console. (@): Instruction can be differentiated using input rise time to execute the instruction in just one cycle.
21
Page 22
CPM1A
CPM1A
J SUMMARY OF FUNCTION CODES The following table lists the CPM1A instructions that have fixed function codes. Each instruction is listed by mnemonic and by instruction name. Use the numbers in the leftmost column as the left digit and the number in the column heading as the right digit of the function code. Left digit
Right digit 0
1
2
3
4
5
6
7
8
9
0
NOP No operation
END End
IL Interlock
ILC Interlock clear
JMP Jump
JME Jump end
FAL(@) Failure alarm and reset
FALS Severe failure alarm
STEP Step define
SNXT Step start
1
SFT Shift register
KEEP Keep
CNTR Reversible counter
DIFU Differentiate up
DIFD Differentiate down
TIMH Highspeed timer
WSFT(@) Word shift
ASFT(@) Asynchronous shift register
---
---
2
CMP Compare
MOV(@) Move
MVN(@) Move not
BIN(@) BCD to binary
BCD(@) Binary to BCD
ASL(@) Shift left
ASR(@) Shift right
ROL(@) Rotate left
ROR(@) Rotate right
COM(@) Complement
3
ADD(@) BCD add
SUB(@) BCD subtract
MUL(@) BCD multiply
DIV(@) BCD divide
ANDW (@) Logical AND
ORW(@) Logical OR
XORW (@) Exclusive OR
XNRW (@) Exclusive NOR
INC(@) Increment
DEC(@) Decrement
4
STC(@) Set carry
CLC(@) Clear carry
---
---
---
---
MSG(@) Message display
---
---
---
5
ADB(@) Binary add
SBB(@) Binary subtract
MLB(@) Binary multiply
DVB(@) Binary divide
ADDL(@) Double BCD add
SUBL(@) Double BCD subtract
MULL(@) Double BCD multiply
DIVL(@) Double BCD divide
---
---
6
CMPL Double compare
INI(@) Mode control
PRV(@) Highspeed counter PV read
CTBL(@) Comparison table load
SPED(@) Speed output (See Note)
PULS(@) Set pulses (See Note)
---
BCNT(@) Bit counter
BCMP(@) Block compare
STIM(@) Interval timer
7
XFER(@) Block transfer
BSET(@) Block set
---
XCHG(@) Data exchange
SLD(@) One digit shift left
SRD(@) One digit shift right
MLPX(@) 4-to-16 decoder
DMPX(@) 16-to-4 encoder
SDEC(@) 7-segment decoder
---
8
DIST(@) Single word distribute
COLL(@) Data collect
MOVB(@) Move bit
MOVD(@) Move digit
SFTR(@) Reversible shift register
TCMP(@) Table compare
ASC(@) ASCII convert
---
---
INT(@) Interrupt control
9
---
SBS(@) Subroutine entry
SBN Subroutine define
RET Subroutine return
---
---
---
IORF(@) I/O refresh
---
MCRO (@) Macro
Note: Only for the CPM1A transistor output models.
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
R
OMRON ELECTRONICS LLC
OMRON CANADA, INC.
One East Commerce Drive Schaumburg, IL 60173
885 Milner Avenue Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GC MSPLC1
22
03/01
Specifications subject to change without notice.
Printed in U.S.A.