Page 211
M SERIES DAC TECHNICAL SUPPORT ____________________________________________________________________________
Contact rating: VDC
3A @120 VAC, 2A @220 VAC or 28 resistive load
Contact resistance: Life expectancy:
100 milliohms initially Mechanical: 20 million operations (min) Electrical: 100,000 (min) @ full load
Vibration:
10g @ 55-110Hz, 0.062", Dual amplitude(DA) -55Hz
Shock:
10g
Voltage isolation:
500 Vrms Channel-Channel & Channel-Ground
Connector:
DB-25 female
Power Requirements: are on –
+5VDC, 300ma typical when all relays (provided by M16/M8 power supply).
Software Control:
Relays individually programmable to act upon, record and/or report events by time, or on demand. Operating temperature range 0o to 55o C Storage temperature range -55o to 85o C Humidity 5% to 95% non-condensing
Environmental:
V79 PDI-1 SWITCH INPUT STATUS MODULE NOTE: These values are typical for 25o C unless otherwise noted) Inputs:
16 with individual ground returns or common (single-point) ground.
Drive Distance:
Up to 1000 Ohms cable resistance, for example: AWG 36 - 2400 ft., AWG 24 -
15000 ft., AWG 22 - 62000 ft.
199
Page 212
M SERIES DAC TECHNICAL SUPPORT ____________________________________________________________________________
Power Requirements: M16/M8
+5VDC, 40 ma typical (provided by pwr supply).
Debounce: Environmental:
0 to 60000 ms (software selectable). Operating temperature range: 0o to 70o C Storage temperature range: -40o to 85o C Humidity: 5% to 95% non-condensing
V80 PDI-2 OPTICALLY ISOLATED INPUT MODULE
Module Type
PDI-2A PDI-2B
Number of Inputs:
16
16
Input Voltage Range:
5-24
100-130
Maximum Input Current:
50ma
20ma
Minimum Turn On Current:
8ma
8ma
Max Turn On Time:
1ms
1ms
Max Turn Off Time:
1ms
1ms
VOLTAGE ISOLATION: Power Requirements: M16/M8
AC/DC
500V 500V (Input to Input and Input to ground) +5VDC, 40 ma typical (provided by pwr supply)
Debounce Time:
0 to 60000 ms (software selectable)
Environmental:
Operating temperature range: 0o to 70o C Storage temperature range: -40o to 85o C Humidity: 5% to 95% non-condensing
V82 PCM-1 SPECIFICATIONS FACTORY POWER-UP DEFAULT CONFIGURATION: Channel Names: 200
MOD01P01 for Module 1 Channel 1 MOD01P02 for Module 1 Channel 2
Page 213
M SERIES DAC TECHNICAL SUPPORT ____________________________________________________________________________
. . . MOD16P16 for Module 16 Channel 16 Instruction Table:
The Instruction Table is blank by default. If an instruction is entered into the Instruction
Table, that instruction and the "latch" parameter are disabled by default. Program Strings:
All output strings are blank by default.
Conversion Tables:
All conversion tables are blank by default.
User-Programmable Configurations: are
Easy to configure using on-screen menu. Choices saved in non-volatile memory to become the new power-up default configuration. Channel Names:
Any character string up to 16 ASCII characters.
Instruction Table:
Up to 999 instructions can be entered. Each instruction can be enabled or disabled and given a name up to 8 ASCII characters. There are fields for Enable, Line Name, CMD Type, and 5 arguments for each instruction. Each instruction has a "latch" parameter that can be enabled or disabled. Program Strings:
Up to 64 ASCII strings can be programmed.
String Name:
Up to 8 ASCII characters.
String Content:
Up to 64 ASCII characters.
Conversion Tables: programmed.
Up to 16 conversion tables can be
Conversion Table Name:
Up to 8 ASCII characters. 201
Page 214
M SERIES DAC TECHNICAL SUPPORT ____________________________________________________________________________
Slope:
-9999.99 to +9999.99
Y-Intercept:
-9999.99 to +9999.99
Range:
Up to 5 linear ranges per conversion table.
V 93A SPECIFICATIONS
Interface:
Dial-up telephone line
Modulation:
V.32bis (14,400 bps) or V.32 (9600 bps)
Compression:
V.42bis, MNP5
Connectors:
2 x 4-pin modular
Module LEDS:
TD (Transmit Data), RD (Receive Data), CD (Carrier Detect), MR (Modem Ready), and CX (Connection) status LEDs. Transmit Level:
-10 dBm (dial-up)
Receiver Sensitivity:
-45 dBm
Dimensions:
6"h x 4.5"w.
