Spec sheet · Leuze
Leuze PRK 97/4 Spec Sheet
Spec sheet2 pagesPDF 87 KB
Both pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
A two-page Leuze electronic data sheet for the PRK 97 series of retro-reflective photoelectric sensors with polarisation filter. Besides the PRK 97/4 it lists the PRK 97/4 L, PRK 97/4 L.1, PRK 97/4 S, PRK 97/4 DS, PRK 97/4 DS.1, PRK 97/4 DL, PRK 97/4.8 L, PRK 97/44 L and PRK 97/2 L with their part numbers. It gives the features, optical, electrical, mechanical and environmental data, operating ranges with each reflector, accessories and a selection table.
- Device
- Polarised retro-reflective photoelectric sensor with visible red light p. 1
- Supply voltage
- 10 … 30VDC (incl. residual ripple) p. 2
- Output
- PNP or NPN transistor output, light/dark switching; PRK 97/44 L with complementary outputs p. 2
- Range
- Typical operating range limit 0.1 … 6m with a TK(S) 100x100 reflector p. 2
- Operating range by reflector
- TK(S) 100x100: 0.1 … 4m; MTK(S) 50x50: 0.1 … 3m; TK(S) 30x50: 0.1 … 1.7m; TK(S) 20x40: 0.1 … 1.4m; Tape 2 100x100: 0.15 … 1.4m p. 2
- Light source
- LED (modulated light), 660nm visible red light, polarised p. 2
- Connection
- M12 connector 4-pin (stainless steel), 4-pin connector, or 2m cable (cross section 3x0.25mm²) p. 2
- Sensitivity
- PRK 97/4 L.1 only: adjustable with a 12-turn potentiometer, for detecting transparent objects p. 1, 2
- Housing
- Robust metal housing with glass cover p. 1
- Enclosure
- IP 67/IP 65 (for all S types) p. 2
- Part numbers
- PRK 97/4 500 80994; PRK 97/4 L 500 19663; PRK 97/4 L.1 500 25324; PRK 97/4 S 500 17092; PRK 97/4 DS 500 81305; PRK 97/4 DS.1 500 25686; PRK 97/4 DL 500 29642; PRK 97/4.8 L 500 80474; PRK 97/44 L 500 35301; PRK 97/2 L 500 29641 p. 2
- Accessories
- Mounting systems (BT 92, UMS 1, UMS 96-95), diaphragm (BL 97.1), M12 connectors (KD …), ready-made cables (KB …), reflectors, reflective tapes, sold separately p. 1
Good to know
- The PRK 97/4 S and PRK 97/4 DS are shipped with a cable connector. p. 2
- The operating range is the recommended range with performance reserve; the typical range limit is the maximum without reserve. p. 2
Questions this sheet answers
What voltage does the Leuze PRK 97/4 need?
10 to 30 VDC, including residual ripple. p. 2
Is the PRK 97 output PNP or NPN?
The series has PNP or NPN transistor outputs with light/dark switching; the PRK 97/44 L has complementary outputs. p. 2
How far can the PRK 97/4 see a reflector?
Up to 6 m as a typical limit with a TK(S) 100x100 reflector; the recommended range with that reflector is 0.1 to 4 m. p. 2
Can the PRK 97 detect transparent objects?
The data sheet says its adjustable sensitivity allows detection of transparent objects; the sensitivity adjustment is only on the PRK 97/4 L.1. p. 1
What is the part number of the PRK 97/4 L?
