Page 131

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

Set Unit Number Program Password Exit System Menu

3 4 X

Enter Request: For detailed Control Board System Menu information see the M-Series DAC Owner’s Manual Number U140E111-02. MANUAL CONNECTION The “Manual Connection” selection for the V72 menu is used to make a module level connection which is used for sending commands to the module. The “Manual Connection” is used to make a connection to a module such as the Control Relay Module, A-to-D Module, Event Counter Module, main board, etc. Use the “Manual Connection” for module connections other than a Serial I/O module unless you want to operate a Serial I/O module in the Command Mode of operation. The “Manual Connection” selection should not be used for configuration. By responding to the Enter Request: message at the end of the V72 menu with “M” you receive a response similar to the following: Device A (2,1 Device B (2,2 Device C (2,3 Device D (2,4 Device A (3,1 Device B (3,2 Device C (3,3 Device D (3,4 Immediate Data Collection Configure Manual Connection Unit Reset Module Status Logout

1 2 3 4 5 6 7 8 I C M R S T

Enter Request: M Enter Module number: 2 Enter Port number (<CR> for none): 3

119

Page 132

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

By entering “2” at the Enter Module number and entering “3” at the Enter Port number, the user has selected module number 2 and port number 3. Verify the connection by insuring that the red LED of Port 3, Module 2 on the front panel of the M-Series DAC base unit has been selected. UNIT RESET Users can instruct the M-Series DAC with the V72 Ethernet module, to “reset” by using the Menu Selection Method to reset the unit. Only a user connected to the host module can issue the reset command. Users can also instruct the M-Series DAC to reset by sending the ASCII string “$BTRESET” from the service port. The Unit Reset and $BTRESET commands do not affect any saved configuration parameters that have been changed from the default values. IMPORTANT: The Unit Reset command will terminate communications with connected equipment to the M-Series DAC. You must re-establish communications with the M-Series DAC system after the unit has been reset. The Unit Reset menu selection is found in the V72 Module Menu. This Menu is invoked by sending the Attention Character(default ;;;;;) to the V72 host module five times. The V72 will respond with a menu similar to the following, if two Serial I/O modules are installed. By responding to the Enter Request: message at the end of the menu with “R”(Unit Reset), you will reset the M-Series unit. Device A (2,1) Device B (2,2) Device C (2,3) Device D (2,4) Device A (3,1) Device B (3,2) Device C (3,3) Device D (3,4) Immediate Data Collection Configure Manual Connection Unit Reset Module Status Logout Enter Request: R The M-Series DAC unit has been reset.

120

1 2 3 4 5 6 7 8 I C M R S T

Page 133

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

MODULE STATUS By responding to the Enter Request: message in the V72 menu with “S” (Module Status), you can review the current module status. The V72 host module will respond with a menu that is similar to the following: Device A (2,1) Device B (2,2) Device C (2,3) Device D (2,4) Device A (3,1) Device B (3,2) Device C (3,3) Device D (3,4) Immediate Data Collection Configure Manual Connection Unit Reset Module Status Logout

1 2 3 4 5 6 7 8 I C M R S T

Enter Request: S V72 Status & Diagnostics Menu. System Internal Communications Network Interface Logged Users Exit

1 2 3 4 X

SYSTEM STATUS By responding to the Enter Request: message in the V72 Status & Diagnostics Menu with “1” (System), you can review the current system status. The V72 host module will respond with a menu that is similar to the following: >1 System Status: Available local memory (256 byte buffers): 510 System memory (M03 modules, MB): 0 Connections in use: 1

121

Page 134

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

Pending messages (module #s): none Immediate Mode User: none Command/Configuration Mode User: none System up time (days:hh:mm:ss): 2:07:43:54 <Strike any key to continue.> INTERNAL COMMUNICATIONS By responding to the Enter Request: message in the V72 Status & Diagnostics Menu with “2” (Internal Communications), you can review the current internal communications status. The V72 host module will respond with a menu that is similar to the following: V72 Status & Diagnostics Menu. System Internal Communications Network Interface Logged Users Exit

1 2 3 4 X

>2 Internal Bus Status: Internal Bus Errors: 0 Bus transmit data channel: clear <Strike any key to continue.> NETWORK INTERFACE By responding to the Enter Request: message in the V72 Status & Diagnostics Menu with “3” (Network Interface), you can review the current Network Interface status. The V72 host module will respond with a menu that is similar to the following:

V72 Status & Diagnostics Menu. System Internal Communications Network Interface

122

1 2 3

Page 135

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

Logged Users Exit

4 X

>3 Network Status: Medium status: good Medium faults: 0 Xmit bufr errs: 0 Available send buffers: 30 Receive queue status: open <Strike any key to continue.> LOGGED USERS By responding to the Enter Request: message in the V72 Status & Diagnostics Menu with “4” (Logged Users), you can review the Logged Users into the system. The V72 host module will respond with a menu that is similar to the following: V72 Status & Diagnostics Menu. System Internal Communications Network Interface Logged Users Exit >4

1 2 3 4 X

Active Users: Address/Port

Internal TX/RX Net Data Flo TX/RX

1) *200.4.3.10 none/none ok/ok

2) 200.4.3.10

2,3/2,3 ok/ok

Bus Data Flo

TX/RX no/ok ok/ok The star (*) indicates that Active User #1 is currently communicating with the V72 Ethernet module. By responding to the “Strike ‘T’” message in the Logged Users Menu with “T” (Terminate) you will see a screen that asks “Enter number of connection to terminate”. See the screen that follows: <Strike "T" to terminate a session, any other key to continue.> T

123

Page 136

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

By responding with “2” to the “terminate a session” message, the V72 will respond with a menu that is similar to the following: Enter number of connection to terminate, <CR>: 2 Connection being terminated. Active Users: Address/Port

Internal TX/RX

1) *200.4.3.10 2) -200.4.3.10 none/none 2,3/2,3

Net Data Flo TX/RX

Bus Data Flo

TX/RX ok/ok ok/ok no/ok ok/ok

The (-) before the address located at Active User number 2 indicates that the session to Active User 2 will be terminated. V72 Status & Diagnostics Menu. System Internal Communications Network Interface Logged Users Exit

1 2 3 4 X

By responding with “X” to the “Exit” message, the user will exit from the V72 Status and Diagnostics Menu EXIT By responding to the Enter Request: message in the V72 Status & Diagnostics Menu with “X” (Exit), you will exit the V72 Status & Diagnostics Menu. The V72 host module will respond with the following: >X LOGOUT By responding to the Enter Request: message in the V72 Main Menu with “T” (Logout), you will terminate your TELNET connection. The V72 host module will respond with a message similar to the following: Device A Device B

124

(2,1) (2,2)

1 2

Page 137

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

Device C (2,3) Device D (2,4) Device A (3,1) Device B (3,20) Device C (3,3) Device D (3,4) Immediate Data Collection Configure Manual Connection Unit Reset Module Status Logout

3 4 5 6 7 8 I C M R S T

<Your ‘TELNET’ connection has been terminated> ASCII STRING COMMAND METHOD Serial I/O module ports(V74/V75) can also be selected by sending an ASCII character string to the V72 host module that consists of the Port Select Code (default is $BT), the desired Serial I/O module number (2 to 3 for M3 DAC), (2 to 6 for M6 DAC), (2 to 9 for M9 DAC), and (2 to 16 for the M16 DAC), the desired Serial I/O module port number (1 to 4), and <cr>. For example, to select Port 1 of a V74 module installed as Module 2 using the default Port Select Code, send $BT2,1<cr>. To disconnect, either select another V72 module or send the disconnect sequence. The disconnect sequence consists of the Port Select Code followed by <cr> (e.g., $BT<cr>). Once you disconnect, you can logout by typing LOGOUT<cr>. NOTE: These commands are illustrated using the default port select code ($BT).

