Bar Code Reader BCL 40 with Integrated Decoder, Connector Unit MA 10: Technical Description, pages 62 to 69

Pages 62 to 69 of 94: 8 Operation; 9 Communicating with the Device

The original document is the PDF (1.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Leuze BCL-40

Page 62

Leuze electronic

Operation

8

Operation

8.1

Display Elements On the back side of the MA 10, there are 4 LEDs which display the momentary operating status. LED

Colour

Meaning

RDY green

Ready

ERR yellow

Error

ACT red

Scanner active

DEC green

Decoding successful

Status conditions of the LEDs All four LEDs illuminate • for approx. 0.5 second after connecting the operating voltage. • after accepting a "cold start" reset (> 4s) up until the reset button is released.

All four LEDs blink • if the connection between the MA 10 and BCL 40 is interrupted.

RDY blinks • during the "Power On" function test.

RDY illuminates • when the devices are ready.

ERR illuminates • if a hardware error is encountered after the initialisation phase or in the case of a serious software error.

RDY and ERR blink simultaneously • when the setup program is activated. Notice: No read operations can be carried out.

RDY and ERR blink alternately • when the "autoConfig" function is activated by setting the corresponding DIP switch. • when a reference code is defined (Teach-In).

ACT illuminates • while the scanner is active, i.e. when the laser is in operation.

ACT blinks • if a warning is output during the 'autoControl' function.

DEC illuminates • for approx. 0.5 second after successfully completing a decoding process.

60

BCL 40

Leuze electronic

Page 63

Leuze electronic 8.2

Operation

Important Functions During Operation The BCL 40 has a function which automatically monitors the reading quality as well as the quality of the bar code label.

"autoControl" function When the "autoControl" function is active, the BCL 40 constantly compares the total number of scans with the number of decoded scans. If the number of decodable scans falls below a user defined percent of the total scans, the MA 10 outputs a warning: • the ACT LED blinks. • a warning symbol can be output to the host. • a switched output can be controlled. A detailed description of all adjustable parameters can be found in chapter 9.

8.3

Error Handling Errors are visibly indicated on the MA 10 via the ERR LED (see chapter 7.2 "Function Test"). Further error, warning and status messages are transferred via the host interface or the terminal interface.

Types of errors Errors are divided up into the following types: • Warnings

Warnings Warnings indicate temporary operating faults which do not effect the proper functioning of the device.

Serious errors Serious errors impair the proper functioning of the device. The device must be reinitialised.

Troubleshooting Isolated warnings can be ignored, since the BCL 40 will continue to function properly. Following a serious error, you should reinitialise the BCL. It will then usually again function properly. If a hardware problem is present, the BCL 40 will not reinitialise. Warnings and errors which occur frequently can be corrected easiest using the "BCL Configuration Tool" configuration and control software. If you cannot correct faults and errors with the software, please contact a Leuze electronic sales office or service facility. For addresses, please refer to the back page of this operating manual. Leuze electronic

BCL 40

61

TNT 35/7-24V

• Serious errors

Page 64

Leuze electronic

Communicating with the Device

9

Communicating with the Device Device parameters can be set via commands or using the easy-to-use "BCL Configuration Tool" control software.

9.1

Installation of the "BCL Configuration Tool" software © Place the installation CD in your CD drive. © Call up the installation file (e.g. Setup.exe) The following window appears:

Installation window

Figure 9.1:

Installation window

© Confirm the following licence agreement and select the installation path in the following window:

62

BCL 40

Leuze electronic

Page 65

Leuze electronic

Communicating with the Device

Installation directory

Figure 9.2:

Installation directory

© Confirm your entry with Continue, then follow the installation routine. For further details please refer to online help of the "BCL Configuration Tool" software.

Graphic configuration using the "BCL Configuration Tool" software In the following, you will find an overview and brief explanation of the adjustment options offered on the individual tabs.

Leuze electronic

BCL 40

63

TNT 35/7-24V

9.2

Page 66

Leuze electronic

Communicating with the Device 9.2.1

Code menu

Figure 9.3:

64

"Decode" menu, standard setting

Option

Explanation

Code table

Here, the codes which are to be decoded are set. As of software version V51.03 of BCL 40, the codes depicted above are enabled by default. We recommend enabling only the code types which are to actually be read with the corresponding element numbers. Notice: Code1 must always be selected. If multiple code types are to be used, set in sequential order: Code1, Code2…

Element number

In the field Element number, up to 3 element entries may be entered. An area is represented by a dashed line: e.g. 4-40 digits. With 2 or 3 different element entries by a comma: e.g: 8,13 digits Both are possible as well: e.g.: 4-10,20 digits Notice: If the code EAN128 is to be read, 3 additional digits are to be set for the code identifier.

Properties

Behind the "Properties" button, to the right of the respective code, the code-specific settings, such as the check digit, can be selected.

Number of bar codes

Here, the number of the bar codes to be decoded within a read cycle (one reading gate) is set.

BCL 40

Leuze electronic

Page 67

Leuze electronic

Communicating with the Device

Attention! Due to its internal design (hardware-ASIC-decoding), only one double-width code may be enabled for the BCL40. Double-width codes are the codes Code 2/5 Interleaved, Code 39 and Codabar. This means that only one of these three code types may be enabled!

Properties of the Code menu

Properties of the Decode menu, standard setting

Option

Explanation

Min wide narrow ratio

This value may be changed only in special cases!

Quiet zone size

Quiet zone: the area to the left and right of the bar code Module: width of the narrowest line in the bar code According to the code specifications, each bar code must have a quiet zone which is 10x as wide as the module of the bar code. Ex: for a code having a module of 0.5mm, 5mm blank space must be present at both the left and right of the code. By default, the scanner checks the a quiet zone which is 7 times greater than the module. This means that 7x or greater is o.k.

Scans between info

Number of scans which return no decodable data for a given label which must be performed before further data are classified as belonging to a different label. In this way it is possible to differentiate between sequential labels with identical data. This setting does not need to be changed in normal use.

Reading security (equal scans)

Specifies how often a code must be decoded before the result is valid and output. This value can be increased for inspection and test purposes.

Leuze electronic

BCL 40

65

TNT 35/7-24V

Figure 9.4:

Page 68

Leuze electronic

Communicating with the Device 9.2.2

Output menu

Figure 9.5:

66

"Output" menu

Option

Explanation

Output header

Select from the options listed below. The output header is sent in a separate message before the read result.

Label header

The Label header is set directly before the code data.

Label footer

The label footer is appended directly to the code data.

All labels in one message

If this item is activated, all read codes are sent together with the output header in a complete message. -> The structure of this message string is depicted symbolically in the preview window.

No read string

This character is set for each unrecognised bar code. Multiple characters (= string) may be entered here. Up to 20 characters are possible.

Properties

Set the desired formatting modes and formatting characters as necessary.

BCL 40

Leuze electronic

Page 69

Leuze electronic 9.2.3

Communicating with the Device

Control

Figure 9.6:

"Control" menu, standard setting

Option

Explanation

Sensor 1

If this item is selected, the scanner can be activated via its switching input 1 (= trigger start reading gate).

Command characters

The standard online character for the trigger start is the "+" character. This character can be changed only via the tree structure.

Decode delay time

This point is usually used only for test purposes. After the time set here has passed, the scanner automatically reactivates itself following a reading gate end.

Deactivation Sensor 1

This item changes together with switching input 1 upon "Activation".

Command characters

The standard online character for the trigger end is the "-" character. This character can be changed only via the tree structure.

Leuze electronic

BCL 40

67

TNT 35/7-24V

Activation