Manual · Allen-Bradley
Analog Input Module (Cat. No. 1771-IFE Series C) User Manual
Manual82 pagesPDF 727 KB
User manual for the Allen-Bradley 1771-IFE Series C analog input module: installation, block transfer programming, configuration and calibration.
Covers · 1 model
The models it covers
Summary
What is in it
The user manual for the Allen-Bradley 1771-IFE Series C analog input module, a single-slot block transfer module for 1771 I/O chassis. It covers module features, installation, configuration plugs and the Series A/B simulation jumper, wiring and grounding, block transfer programming for PLC-2, PLC-3 and PLC-5 processors, input ranges, data formats, filtering, scaling, reading status and input data, calibration and troubleshooting, with specifications and programming examples in the appendices.
Its parts
- Overview of the Analog Input Module
- Installing the Input Module
- Module Programming
- Configuring Your Module
- Module Status and Input Data
- Calibrating Your Module
- Troubleshooting Your Input Module
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
User manual for the Allen-Bradley 1771-IFE Series C analog input module, which reads up to 16 single-ended or 8 differential voltage or current inputs for programmable controllers with block transfer. It explains installation, configuration plugs, programming, diagnostics, troubleshooting and the specifications.
- Device
- Single-slot block transfer analog input module for any 1771 I/O chassis p. 9, 10
- Inputs
- 16 single-ended or 8 differential; voltage or current per input by configuration plugs p. 10, 15
- Voltage ranges
- +1 to +5V dc, 0 to +5V dc, -5 to +5V dc, -10 to +10V dc, 0 to +10V dc p. 61
- Current ranges
- +4 to +20mA, 0 to +20mA, -20 to +20mA p. 61
- Resolution
- 12-bit binary; 12 bits plus sign on bipolar ranges p. 61
- Backplane power
- 500mA @ +5V from the I/O chassis backplane; no external supply (passive transducers need user loop power) p. 10, 61
- Data formats
- Four-digit BCD or twelve-bit binary; selectable scaling to engineering units, digital filtering, real-time sampling p. 10
- Accuracy
- 0.1% of full scale range (at 25 C) p. 61
- Input impedance
- >10 Megohms (voltage ranges); 250 ohms (current ranges) p. 61
- Input protection
- Overvoltage 200V (voltage mode), 8V (current mode); overcurrent 30mA p. 61
- Internal scan rate
- 13.7ms for 8 differential, 27.4ms for 16 single-ended inputs; add 0.3ms for filtering p. 61
- Wiring arm and keying
- Wiring arm 1771-WG; keying between 10 and 12, between 24 and 26 p. 62
- Power dissipation
- 2.5 Watts maximum (8.52 BTU/hr) p. 61
- Series A/B replacement
- Series C has an A/B simulation switch to replace Series A or B modules p. 3
What this manual walks you through
- Choosing a slot and checking chassis power p. 14, 15
- Setting the configuration plugs for voltage or current inputs p. 15
- Transferring data with BTW and BTR block transfers p. 11, 12
- Reading the indicators and diagnostic status bits p. 51, 52
- Checking module operation in a simple test system p. 54
- Checking for common mode voltages p. 57
- Isolating a bad input p. 58
Good to know
- Not for use with the 1771-AL PLC-2/20, 2/30 Local Adapter. p. 9
- Do not mix single-ended and differential inputs on the module. p. 15
- Keep the module out of a module group with a discrete high density module, and away from ac or high voltage dc modules. p. 9
- Common mode voltage above +14.25V on any input can cause crosstalk and make all channel data invalid. p. 57
- Remove power from the chassis backplane and wiring arm before removing or installing input wiring. p. 58
Questions this manual answers
What input ranges does the 1771-IFE accept?
Five voltage ranges (+1 to +5V dc, 0 to +5V dc, -5 to +5V dc, -10 to +10V dc, 0 to +10V dc) and three current ranges (+4 to +20mA, 0 to +20mA, -20 to +20mA). p. 61
How much backplane current does the 1771-IFE need?
500mA from the backplane; add it to the other modules in the chassis to avoid overloading the power supply. p. 14
Can a 1771-IFE Series C replace a Series A or B module?
Yes. Series C has an A/B simulation switch so it can be used in place of Series A or B modules. p. 3
What does the red FAULT light on the 1771-IFE mean?
The module has detected a fault condition; on a self test fault, block transfers stop and the green RUN light goes out. p. 51
How is the 1771-IFE set when it ships?
From the factory it is set for voltage mode and Series C applications. p. 14
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-6.5.115, Analog Input Module, User Manual1
- Important User Information2
- Summary of Changes3
- Preface - Using This Manual7
- 1 - Overview of the Analog Input Module10
- 2 - Installing the Input Module13
- 3 - Module Programming27
- 4 - Configuring Your Module33
- 5 - Module Status and Input Data43
- 6 - Calibrating Your Module46
- 7 - Troubleshooting Your Input Module51
- A - Specifications61
- B - Differences Between Series A and B Modules and Series C Modules63
- C - Programming Examples64
- D - Data Table Formats68
- E - Block Transfer (Mini-PLC-2 and PLC-2/20 Processors)71
- F - Forms74
- Index77
- Allen-Bradley Publication Problem Report79
- Business Reply Card80
- Support Services81
- Back Cover82