202
Page 215
M SERIES DAC APPENDIX B ____________________________________________________________________________
APPENDIX B MODEM COMMAND SUMMARY U.S. ROBOTIC MODEMS COMMAND
INTERPRETATION
AT&B1
Fixed Serial Port Rate (default)
AT&C1
Normal CD Operations (default)
AT&D2
Normal DTR Operations (default)
ATSO=1
Auto answer telephone line in 4 or fewer rings
ATE0
Modem does not display keyboard commands.
ATQ1
Place modem into quiet mode
AT&W0
Save the modem’s configuration in non-volatile memory
NOTE: To send all of the above at the same time, type the following command: AT&B1&C1&D2S0=1E0Q1&W0
ROCKWELL CHIP SET MODEMS COMMAND
INTERPRETATION
ATS23=59
Fixed Serial Port Rate (default)
AT&C1
Normal CD Operations (default)
AT&D2
Normal DTR Operations (default)
ATS0=1
Auto answer telephone line in 4 or fewer rings
ATE0
Modem does not display keyboard commands
ATQ1
Place modem into quiet mode
AT&W0
Save modem’s configuration in non-volatile memory
NOTE: To send all of the above at the same time, type the following command: ATS23=59&C1&D2S0=1E0Q1&W0 203
Page 216
M SERIES DAC APPENDIX E ____________________________________________________________________________
APPENDIX C MODULE COMMAND SUMMARY V74/V75/V87 DAC DATA COMMAND SUMMARY Command
Description
$CONFIG<cr>
Full menu configuration command.
$BTBn<cr> (n=1 to 16)
Broadcast. This command puts module n into broadcast mode where data received by the host module is sent to all V74/V75/V76/V87 ports simultaneously.
CBn<cr> (n=1 to 4, 0=all)
Clear Buffer. This command clears all buffered messages from the specified ports.
ID<cr>
Port ID Status. This command reports the current Port ID status for the ports of the selected module. The Port ID can have the format of either UU:MM,PP (Unit:Module, Port) or the device name of the port.
RAn<cr> (n=1 to 4, 0=all)
Report All Buffered Messages. This command reports all messages in the buffer at the time the command was sent. If there are no messages, <lf> is sent to the host controller.
RBn<cr> (n=1 to 4, 0=all)
Report All Buffered Data. This command reports all data in the buffer at the time which the command was received with no regard for messages. If there is no data, <lf> is sent to the host controller.
* RESET<cr>
Reset. This command instructs the entire M Series system to do a software reset.
RSn<cr> (n=1 to 4, 0=all)
Report Single Message. This command reports a single buffered message. If there is no message, <lf> is sent to the host controller.
RT<cr>
Read Time. This command requests the base unit to send the current date and time.
SRn<cr> (n=1 to 4, 0=all)
Stop Report. This command stops data flow from an RBn or RAn command.
ST HH:MM:SS,MM/DD/YY<cr>
Set Time. This command programs the date and time of the base unit's time-of-day clock.
NOTE: Multiple V74/V75/V76/V87 ports are selected using 2 formats. Examples: RA1,2,3,4<cr> and RA0<cr>. * The RESET<cr> command must be issued from the service port or service modem.
204
Page 217
M SERIES DAC TECHNICAL SUPPORT ____________________________________________________________________________
V77 ADM-1 DATA COMMAND SUMMARY Command
Description
CAn<cr> (n=0 or 1 to 3)
Calibrate. 0=all, 1=25%, 2=50%, and 3=75% of Full Scale (FS). Initiates auto-calibration. ADM-1 tests for offsets and makes necessary corrections. Corrections are continually applied to all reported data messages until another Calibrate command is issued.
CBc<cr> (c=Ch# 1 to 16, 0=all)
Clear Buffer. Clears all old data from the buffer when a new data set is started.
RAc<cr> (c=Ch# 1 to 16, 0=all)
Report All Buffered Samples.
RS c<cr> (c=Ch# 1 to 16, 0=all)
Report Single Sample if Available
SAc<cr> (c=Ch# 1 to 16, 0=all)
Sample. Read and report sample at programmed setup.
V77 ADM-1 DYNAMIC CONFIGURATION COMMAND SUMMARY Command
Description
AVn<cr> (n=1 to 4,000)
Number of Samples to Average
DFn<cr> (n=1 or 2)
Data Format. 1=Hexadecimal and 2=Decimal.
