A two-page Echelon data sheet for the LonPoint LPR Router Modules, models 42100R to 42105R, sold as LPR-10 to LPR-15. These routers join two LONWORKS twisted pair channels of the TP/FT-10, TP/XF-78 and TP/XF-1250 types. The sheet gives the shared specifications, mounting options and front panel features of the series.

Device
Two-channel LONWORKS (ANSI/EIA-709.1) router module for twisted pair channels p. 1
Power
16-30VAC or DC @ 2VA, internally isolated; polarity-insensitive p. 2
Processor
Two Neuron 3150 Chips, 10MHz p. 2
Mounting
Type 2 Base Plate (4 in. square electrical boxes) or Type 2D DIN Base Plate (wall, panel or 35mm DIN rail) p. 2
Dimensions
3.9 x 3.9 x 1.0 in. (10cm x 10cm x 2.5cm) p. 2
Temperature
-40 to +85 C operating and non-operating; 10 to 95% RH @ 50 C p. 2
Router modes
Repeater, configured router or learning router p. 1
Front panel
Two network access jacks (Echelon PCC-10 Cable Model 78303), power LED, packet activity LED, service switch and LED p. 1
Wiring
Screw terminals; power and network wiring looped through the base plate, so modules hot-plug without stopping either channel p. 1
Channel types
Series covers TP/FT-10, TP/XF-78 and TP/XF-1250 channels, including a 1.25Mbps TP/XF-1250 backbone p. 1
Model numbers
42100R, 42101R, 42102R, 42103R, 42104R and 42105R, RoHS compliant p. 1
Software
Configured and commissioned with the LonMaker tool p. 1
Certifications
The sheet states U.L. Listed, cU.L. Listed, CE Mark, FCC; U.L. 916 p. 1, 2

What this sheet walks you through

  • Choosing among the six LPR router models by channel types p. 1
  • Mounting in a 4 inch square electrical box or on a DIN base plate p. 2

Good to know

  • The modules are not designed for equipment or systems where human health or safety is at risk. p. 2

Questions this sheet answers

What power does an Echelon LPR router module need?

16-30VAC or DC at 2VA, with an internally isolated power supply and polarity-insensitive connections. p. 2

Can an LPR router be swapped without taking the network down?

Yes. Power and network wiring loop through the base plate, so a module can be hot-plugged without disrupting either channel. p. 1

How big is the LonPoint LPR router?

3.9 x 3.9 x 1.0 in. (10cm x 10cm x 2.5cm). p. 2

Can an LPR router work as a repeater?

Yes. LPR Routers can be installed as repeaters, configured routers or learning routers. p. 1

The file

Size and text

Pages2
PDF375 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Echelon LPR-14 Spec Sheet

The text of page 1, from the PDF itself

LPR Router Modules Models 42100R, 42101R, 42102R, 42103R, 42104R, and 42105R t Router for TP/FT-10, TP/XF-78, and TP/XF-1250 LONWORKS® (ANSI/CEA-709.1) channels t Screw terminal wiring connections t 16-30VAC or VDC operation t Network access from front panel jacks t Two-piece design cuts installation time, cost t U.L. Listed, cU.L. Listed, CE Mark, FCC

LonPoint® Modules The LonPoint Modules are products designed to integrate new and legacy sensors and actuators, as well as LONMARK® devices, into cost-effective, interoperable, control systems for building and industrial applications. In contrast to traditional control networks, which use closed islands of control linked with proprietary gateways, the LonPoint Modules offer an open distributed system architecture in which every device performs some control processing and can be accessed from any location in the network. Distributing the processing throughout the network and providing open access to every device lowers the overall installation and life cycle costs, increases reliability by minimizing single points of failure, and provides the flexibility to adapt the system to a wide variety of applications. The system consists of the LonPoint Interface, Scheduler, Data Logger, Router Modules, LonPoint Application Programs, LNS® based LonMaker® Integration Tool, LonPoint Plug-In and LNS DDE Server. The LPR Router Modules may be used with a LonPoint System or as part of any LONWORKS network.

