Spec sheet · Allen-Bradley
SLC 100 I/O Expansion Units Product Data
Spec sheet20 pagesPDF 2.2 MB
Product data sheet for the Allen-Bradley SLC 100 I/O expansion units (1745): basic, relay output and analog input units.
Covers · 1 model
The models it covers
Summary
What is in it
A product data sheet for the Allen-Bradley SLC 100 expansion units (catalog 1745-E series), which add I/O circuits to an SLC 100 or SLC 150 processor unit. It describes the basic, relay output and analog input expansion units, installation considerations, mounting and system layout, how I/O address blocks are assigned with connection examples, the 1745-C2 and 1745-C3 interconnect cables, line, digital input, analog input and output wiring, output contact protection, and general, input and output specifications.
Its parts
- The Expansion Unit
- Basic Expansion Unit
- Relay Output Expansion Unit
- Analog Input Expansion Unit
- Installation Considerations
- Mounting
- Addressing I/O
- System Layout
- Connection Cables
- Line Wiring Connections
- Digital Input Wiring Connections
- Analog Input Wiring Connections
- Output Wiring Connections
- Output Contact Protection
- General Specifications
From the sheet · read page by page
Key facts from this sheet
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
An Allen-Bradley product data sheet (publication 1745-2.2, January 1987) for the SLC 100 I/O expansion units: the basic unit, the relay output unit and the analog input unit. It explains how the units add I/O to an SLC 100 or SLC 150 processor unit, how I/O addresses are assigned, how to connect the interconnect cables, and how to wire inputs and outputs.
- Use
- Adds I/O circuits to an SLC 100 or SLC 150 processor unit, up to 112 I/O in all p. 1, 8
- Basic unit
- 10 input circuits and 6 relay (hard contact) output circuits p. 2
- Relay output unit
- No input circuits, 12 relay output circuits p. 1, 3
- Analog input unit
- 4 analog input circuits with 2 adjustable set points each, no outputs p. 1, 4
- Interconnect cable
- 1745-C2, 10-pin to 10-pin, supplied with each expansion unit; 18.5 inches (47 cm) p. 9
- SLC 150 cable
- 1745-C3, 20-pin to 10-pin, supplied with the SLC 150 processor unit; 18.5 inches (47 cm) p. 9
- Address blocks
- 112 I/O in 7 blocks of 10 inputs and 6 outputs; SLC 100 processor uses block 1, SLC 150 uses blocks 1 and 2 p. 6
- Analog voltage input
- +V to (-): 0 to +10 volts, differential; response time 3.5 milliseconds max p. 18
- Analog current input
- +I to (-): 0 to 20mA, differential; response time 3.5 milliseconds max p. 18
- Analog isolation
- 1500 volts minimum between input and control logic p. 18
- Terminals
- Self-lifting pressure plates; accept two #14 AWG wires p. 2
- Indicators
- Green DC POWER LED; red status LEDs for inputs, outputs or set points p. 2, 4
- Fuse
- Input power fuse behind the front cover p. 2
- Enclosure air
- Cooling air in the enclosure kept within 0 to 60°C p. 8
What this sheet walks you through
- Assigning I/O addresses to expansion units p. 6, 7
- Laying out units in the enclosure with spacing for cooling p. 8
- Installing the interconnect cables p. 9, 10
- Wiring digital inputs p. 11
- Wiring analog inputs and adjusting set points p. 12, 13
- Wiring relay outputs p. 14
- Protecting output contacts with surge suppression p. 15
Good to know
- Do not use interconnect cables longer than those supplied; longer cables could affect data communications and cause unsafe operation. p. 9
- High speed input modules can be used with the SLC 150 processor unit only. p. 8
- An open circuit at the source end of an analog input could make the input oscillate around the set point. p. 12
- On the basic unit, the 2 mA OFF state leakage figure for 24VAC circuits applies to inputs 1 and 2 only. p. 17
Questions this sheet answers
How many I/O can an SLC 100 system have with expansion units?
Up to 112 I/O, in 7 address blocks of 10 inputs and 6 outputs each. p. 6
Which cable connects an SLC 100 expansion unit to an SLC 150 processor?
Cable 1745-C3, supplied with the SLC 150 processor unit. Expansion units connect to each other with 1745-C2. p. 10
How do I adjust a set point on the 1745 analog input unit?
Apply the set point voltage or current, then turn the potentiometer with a screwdriver blade of 0.1 inch or less until its LED lights; clockwise increases the setting. p. 12
Can SLC 100 expansion units be used with an SLC 150 processor?
Yes. SLC 100 and SLC 150 expansion units can be connected to either an SLC 100 or an SLC 150 processor unit. p. 8
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1745-2.2, SLC 100 I/O Expansion Units1
- The Expansion Unit1
- Basic Expansion Unit2
- Relay Output Expansion Unit3
- Analog Input Expansion Unit4
- Installation Considerations5
- Mounting5
- Addressing I/O6
- System Layout8
- Connection Cables9
- Line Wiring Connections11
- Digital Input Wiring Connections11
- Analog Input Wiring Connections12
- Output Wiring Connections14
- Output Contact Protection15
- General Specifications16
- Input Specifications -Basic Expansion Unit17
- Input Specifications -Analog Input Expansion Unit18
- Output Specifications19
- Back Cover20