RMn<cr> (n=1 to 3)
Reporting Method. 1=Command, 2=Immediate, and 3=Schedule.
SDn<cr> (n=1 or 2)
Single Ended/Differential. 1=single ended and 2=differential.
S Mn<cr> (n=1 or 2)
Sampling Method. 1=Command, 2=Immediate, and 3=Schedule.
SPn<cr> (n=1 or 2)
Sample Period. 1=Continuous and 2=Time.
SRn<cr> (n=1 to 4000)
Sample Rate (Samples/Sec)
TTn<cr> (n=1 or 2)
Time Tag. 1=Enable and 2=Disable.
UBn<cr> (n=1 or 2)
Unipolar/Bipolar. 1=unipolar and 2=bipolar.
VRn<cr> (n=1 to 5)
Set Voltage Range. 1 = +10V (with JP1 installed), 2 = +5V (or 0 to +10V), 3 = +2.5V (or 0 to +5V), 4 = +1.25V (or 0 to +2.5V) and 5 = +0.625V (or 0 to +1.25V)
205
Page 218
M SERIES DAC TECHNICAL SUPPORT ____________________________________________________________________________
V78 CRM-1 DATA COMMAND SUMMARY Command
Description
CBr<cr> (r=Relay# 1 to 8, 0=all*)
Clear Buffer. Clears all buffered relay status history (change of state).
DRr<cr> (r=Relay# 1 to 8, 0=all*)
De-energize Relay(s)
ERr<cr> (r=Relay# 1 to 8, 0=all*)
Energize Relay(s)
RAr<cr> (r=Relay# 1 to 8, 0=all*)
Report All Buffered Relay Status History
RS r<cr> (r=Relay# 1 to 8, 0=all*)
Report Single Relay Status History Sample if Available
SAr<cr> (r=Relay# 1 to 8, 0=all*)
Sample. Read and report the current status of the selected relay(s).
V78 CRM-1 I/O MODULE DYNAMIC CONFIGURATION COMMAND SUMMARY Command
Description
RMn<cr> (n=1 to 3)
Reporting Method. 1=Command, 2=Immediate, and 3=Schedule.
TTn<cr> (n=1 or 2)
Time Tag. 1=Enable and 2=Disable.
206
Page 219
M SERIES DAC TECHNICAL SUPPORT ____________________________________________________________________________
V79 PDI-1 & V80 PDI-2 COMMAND SUMMARY Command
Description
CBc<cr> (c=Ch# 1 to 16, 0=all)
Clear Event Buffer. Clear all buffered event samples.
CCc<cr> (c=Ch# 1 to 16, 0=all)
Clear Event Counter(s)
CRc<cr> (c=Ch# 1 to 16, 0=all)
Clear Event Latch Data
RAc<cr> (c=Ch# 1 to 16, 0=all)
Report All Buffered Events
RCc<cr> (c=Ch# 1 to 16, 0=all)
Report Event Counter(s)
RDc<cr> (c=Ch# 1 to 16, 0=all)
Report Event Duration(s)
RLc<cr> (c=Ch# 1 to 16, 0=all)
Report Event Latch Data
ROc<cr> (c=Ch# 1 to 16, 0=all)
Report Event Counter and Reset
RRc<cr> (c=Ch# 1 to 16, 0=all)
Report Event Latch Data
RS c<cr> (c=Ch# 1 to 16, 0=all)
Report Single Buffered Event (first in, first out)
SAc<cr> (c=Ch# 1 to 16, 0=all)
Read and report the current state of the selected input(s).
SLc<cr> (c=Ch# 1 to 16, 0=all)
Report Latest Event
* Multiple channels are selected using 4 formats. Examples: SA1,2,3,4,5,6,7,8<cr>, SA1-8<cr>, SA0<cr>, SA1,2,4-8<cr>
V79 PDI-1 & V80 PDI-2 DYNAMIC CONFIGURATION COMMAND SUMMARY Command
Description
DBn<cr> (n=0-65535ms)
Debounce Delay
DFn<cr> (n=1 or 2)
Data Format. 1=Hexadecimal and 2=Decimal.
RMn<cr> (n=1 to 3)
Reporting Method. 1=Command, 2=Immediate, and 3=Schedule.
TTn<cr> (n=1 or 2)
Time Tag. 1=Enable and 2=Disable.
207
Page 220
M SERIES DAC APPENDIX E ____________________________________________________________________________
APPENDIX D – CABLES AND ADAPTERS
208