Page 21
Installation and Network Layouts DL405 Slot Choices
3--3
For PLC systems with D4--430 and D4--440 CPUs, the ERM modules can reside in any I/O slot but only in the CPU-base. The D4--450 CPU allows the installation of the ERM module in the CPU-base or in local expansion bases. If the ERM module is used in a local expansion base, all bases in the system must be the “--1” type bases. The valid part numbers for these bases are D4--04B--1, D4--06B--1, and D4--08B--1. The “--1” on the end of the part number indicates that the base supports specialty modules including the ERM. The “--1” bases can be connected as local expansion bases or remote bases. They are not the same thing. Remote bases do not support the ERM modules!
405 CPU Slot 0
Slot 1
Slot 2
Slot 3
Module Type H4--ERM (--F)
H4--ERM (--F)
Base
D4--430/440
D4--450
D4--450
D4--04B, D4--04B--1
Usable CPU-Base Slots 0, 1, 2, 3
Usable Expansion Base Slots N/A
D4--06B, D4--06B--1
0, 1, 2, 3, 4, 5
N/A
D4--08B, D4--08B--1
0, 1, 2, 3, 4, 5, 6, 7
N/A
D4--04B
0, 1, 2, 3
N/A
D4--06B
0, 1, 2, 3, 4, 5
N/A
D4--08B
0, 1, 2, 3, 4, 5, 6, 7
N/A
D4--04B--1
0, 1, 2, 3
0, 1, 2, 3*
D4--06B--1
0, 1, 2, 3, 4, 5
0, 1, 2, 3, 4, 5*
D4--08B--1
0, 1, 2, 3, 4, 5, 6, 7
0, 1, 2, 3, 4, 5, 6, 7*
* You must use the “--1” base for the CPU-base and all local expansion bases. NOTE: Before installing the ERM module, confirm that your power budget will accommodate the added module. See the DL205 or DL405 User Manual for your PLC for more information about calculating the power budget. See Appendix A for the power consumption of the ERM modules.
Installation and Safety Guidelines
H4--ERM (--F)
CPU
Installation and Network Layouts
WARNING: Your system can be damaged if you install or remove system components before disconnecting the system power. To minimize the risk of equipment damage, electrical shock, or personal injury, always disconnect the system power before installing or removing any system component.
Page 22
3--4
Installation and Network Layouts
H4--ERM (--F) To insert the ERM module in a DL405 base, place the bottom tab of the module into Module Installation the notch at the bottom of the base. Pivot the module toward the base as shown below. Ensure that each module is tightly seated and secured with the captive screw at the top of the module. DL405 Base
Installation and Safety Guidelines
Installation and Network Layouts
Disconnect power before installing module!
Which Modules are The Ethernet remote I/O slaves accept the most commonly used I/O modules for the Supported in the DL205/DL405 system and Terminator I/O systems (AC, DC, AC/DC, Relay and Analog). The table below lists by category those modules that you may use in a Ethernet Slaves remote I/O slave. Module/Unit
Remote Base
Module/Unit
Remote Base
CPUs
No
No
DC Input Modules
Yes
Remote I/O Ethernet Remote Master
AC Input Modules
Yes
Ethernet Remote Slave (EBC)
CPU Slot Only
AC/DC Input Modules
Yes
Communications and Networking Modules
No
DC Output Modules
Yes
H2--CTRIO (205)
Yes
AC Output Modules
Yes
D4--HSC
Yes
Relay Output Modules
Yes
D2--CTRINT
No
Analog Modules
Yes
Thermocouple Module
Yes
RTD Module
Yes
NOTE: The User Manual for Analog I/O Modules discusses scan times for updating analog I/O data for modules installed in local bases. Please be aware that the scan times for updating are different for remote I/O modules installed in remote bases. The CPU scan is asynchronous with the remote scan by the master module. Thus, an analog input module installed in a remote base, for example, may not have its data updated by the CPU “once every scan per channel” as stated in the user manual. The CPU scan may, in fact, cycle several times while the remote scan is taking place. Take this into account in applications where the timing is critical.
Page 23
Installation and Network Layouts
3--5
ERM Network Layouts Each ERM module can support up to 16 remote slaves. The slaves supported are the H4--EBC(--F), H2--EBC(--F) and the T1H--EBC. A hub or repeater connects multiple slaves into a star topology. Multiple hubs or repeaters can be used to create a star--bus--star topology. Once the ERM I/O network is configured and running, the PC can be removed from the network. Configuring the Ethernet Remote I/O Network
Use a PC equipped with a 10BaseT or 10BaseFL network adapter card and the Ethernet Remote Master (ERM) Workbench software configuration utility that comes with this manual to configure the ERM module and its slaves over the ethernet remote I/O network.