LPR Routers can be installed as repeaters, configured routers, or learning routers. Models 42100R, 42101R, 42102R, 42103R, 42104R, and 42105R are compliant with the European Directive 2002/95/EC on the restriction of the use of certain hazardous substances (RoHS) in electrical and electronic equipment. Using the LonMaker tool, the user configures and commissions the LPR Routers and other LonPoint modules, as well as third-party LONMARK and LONWORKS devices, to create an interoperable, distributed control system. Network design and configuration is simplified by the Visio® interface of the LonMaker tool, which can both import and export AutoCAD® files and generate as-built documentation. A unique, two-piece design allows pre-wiring and cable testing by an electrician prior to installation of the electronics; technician time can be reserved for tasks such as node configuration. Power and network wiring are “looped” through the base plate, providing the ability to replace modules by hotplugging without disrupting the operation of the two network channels. Network Access Jacks; use with Echelon PCC-10 Cable Model 78303

LPR-10 Modules

Network A Network B

The LPR Modules are two-channel LONWORKS (ANSI/EIA-709.1) routers that can interface two different twisted pair channels (e.g., a high speed 1.25Mbps TP/XF1250 backbone and a TP/FT-10 free topology channel), manage network traffic, increase the total number of LONWORKS devices, or increase the amount of cabling in a system.

LonPoint Interface Model and Software Revision LPR

ULCULUS

MODEL 42100 972 LISTED 178K SW VERSION 1 .0 ENERGY MANAGEMENT EQUIPMENT SUBASMBLY ID NUMBER

LPR MODEL 42100˚˚ID NUMBER

Peel-Off Code 39 Format Bar Code of LonPoint Interface Neuron Chip ID Number

LPR MODEL 42100˚˚ID NUMBER

Six different models of LPR Routers are available: Name LPR-10 LPR-11 LPR-12 LPR-13 LPR-14 LPR-15

Model 42100R 42101R 42102R 42103R 42104R 42105R

Channel Types TP/FT-10 to TP/FT-10 TP/FT-10 to TP/XF-78 TP/FT-10 to TP/XF-1250 TP/XF-78 to TP/XF-78 TP/XF-78 to TP/XF-1250 TP/XF-1250 to TP/XF-1250

Service Switch Service LEDs Network A Network B

Packet Activity LED Router Transferring Packets: Flashing

Power LED: Power On: Illuminated Continuously

Page 2 of Echelon LPR-14 Spec Sheet

The text of page 2, from the PDF itself

Service LEDLonPoint ModuleBase Plate

4" Square Electrical Box

LonPoint Interface Module 4″ Square by 2″ Deep Electrical Box Mounting Configuration

Polarity-insensitive power and network connections minimize the chance of miswiring. Two front panel jacks access the two twisted pair networks without any disassembly, saving time when the network must be accessed for configuration or maintenance. A front panel bar code with the model, revision, and two removable Neuron® Chip ID stickers is provided. When placed on the building or system design plans, these stickers can save installation time, especially for inaccessible nodes.

Type 2D DIN Base Plate Front View

Mounting The LPR modules may be used with either a Type 2 Base Plate (for use with 4″ square electrical boxes) or a Type 2D DIN Base Plate (for wall, panel, or 35mm DIN-rail mounting).

Specifications Function Processor Service function Transceiver type Input power Mounting Temperature Humidity EMI Safety agency Dimensions

Description Two Neuron 3150® Chips, 10MHz Recessed service switch, service (wink) LED. Dual tear-off bar-code Neuron ID self-adhesive tag Varies by model 16-30VAC or DC @ 2VA, internally isolated power supply Type 2 or Type 2D DIN Base Plate -40 to +85°C, operating and non-operating 10 to 95% RH @ 50°C FCC A, CE Mark U.L. 916 3.9″ x 3.9″ x 1.0″ (10cm x 10cm x 2.5cm)

Copyright © 1999-2007, Echelon Corporation. Echelon, LON, LONWORKS, LONMARK, LonBuilder, NodeBuilder, LonManager, LonTalk, LonUsers, LonPoint, Digital Home, Neuron, 3120, 3150, LNS, i.LON, LONWORLD, ShortStack, Panoramix, Panoramix Powered by Echelon, LonMaker, the Echelon logo, and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries. Pyxos, LonLink, LonResponse, LonSupport, LONews, Open Systems Alliance, OpenLDV, LonBridge, Powered by Echelon, LNS Powered by Echelon, LONWORKS Powered by Echelon, Networked Energy Services Powered by Echelon, NES Powered by Echelon, and Thinking Inside the Box are trademarks of Echelon Corporation. Other trademarks belong to their respective holders. Disclaimer Neuron Chips, Free Topology Twisted Pair Transceiver Modules, and other OEM Products were not designed for use in equipment or systems which involve danger to human health or safety or a risk of property damage and Echelon assumes no responsibility or liability for use of the Neuron Chips or Free Topology Twisted Pair Transceiver Modules in such applications. ECHELON MAKES AND YOU RECEIVE NO WARRANTIES OR CONDITIONS, EXPRESS, IMPLIED, STATUTORY OR IN ANY COMMUNICATION WITH YOU, AND ECHELON SPECIFICALLY DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. 003-0137-01G