500 19663. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
Leuze electronic PRK 97
Retro-reflective photoelectric sensors with polarisation filter Dimensioned drawing
0.1 … 6m 10 - 30 V DC
! Polarised retro-reflective photoelectric sensors with visible red light ! Small construction with glass cover and robust metal housing for protection against environmental influences ! Adjustable sensitivity with high resolution allows detection of transparent objects ! Connection via M12 connector, plug or cable ! Activation input for testing and interlinking
A B C
We reserve the right to make changes • 97_b02e.fm
ISO 9001IEC 60947...C
Sensitivity adjustment (only PRK 97/4 L.1) Indicator diode Optical axis
Electrical connectionUL US LISTEDIEC 60947...IP 67
Accessories: (available separately)
! Mounting systems (BT 92, UMS 1, UMS 96-95) ! Diaphragm (BL 97.1) ! M12 connectors (KD …) ! Ready-made cables (KB …) ! Reflectors ! Reflective tapes
Leuze electronic GmbH + Co KG www.leuze.de
Post-box 1111 D-73277 Owen-Teck Tel. ++49 7021 5730
PRK 97… - 05
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
Leuze electronic PRK 97 Specifications
TablesOptical dataReflectors
Typ. operating range limit (TK(S) 100x100) 1) 0.1 … 6m Operating range 2) see table Light source LED (modulated light) Wavelength 660nm (visible red light, polarised)
Timing Switching frequency Response time Delay before start-up
200Hz 2.5ms ≤ 100ms
Electrical data Operating voltage UB Residual ripple Bias current Switching output Function characteristics
10 … 30VDC (incl. residual ripple) ≤ 15% of UB ≤ 30mA PNP or NPN transistor output light/dark switching (PRK 97/44 L with complementary outputs) ≥ (UB -2V)/≤ 2V max. 100mA adjustable with 12-turn potentiometer for PRK 97/4 L.1
Signal voltage high/low Output current Sensitivity
1 2 3 4 5
TK(S) 100x100 0.1 … 4m MTK(S) 50x50 0.1 … 3m TK(S) 30x50 0.1 … 1.7m TK(S) 20x40 0.1 … 1.4m Tape 2 100x100 0.15 … 1.4m
1 2 3 4 50.1 0.1 0.1 0.1 0.154 3 2.61.7 1.4 1.46 4.52.1 2.4
Operating range [m] Typ. operating range limit [m]
TK … TKS … Tape 2
Indicators LED yellow LED yellow flashing
Operating range
= adhesive = screw type = adhesive
light path free light path free, no performance reserve
Mechanical data diecast zinc glass 85g M12 connector 4-pin, stainless steel, connector 4-pin or cable 2m (cross section 3x0.25mm²)
Environmental data Ambient temp. (operation/storage) Protective circuit 3) VDE safety class 4) Protection class LED class Standards applied
-20°C … +60°C/-30°C …+70°C 2, 3 I (for S types) II, all-insulated (for all L and cable types) IP 67/IP 65 (for all S types) 1 (acc. to EN 60825-1) IEC 60947-5-2
Diagrams Typ. response behaviour (TK 100x100) Misalignment y [mm]
Housing Optics cover Weight Connection type
150 100 y250 0 -50y1-100 -150 0123456Distance x [m]Options y2
Activation input active Transmitter active/not active
≥ 8V/≤ 2V or not connected
y1 x
1) Typ. operating range limit: max. attainable range without performance reserve 2) Operating range: recommended range with performance reserve 3) 2=polarity reversal protection, 3=short-circuit protection for all outputs 4) Rating voltage 250VAC
PRK 97… - 05!!!!!!!!! !!!!!! !!!! !!
PRK 97/4 DS Part No. 500 81305
!
PRK 97/44 L Part No. 500 35301
PRK 97/4 L.1 Part No. 500 25324
!
PRK 97/2 L Part No. 500 29641
PRK 97/4 Part No. 500 80994
Equipment # Switching output PNP transistor NPN transistor Switching light switching dark switching compl. switch. outputs Connection M12 connector cable plug Features activation input sensitivity UL
PRK 97/4 DL Part No. 500 29642
Order code "
PRK 97/4 DS.1 Part No. 500 25686
! PRK 97/4 S and PRK 97/ 4 DS are shipped with cable connector.
PRK 97/4 S Part No. 500 17092
Selection table PRK 97/4 L Part No. 500 19663
Remarks PRK 97/4.8 L Part No. 500 80474
Order guide!!! !!! !! !!!!!?! !?!! 0501