PC running ERM WorkBench to configure the ERM network DirectLogic PLC or WinPLC ERM Module
DirectLogic DL205 I/O
Terminator I/O
Once the ERM I/O network is configured and running, the PC can be removed from the network. DirectLogic PLC or WinPLC ERM Module
DirectLogic DL205 I/O
Dedicated Hub for ERM Network
DirectLogic DL405 I/O
Terminator I/O
Installation and Safety Guidelines
Running the Ethernet Remote I/O Network
Installation and Network Layouts
DirectLogic DL405 I/O
Dedicated Hub for ERM network.
Page 24
3--6
Installation and Network Layouts
ERM / ECOM Systems
Keep ERM networks, multiple ERM networks and ECOM / office networks isolated from one another as shown below. Do not attempt to connect an ECOM module or non ERM Workbench PC to a hub that the dedicated ERM network is using. Having an ECOM module(s) on an ERM Ethernet network can adversely affect the reliability and the speed of the ERM slave I/O.
Keep ERM and ECOM modules on separate Networks! E R M
E C O M
PC for HMI or SCADA, etc.
Dedicated ERM Network
Installation and Safety Guidelines
Installation and Network Layouts
ECOM or Office Network
ECOM
Dedicated Hub for ERM Network
PC for Data Acquisition in MES, ERP or other business systems
Warning: We recommend using a dedicated Ethernet remote I/O network for the ERM and its slaves. While Ethernet networks can handle a very large number of data transmissions, and normally handle them very quickly, heavy Ethernet traffic can adversely affect the reliability of the slave I/O and the speed of the network.
Page 25
3--7
Installation and Network Layouts
Network Cabling ERM Supports Two Two types of ERMs are available. One type supports the 10BaseT standard, and the other supports the 10BaseFL standard. The 10BaseT standard uses twisted pairs of Standards copper wire conductors, and the 10BaseFL standard is for fiber optic cabling. 10BaseT
10BaseFL
Unshielded Twisted-Pair cable with RJ45 connectors
62.5/125 MMF fiber optics cable with ST-style connectors
Patch (Straight--through) Cable OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN
RJ45
OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN
1 2 3 4 5 6 7 8
TD+ TD-RD+ RD--
RJ45
Crossover Cable 1 2 3 4 5 6 78
8-pin RJ45 Connector (8P8C)
TD+ 1 TD-- 2 RD+ 3 4 5 RD-- 6 7 8
RJ45
OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN
GRN/WHT GRN TD+ 1 OR/WHT TD-- 2 RD+ 3 BLU 4 BLU/WHT 5 OR RD-6 BRN/WHT 7 BRN 8
RJ45
This diagram illustrates the standard wire positions in the RJ45 connector. We recommend all ERM 10BaseT cables to be Category 5, UTP cable.
Installation and Safety Guidelines
10BaseT
TD+ 1 TD-- 2 RD+ 3 4 5 RD-- 6 7 8
Installation and Network Layouts
10BaseT Networks The cable used to connect a PLC (or PC) to a hub or repeater is called a patch (straight-through) cable. The cable used to connect two Ethernet devices (Point--to--Point) together is a crossover cable. We recommend that you purchase cables pre-assembled with connectors for convenient and reliable networking.
Page 26
Installation and Network Layouts
3--8
Installation and Network Layouts
10BaseT Connections
Most 10BaseT hubs or repeaters use a patch (straight-through) cable for connecting the network devices (PLCs or PCs). For hub-to-hub connections a crossover type cable is commonly required. The figures on page 3--6 show pin assignments and insulation color codes for patch (straight-through) and crossover type Ethernet cables.
UTP Cable
The ERM has an eight-pin modular port that accepts RJ45 type connectors. UTP (Unshielded Twisted-Pair) cable is rated according to its data-carrying ability (bandwidth) and is given a “category” number. We strongly recommend using a category 5 cable for all ERM connections.
10BaseFL Connections
Each module has two bayonet ST-style connectors. The ST-style connector uses a quick release coupling which requires a quarter turn to engage or disengage. The connectors provide mechanical and optical alignment of fibers. Each cable segment requires two strands of fiber: one to transmit data and one to receive data. The ST-style connectors are used to connect the H2--ERM--F or H4--ERM--F module to another H2--ERM--F or H4--ERM--F module or a fiber optic hub or repeater.
Fiber Optic Cable
The H2--ERM--F and H4--ERM--F modules accept 62.5/125 multimode fiber optic (MMF) cable. The glass core diameter is 62.5 micrometers and the glass cladding is 125 micrometers. The fiber optic cable is highly immune to noise and permits communications over much greater distances than 10BaseT.
