12 Troubleshooting
This chapter describes the process of troubleshooting the LonPoint Modules.
LonPoint Hardware Guide
12-1
Page 112
Troubleshooting Table Table 12.1 presents common troubleshooting symptoms, and associated diagnoses, that may be encountered in the field.
Table 12.1 Troubleshooting Symptoms and Diagnoses Symptom
Diagnosis
Power LED illuminated
This is the normal state of the LED when the node is powered.
Power LED flashing then returning to continually illuminated
This is the normal state for a network management Wink function, and indicates that the module is being signalled by the LonMaker for Windows Integration Tool.
Power LED extinguished
Power supply providing power to the module has lost primary power. Check power supply output for the presence of power. Power wiring not correctly connected to module. Use a volt meter to check for power on base plate power terminals. Input voltage too low due to excessive load on the power supply providing power to the module, excessively long power cabling, or shorted power wiring. Use a volt meter to check for the correct voltage level on the base plate power terminals. Correct cabling length if too long. Repair faulty power cable. Type 1D or 2D DIN Base Plate Jumper Plug not correctly inserted.
Service LED extinguished
This is the normal state of the LED for a configured module.
Service LED flashing
The module is unconfigured. This is the normal state of a new module. The module must be commissioned by the LonMaker tool.
Service LED illuminated
The module is applicationless - it has lost its application software program. The module must be reloaded by the LonMaker for Windows Integration Tool.
No network communications
Network wiring not correctly connected to module. Network cabling shorted, open, or otherwise damaged. Use continuity meter to check cabling. Router(s) on network not commissioned, not powered, or otherwise not functioning correctly. Type 1D or Type 2D DIN Base Plate Jumper Plug not correctly inserted. Incorrect orientation of Type 1D and Type 2D DIN Base Plates. Incorrect router channel type installed on channel.
Erratic or improper network communications
Network wiring not securely connected to Base Plate terminals. The optimum tightening torque for a Base Plate screw terminal is 4 lbs. in. (0.5Nm) maximum. Module not properly seated in the Base Plate. Ensure that the module is pressed firmly into the Base Plate and secured with suitable fixing screws.
12-2
Troubleshooting
Page 113
Erratic or improper network communications (continued)
Improper or missing network termination. A free topology TP/FT-10 channel requires one Model 44100 Terminator located anywhere on the channel. A bus topology TP/FT-10 channel requires two Model 44101 terminators, one at each end of the bus. A TP/XF-1250 channel only operates in a bus topology, and requires two Model 44200 Terminators, one at each end of the bus. Excessive network cabling. See Chapter 3 for a discussion of the maximum cable distances permissible on the TP/FT-10 and TP/XF-1250 channels. If the channel cabling is too long, install one or more LPR Routers in series with the network cabling. Improper network cabling. See Chapter 3 for a discussion of the types of cabling that are approved for use on the TP/FT-10 and TP/XF-1250 channels. In some cases it is possible to correct network communications by installing one or more LPR Routers in series with the network cabling. In other cases the cabling must be replaced with an approved cable. Excessive number of modules on a channel. See Chapter 3 for a discussion of the number of devices that can be installed on a channel. If too many modules are on the channel, install one or more LPR Routers in series with the network cabling. Modules are connected to the wrong channel of an LPR Router. Care must be taken to ensure that correct types of devices are connected to the two channels of a router. LonPoint modules should only be connected to a TP/FT-10 channel.
Improper operation of digital inputs
Input voltage is too low to be detected. Ensure that the input signal level matches the capabilities of the DI-10 module.
Improper operation of digital input LEDs
Node unconfigured. LEDs only function in configured mode.
Improper operation of digital output
Mismatch between the output current of the module and the device being driven. The maximum current from any single DO-10 output is 100mA source, with a maximum total of 110mA source for all four outputs. Hand/off/auto switch(es) in the wrong position. The hand/off/auto switch forces the output low (0 position), high (1 position), or allows the application program to select the output state (center network position).
Improper operation of digital output LEDs
Node unconfigured. LEDs only function in configured mode.
Improper operation of analog inputs
Jumpers incorrectly set on AI-10 modules. See Chapter 7 for a discussion of jumper settings. Make certain that the Input 1 jumpers are set correctly for analog input 1, and likewise that Input 2 jumpers are set correctly for analog input 2. Common wiring shared between two analog inputs. Each analog input to the AI-10 module must have a separate + and - connection; the two analog inputs should not share a common + or - connection. Software configuration is incorrectly set for the specified analog input. The gain and range settings must be configured correctly in order for the AI-10 to properly supervise the analog input.
LonPoint Hardware Guide
12-3
Page 114
Improper operation of analog outputs
Jumpers incorrectly set on AO-10 modules. See Chapter 8 for a discussion of jumper settings. Make certain that the Output 1 jumpers are set correctly for actuator output 1, and likewise that Output 2 jumpers are set correctly for actuator output 2. Common wiring shared between two analog outputs. Each analog output on the AO-10 module must have a separate + and - connection; the two analog outputs should not share a common + or - connection. Software configuration is incorrectly set for the specified voltage or current output. The voltage and current settings must be configured correctly in order for the AO-10 to properly drive the analog output.
12-4
Troubleshooting
Page 115
E
DECLARATION OF CONFORMITY ®
LONPOINT MODULES Application of Council Directive :
89/23EEC; 89/337/EEC
Manufacturer’s Name:
Echelon Corporation
Manufacturer’s Address:
4015 Miranda Avenue Palo Alto, CA 94304 USA
Manufacturer’s Address: in Europe
Echelon BV Printerweg 3 3821 AP Amersfoort The Netherlands
Product Model Number:
40111, 40222, 41100, 41200, 41300, 41400, 41500, 42100, 42101, 42102, 42103, 42104, 42105, 43100, 44100, 44200, 48111, 48222.
Type of Equipment:
Industrial Control, Energy Management Equipment
Standards to which: Conformity is Declared
EN55011-A, 1991 EN61000-4-2 EN61000-4-4 EN61000-4-6 EN61000-4-11
EN50082-2, 1995 EN61000-4-3 EN61000-4-5 EN61000-4-8 ENV50204
I, Paul Smith, hereby declare that the equipment specified above conforms to the above Directives and Standards.
Place: Amersfoort, The Netherlands
Date: March, 1999
Position: Controller, Echelon BV