125

Page 138

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

V72 COMMAND SUMMARY Command Description $BTn,p<cr> Request to connect to peripheral module "n" port "p". If module m is operating in full duplex mode, full duplex communication is established when connection is made. Otherwise, the connection is for output only (from V72 to the selected module/port). $BTn<cr> Request to connect to module "n". Upon connection, the V72 will enter command mode for the selected module and the selected module will respond to its command set. The selected module may be configured by sending "$CONFIG<cr>" after the "$BTn<cr>". $BTI<cr> Receive immediate mode data. This will cause the user to receive messages or data from modules configured to operate in immediate message mode or immediate data mode. $BT<cr> Disconnect. Terminates the current operation mode or module/port connection. Network session remains active. $BTX<cr> Network disconnect. Terminates the workstation session. Releases all session resources, such as modes or ports. $BTRI<cr> Locates the user of the Immediate Receive Mode and terminates the session if found, releasing the mode. $BTRC<cr> Locates the user of the Command/Configuration mode and terminates the session if found, releasing the mode. $BTRn,p<cr Locates the user of n,p (module,port) and terminates the session if > found, releasing the port. $BTRS<cr> Reset. This command is used to reset the unit. $BTN<cr> Entry of this command will prevent the V72 from sending advisory or error messages to the user (see Section 4.6). This command may be useful where an automated process does not wish to contend with unit messages appearing in the data stream. By default, a connection will allow these messages to be sent unless disabled by this command. $BTM<cr> Entry of this command will re-enable the V72 to send module advisory and error messages to the user. $BTS<cr> Access the V72 status diagnostics menu. n = desired module number (1 to 16), p = desired port number (1 to 4)

MESSAGES The V72 generates various messages in response to certain commands/situations as described in the table below.

126

Page 139

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

MESSAGE Module "n" not installed

Module "n" not responding

Module "n" busy

Module "n", port "p" busy

Login successful

Login failed

Immediate Mode in use

Command/Configuration Mode in use

Command/Configuration Mode in use by Service

V72 MESSAGES DESCRIPTION Issued when a user tries to connect to a peripheral module or port that was not reported as installed to the V72. Verify that correct module number was entered. Check module operation on power-up to verify normal initialization. Issued when a module was reported as installed, but failed to respond within 1 second to a connection request from the V72. Repeated occurrences of this message indicate a possible problem with the module. Check module operation on power-up to verify normal initialization. Issued when a connection request is denied by a module. A connection is typically denied when a module is already supporting a connection to another user. Issued when a port connection request is denied by a module. A connection is typically denied when a port on the module is already supporting a connection to another user. Issued when a user completes the login sequence successfully. Upon the receipt of this message, the user has full access to the DAC and may issue any valid V72 command. Issued when user enters erroneous password. Password is case sensitive and will not tolerate any backspaces or character deletes. Issued when a user tries to enter immediate receive mode (by entering "$BTI<cr>") and another user is already using the resource. Immediate receive mode may only be used by one user at a time. Issued when a user tries to connect to a module (not a port) for command mode or configuration purposes (by entering "$BTn<cr>") and another user is already using the resource. Command/Configuration mode may only be used by one user at a time. This particular message indicates the current user is a network client. Issued when a user tries to connect to a module and the module is in use by a user connected to the service

127

Page 140

M SERIES DAC BASE UNIT AND MODULE OPERATION ____________________________________________________________________________

MESSAGE Port. To release mode, terminate Service Port connection. Resource released

V72 MESSAGES DESCRIPTION port. To free the resource, the Service Port connection must be terminated from the device connected to it.

Issued when the user of a module or port is successfully located and the associated process is terminated. See "Resource Release Function". Resource not released Issued when the user of a node or port is successfully located, but the associated process could not be terminated. For example, if the user wanted to release the Command/Configuration Mode, but the current user was connected via the Service Port, the resource would not be released. No resource user found Issued when no open connection could be associated with the specified mode or port. Connecting....Connected Issued to provide status of Telnet Client connection request. Dots are issued at 1/sec until the connection is established. If the connection cannot be established because the host fails to respond, the connection request will time out in about 30 seconds. Cannot connect to host Issued when a host refuses to accept or fails to respond to a connection request. Host session terminated Issued when a connection is terminated by either the host or the client. n = module number (1 to 16), p = port number (1 to 4) MODULE DIAGNOSTICS The V72 provides two diagnostic modes to the user. The first is an LED-based diagnostic, where the module uses its LEDs to convey information about hardware or configuration errors which will prevent network access. The second is an interactive diagnostic, which provides operational information which may help a user or Bay Tech technical support personnel to diagnose the source of a problem. LED INDICATORS The V72 has two LED indicators on the rear panel and four LED indicators on the front panel of the base unit corresponding to the module slot where the V72 is installed (i.e., Module 1, Module 2, etc.). The two LEDs on the module rear panel are marked as LINK and RX/TX. The green LINK LED illuminates if the V72 has a good 10BASE-T connection. Failure of this LED to illuminate indicates a physical

128