Fiber Optic Module ST Connector
Multimode Fiber Optic (MMF) Cable
Fiber cross-section
Ferrule
Transmit
Sheathing
Core
Installation and Safety Guidelines
Receive
62.5/125 MMF cable with bayonet ST-style connectors
Transmit
Receive
Connecting ERM to Slave
Cladding
Transmit
Receive
Page 27
Installation and Network Layouts
3--9
Maximum Cable Length The maximum distance per 10BaseT cable segment is 100 meters or 328 feet.
Repeaters extend the distance. Each cable segment attached to a repeater can be 100 meters. Two repeaters connected together extend the total range to 300 meters. The maximum distance per 10BaseFL cable segment is 2,000 meters or 6,560 feet (1.2 miles). Repeaters extend the distance. Each cable segment attached to a repeater can be 2,000 meters. Two repeaters connected together extend the total range to 6,000 meters.
10Base--T Ethernet Control Network shown (also supports 10Base--FL Networks)
100 meters (328 feet)
100 meters (328 feet)
100 meters (328 feet)
100 meters (328 feet)
100 meters (328 feet)
Installation and Network Layouts
10Base--T Hub (required if using more than one Ethernet slave)
Installation and Safety Guidelines
Page 28
1 Configuring the ERM and Slave Modules with ERM Workbench In This Chapter. . . ., ERM Workbench Software, Running ERM Workbench PLC Wizard, Running ERM Workbench, Configure the ERM, Select the Slaves, Configure the Slaves, Write Configuration to ERM, Printing ERM Configuration
4
Page 29
4--2
Configuring the ERM and Remote Ethernet Slaves with ERM Workbench
Getting Started
ERM Workbench Software Ethernet Remote Master (ERM) Workbench is a software utility that must be used to configure the ERM and its remote Ethernet slaves. The ERM Workbench supports two methods of configuring the ERM I/O network. Both methods are explained later in this chapter. The two configuration methods are: S ERM Workbench PLC Wizard -- simplifies the ERM I/O network configuration procedure when a PLC is used as the CPU Interface. S ERM Workbench -- configures an ERM I/O network whether the CPU Interface is a PLC or WinPLC, and allows access to all ERM I/O network parameters. NetEdit, a software utility within ERM Workbench, can be used to set the Ethernet master/slave Module ID, set an IP address if necessary or configure 405 EBCs with analog I/O modules. Both ERM Workbench and NetEdit can be used to monitor the remote I/O network and to perform diagnostic and troubleshooting tasks.
Configuring the ERM and Ethernet Remote Slaves
User Application Guidelines
Installing ERM Workbench
ERM Workbench can run on Windows 95/98/2000/MEt or Windows NTt (but not Windows 3.1xt). ERM Workbench is included with this manual on 3.5” diskettes. The latest version of ERM Workbench is available for download from the Host Engineering web site (www.hosteng.com). ERM Workbench consists of several files, all of which must be located in the same directory. The installation process places the files in the C:\HAPTools directory (default). The files may be placed in another directory, but remember all of the ERM Workbench files must be placed within the same directory. Place disk 1 of 2 in Drive A or Drive B. Click on the Windows Start button and then select Run. Type in the path and filename (ex. A:\setup), or click on the Browse button to find the directory and filename (ex. if ERM Workbench was downloaded from web). A series of windows will step through the installation process for disks 1 and 2. Fill in the necessary information as the installation wizard prompts through the install. In the Setup Type window, select Typical setup. This setup type is recommended for most users.
Page 30
Configuring the ERM and Remote Ethernet Slaves with ERM Workbench
4--3
Adding Network Protocol Support to the ERM Workbench PC
You may have already set up your PC with selected networking protocols for Ethernet communications. If not, you will need to select the protocols now for communication with the Ethernet modules. We strongly recommend that you include the IPX protocol. From My Computer on your PC Desktop, go to Control Panel. Double click on Network, then click on the Protocols tab. If IPX is not listed among the protocols already loaded, add it now by clicking on the Add... button. The Select Network Protocol window will pop up (see figure below). Add the TCP/IP protocol if it is necessary for your application. The TCP/IP selection will give you support for the UDP/IP protocol. Also, add the IPX protocol if it is not already active.
® ®
NOTE: We strongly recommend you load IPX protocol on your PC for the connection from your PC to the ethernet modules. Use UDP/IP in your application, if required, but also add IPX to your list of active protocols. Having IPX loaded on your PC gives you a backup for troubleshooting communication problems.
Configuring the ERM and Ethernet Remote Slaves
There are two methods to launch ERM Workbench. The two methods are: S using the Windows Start menu Programs>AutomationDirect Tools>ERM Workbench as shown below S launching DirectSoft32, then select PLC >Tools>ERM Workbench
User Application Guidelines